Honeywell Home T6 Smart Thermostat Installation Guide

June 6, 2024
Honeywell Home

Honeywell Home T6 Smart Thermostat Installation Guide
Honeywell Home T6 Smart Thermostat

Compatible with 24-230V on/off and OpenTherm® appliances such as gas boilers, combi-boilers and heat pump. Also works with zone valve applications but not with electric heating (240V).

Turn OFF the power and remove the old thermostat

To ensure your safety, always make sure mains power is switched OFF before accessing wiring.

Before removing the old thermostat take a picture of the old thermostat’s wiring as reference then proceed to installation.

Turn OFF the power and remove the old thermostat

The T6 thermostat should not be placed near draughts, in direct sunlight or near heat sources. It should be at least 1.2 – 1.5 meters from the floor.

Maximum cable length between Receiver box and thermostat:
15m for 0.5mm² cable or 20m for 1.0mm² cable.

Must be installed by a competent person!
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.

Prepare Receiver Box for installation

Before installation of the Receiver Box

Find a suitable location near to the boiler.

Loosen the front screw to remove cover or tighten it when the cover is  back in place.

Prepare Receiver Box for installation

Needed during installation:

  • Cable with 2 wires from the Receiver Box (R4H810A) to thermostat.
  • Cable with 2 wires from the boiler to Receiver Box.
  • The Receiver Box requires 230V power

Install the Receiver Box

Please refer to the wiring diagrams over the page

  1. Wall box or Rear Wiring
    Hinge open the terminal block flap to access the cables and wall box screw holes.
    Install the Receiver Box
    Install the Receiver Box

  2. Surface wiring
    Use the cable clamps to secure the surface wiring.
    Install the Receiver Box

  3. Replace the cover
    Locate the hinges at the top of the cover and wall plate, close the cover and secure with the screw.

Install the T6 thermostat

Remember to use the same wires that you connected to the Receiver Box when connecting to the thermostat.

Install the T6 thermostat

  1. Using a screwdriver open wallplate terminal cover to connect wires
    Install the T6 thermostat

  2. Connect 2 thermostat wires to the T and T terminals and close cover.
    Install the T6 thermostat

  3. Attach the thermostat to the wallplate when finished.

Complete installation

  • Turn ON mains power to the Heating Appliance and Receiver Box.
    Complete installation

  • After power up, SETUP is displayed on the thermostat’s screen.
    Complete installation

Set Up and configuration

  1. Touch to begin setting up the thermostat.
    Set Up and configuration

  2. Select your language
    Set Up and configuration

  3. Set the clock format, time and date.
    Set Up and configuration

  4. Touch   to finalise setup. (  to setup using the App is currently unsupported)
    Set Up and configuration

Once setup is completed, if you need to change more settings go to the advanced menu. To access the advanced menu press for 5 seconds.

Set Up and configuration

In the advanced menu the following settings can be adjusted:

Menu Item Default Options
LANGUAGE English 0 = English, 1 = Français, 2 = Español 3 = Deutsch, 4 =

Nederlands, 5 = Italiano
OPENTHERM| –| OpenTherm boiler data when available
CYCLE RATE| 6| 3, 6, 9 or 12
MINIMUM ON TIME| 1 minute| 1, 2, 3, 4 or 5 minutes
HEAT RANGE| Min = 5.0ºC
Max = 35.0ºC| Min: 5ºC to 21ºC, Max: 21ºC to 35ºC
SCHEDULE OPTIONS| Daily| 1 = Daily schedule, 2 = 5+2 days schedule
EXTERNAL SENSOR| No sensor| 0 = No sensor, 1 = Room sensor
OPTIMISE| Opt. start OFF
Opt. stop OFF| Opt. start: 0 = OFF, 1 = ON, 2 = Delayed start
Opt. stop: 0 = OFF, 1 = ON
CLOCK| Format: 24h
Time: –:–
Date: 01/09/16| Clock format: 1 = 12h, 2 = 24h
Setup time and date
LOW LOAD CONTROL| ON| 0 = OFF, 1 = ON
TEMPERATURE OFFSET| 0.0ºC| -1.5 ºC to 1.5ºC
RESET| –| Factory, schedule, WiFi and HomeKit reset
FAILSAFE| OFF| 0 = OFF, 1 = ON

Wiring Diagrams

  1. Basic 230V boiler
    Wiring Diagram

  2. Combi boiler

  3. OpenTherm boiler
    Wiring Diagram
    For other wiring diagrams visit:
    Use For Scanning
    QR Code

  4. Two-port zone valve or S-plan
    Wiring Diagram

Customer Support

Need help? For assistance please visit: getconnected.honeywellhome.com
Resideo, 200 Berkshire Place, Winnersh Triangle, Berkshire RG41 5R
Phone: 0300 130 1299

Approvals
Hereby, Pittway Sarl declares that the radio equipment type T6 is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: https://hwllhome.co/DoC

Wi-Fi (2.4GHz): Max Power 100mW, 2.4–2.458GHz
ErP: Class V (+3%), (EU) 811/2013

WEEE Directive 2012/19/EC
Waste Electrical and Electronic Equipment directive
Dustbin Icon At the end of the product life dispose of the packaging and product in a
corresponding recycling centre. Do not dispose of the unit with the
usual domestic refuse. Do not burn the product.

Company Logowww.resideo.com

Pittway Sarl, Z.A. La Pièce 4,
1180 Rolle, Switzerland

Country of origin : UK

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell Home User Manuals

Related Manuals