Honeywell Home HCW 82 Home Wireless indoor Thermometer Devices Installation Guide
- June 6, 2024
- Honeywell Home
Table of Contents
HCW 82/HCF 82
Setpoint Adjuster HCW 82/
Room Temperature Sensor
HCF 82
Installation and Operation
Overview
The HCW 82/HCF 82 room devices are used for intelligent room temperature control. The room temperature sensor HCF 82 measures the room temperature and sends the measured values to other devices. The HCW 82 measures the room temperature and additionally allows the room setpoint temperature to be adjusted.
Application
The room devices transfer the data at 868.3 MHz. The data can be received by other devices such as the underfloor heating controller HCE 80/HCC 80/HCE 80R/ HCC 80R or the Hometronic Manager HCM 200D. Thus a large spectrum of applications can be covered – from individual room control to frost protection control.
Differences HCW 82/HCF 82
The HCW 82 has the following functions in addition to those of the HCF 82:
- Connection possibility for an external power supply unit (see “Operation with an external power source”, Page 9).
- Connection possibility for a window contact (see “Installing the window contact”, Page 10).
- Adjustment dial at which you can change the room temperature setpoint directly.
The adjustment range amounts to ± 12 °C, starting from the basic value of 20 °C (in position 0).
Scope of delivery
- 1 HCW 82/HCF 82
- 2 AA batteries
Commissioning
WARNING
Insufficient data transfer!
Interference of the radio receiver in the device through metallic objects or
further radio devices.
- Ensure there is sufficient distance to metallic objects.
- Mount the device with a distance of at least 1 m to radio devices such as radio headphones, cordless phones according to the DECT standard, etc.
- Select another installation site if the radio interference cannot be rectified.
- Remove the housing cover of the room temperature sensor (see Fig. 1).
- Insert the supplied AA batteries with the correct battery polarity (see Fig. 2).
The batteries have to be replaced when the red LED at the HCW 82/HCF 82 flashes (see “Changing batteries”, Page 10).
The setpoint adjuster HCW 82 can also be operated with an external power source instead of with batteries. Further information can be found in section “Operation with an external power source”, Page 9.
- Place the room temperature sensor at the installation site, but do not install it yet.
- Allocate the corresponding temperature zone to the HCW 82/HCF 82 (see “Teach-in”).
Teach-in
2.1.1. Assignment to underfloor heating controller
In order to assign a temperature zone to the HCW 82/ HCF 82, follow the
instructions from the chapter entitled “Start-up” in the “Underfloor heating
controller HCE 80/HCE 80R/ HCC 80/HCC 80R” installation instructions.
2.1.2. Assignment to Hometronic Manager
HCM 200D
In order to assign a temperature zone to the HCW 82/ HCF 82, follow the
instructions from the chapter entitled “Installing the HCW 82/HCF 82 and
assigning it to a room” in the Hometronic Manager HCM 200D operating
instructions.
2.1.3. Assigning an HCF 82 for frost protection function
The HCW 82/HCF 82 can only be assigned to the Hometronic Manager as a frost
protection sensor if the device switch HS 30 is used for the boiler request.
Proceed as follows in order to assign the HCF 82 as a frost protection sensor:
-
Press the Input button.
The Hometronic Manager is in the “Settings” menu. -
Go to the “Installation” menu.
-
Go to the “Boiler request” menu
-
Turn the Input button until the “Frost protect. sensor” is selected.
-
Press the input button.
The cursor flashes next to the “Frost protect. sensor”. The Hometronic Manager is ready to receive data from the sensor. -
Activate the teach-in function within 4 minutes by pressing the Send button at the room temperature sensor (see Fig. 2, Send button).
After successful teach-in, a * appears next to “Frost protect. sensor” in the display of the Hometronic Manager: The room temperature sensor is assigned to the Hometronic Manager for the frost protection function.
For information on how to read measured data of the room temperature sensor at the Hometronic Manager or adapt the threshold value for the frost protection function, please refer to the operating instructions of the Hometronic Manager.
2.1.4. Failed teach-in
If the teach-in has failed:
-
Improve the data transfer (see below).
-
Repeat the teach-in.
Improving the data transfer -
When selecting the operating site of each device ensure that the distance to radio devices such as radio headphones, cordless phones, etc. according to the DECT standard amounts to at least 1 m.
-
Do not install the devices over metallic wall connecting sockets and at least 30 cm away from the cover of the heat generator.
-
Correct the installation site of the room temperature sensor if necessary.
Installation
- Remove the batteries.
- Mark the drill holes according to the drilling template (see Fig. 3).
- Drill the holes.
- Screw on the room temperature sensor.
- Re-insert the batteries.
- Place the housing cover in position above and snap it down(see Fig. 4).
Particular features of HCW 82
Operation
The room setpoint temperature can be set easily at the setpoint adjuster HCW 82 by means of an adjustment dial. The adjustment range amounts to ± 12 °C, starting from the basic value of 20 °C (in position 0).
- Select the desired change of the preset temperature at the adjustment dial (1) (see Fig. 5) (settings on the scale in °C).
Limiting the adjustment range
You can limit the setting range that can be used at the adjustment dial.
- Remove the housing cover (see Fig. 1, Page 7).
- Place the two small pins into the holes of the adjustment dials in order to limit the adjustment range (see Fig. 6). Orientate yourself on the basis of the inner scale: In Fig. 6, the pins are inserted so that the adjustment dial can only be adjusted by ±3 °C around the zero point.
- Turn the adjustment dial clockwise until it stops.
- Check whether the adjustment dial is in the position shown in Fig. 5.
- If appropriate, put the adjustment back in, rotate by 180° until it has the position shown.
- Turn the adjustment dial to Position 0.
- Place the housing cover in position above and snap it down (see Fig. 4).
Operation with an external power source
In addition to battery operation, the setpoint adjuster HCW 82 is also
prepared for operation with an external power source.
WARNING Damage to the device!
Use of an unsuitable power supply unit.
- Use a power supply unit with 3 V DC ± 10%, min. 25 mA.
- Keep the power supply unit de-energized while connecting it.
- Observe the connection diagram next to the cable terminals.
- Have a power supply unit with 3 V DC ± 10 %, min. 25 mA at hand.
- De-energise the power supply unit.
- Remove the housing cover of the HCW 82 (see Fig. 1, Page 7).
- Remove the batteries.
Dispose of the batteries according to the local statutory requirements and not with the used domestic refuse.
- Unscrew the setpoint adjuster HCW 82.
The maximum permissible cable length from the power supply unit to the device amounts to 100 m. If possible, use a cable of the type JE-Y (ST)Y 2x2x0.8 mm or JE-LIYCY 2x2x0.5 mm2.
-
Lead the outlet cable of the power supply unit through the housing opening (1) (see Fig. 7) to the inside.
-
Connect the outlet cable to terminal (2) (see Fig. 7).
– Connection 2: Earth
– Connection 3: Voltage -
Screw the setpoint adjuster HCW 82 back on.
-
Place the housing cover in position above and snap it down (see Fig. 4).
Installing the window contact
- Connect any sensor with floating contact to the HCW 82 (installation to connection 1 and connection 2, seeFig. 7(2), Page 9).
- Assign the HCW 82 to the Hometronic Manager HCM 200D as a sensor (refer to the HCM 200D instructions “Assigning a room to a sensor”).
If several floating contacts are used, these have to be connected in series.
Changing batteries
Change the batteries if the red LED of the room temperature sensor flashes and the device is not in test mode.
- Remove the housing cover of the HCW 82/HCF 82 (see Fig. 1).
- Remove the batteries.
Dispose of the batteries according to the local statutory requirements and not with the used domestic refuse.
Always replace both batteries together.
Only use 1.5 V batteries of the type LR06, AA.
- Insert the batteries with the right polarity into the battery compartment (see Fig. 2).
- Place the housing cover on at the top and latch it in downwards (see Fig. 4).
Checking radio transmission
The HCW 82/HCF 82 can send a test signal to the allocated receiver (for example an underfloor heating controller) in order to test the signal strength.
-
Keep the teach-in button pressed for at least 30 s until the red LED extinguishes.
The device is now in test mode and sends a test signal every 5 seconds.
The LED flashes briefly at every test signal. -
Check the radio transmission at the receiver. Refer to the respective instructions for information about receiving and evaluating the test signals.
The test mode is terminated automatically after 5 minutes. The test mode can also be terminated by removing the batteries, disconnecting the power supply or by pressing the teach-in button.
Help with problems
Problem | Cause | Remedy |
---|---|---|
Teach-in failed | Batteries inserted incorrectly |
- Insert the batteries correctly.
Radio connection failure|
- Eliminate interference sources (metal, wireless devices).
- Correct installation site. . Repeat the teach-in.
No measured data at Hometronic Manager| Batteries inserted incorrectly|
- Insert the batteries correctly.
Radio connection failure|
- Eliminate interference sources (metal, wireless devices).
- Repeat the teach-in.
Module not assigned or assigned incorrectly|
- Repeat the teach-in.
- Check the assignment.
If appropriate, repeat.
Window contact is ignored| Window contact not assigned|
- Repeat the teach-in for the window contact.
Technical data
Batteries | 1.5 V, type LR06, AA |
---|---|
Power supply unit | 3 V DC ± 10 %, min. 25 mA |
Cable for power supply unit/window contact | Ø2×0.8 mm; 2×0.5 mm2 max. length |
100 m
Frequency| 868.3 MHz (transmitter)
WEEE directive 2002/96/ EC – Waste Electrical and Electronic Equipment directive
- At the end of the product, life disposes of the packaging and product in a corresponding recycling center.
- Do not dispose of the unit with the usual domestic refuse.
- Do not burn the product.