Honeywell Home T6590A Fan-Coil Controller Installation Guide
Installation
Wiring
Application 0: Two Pipes, Heating only
Application 1: Two Pipes, Cooling only
Application 2: Two pipes, Heating or Cooling, Manual changeover
Application 3: Two pipes, Heating or Cooling, Auto changeover
Application 4, 5 & 7 (T6590B ONLY / SEULEMENT T6590B / T6590B SOLTANTO /
SOLO T6590B): Four pipes, Heating & Cooling, Manual or Auto changeover
Application 6 (T6590B ONLY / SEULEMENT T6590B / T6590B SOLTANTO / SOLO
T6590B) : Two pipes, Heating or Cooling with Auxiliary electric heater
Applications
T6590A (2 Pipe Model)
Application
| Description| Changeover| Fan speed| Remote sensor|
Pipe sensor| Remote setback| Auxiliary Heater| Output type
---|---|---|---|---|---|---|---|---
0| 2 pipe system, heating only| –| ON/OFF, 1/2/3, AUTO| •| –| •| –|
ON, OFF
1
| 2 pipe system, cooling only| –| ON/OFF, 1/2/3, AUTO| •| –| •| –| ON, OFF
2
| 2 pipe system, 1 stage heat or 1 stage cool| Manual| ON/OFF, 1/2/3, AUTO| •| –| •| –|
ON, OFF
3
| 2 pipe system, 1 stage heat or 1 stage cool, auto changeover| Seasonal Changeover| ON/OFF, 1/2/3, AUTO| •| •| •| –|
ON, OFF
T6590B (4 Pipe Mode)
Application
| Description| Changeover| Fan speed| Remote sensor| Pipe sensor| Remote setback| Auxiliary Heater|
Output type
---|---|---|---|---|---|---|---|---
0
| 2 pipe system, heating only| –| ON/OFF, 1/2/3, AUTO| •| –| •| –| ON, OFF
1| 2 pipe system, cooling only| –| ON/OFF, 1/2/3, AUTO| •| –| •| –|
ON, OFF
2
| 2 pipe system, 1 stage heat or 1 stagecool| Manual| ON/OFF, 1/2/3, AUTO| •|
–| •| –| ON, OFF
3| 2 pipe system, 1 stage heat or 1 stage cool, auto changeover|
Seasonal Changeover
| ON/OFF, 1/2/3, AUTO| •| •| •| –|
ON, OFF
4
| 4 pipe system 1 stage heat and 1 stage cool| Manual| ON/OFF, 1/2/3, AUTO| •| –| •| –|
ON, OFF
5
| 4 pipe system 1 stage heat and 1 stage cool auto changeover| Auto
changeover| ON/OFF, 1/2/3, AUTO| •| –| •| –| ON, OFF
6| 2 pipe system, 1 stage heat or 1 stage cool with auxiliary electric
heater| Manual with seasonal changeover| ON/OFF, 1/2/3, AUTO| •| •| •| •|
ON, OFF
7
| 4 pipe system, mixed manual and auto| Manual / Auto changeover| ON/OFF, 1/2/3, AUTO| •| –| •| –|
ON, OFF
Installer Setup Mode
The T6590 is delivered with a set of pre-configured operational values that will allow the device to function immediately. However, in order to make the device compatible with a specific system, some of the internal settings may need to be changed. For information on the default values and the configurable options, please refer to the “Installer Parameter Table”.
-
To enter the Installer Setup Mode, press the ( ) and buttons together for 3 seconds.
-
To index between the individual Parameters, use the ( ) button. It is only possible to move upwards through the parameters.
-
To change a selected parameter, use the or button.
-
To save the altered settings, exit the Installer Setup Mode by Pressing the ( ) and buttons together for 3 seconds. NB: If the Installer Setup Mode is exited by time-out (approximately 120 seconds), then the newly changed values will not be saved.
Installer Parameters Table
Parameter No | Parameter | Setting |
---|---|---|
1 | System Type | 0 = 2 Pipe system Heat Only |
1 = 2 Pipe system Cool Only
2 = 2 Pipe system 1H1C manual changeove
3 = 2 Pipe system 1H1C auto changeover (default on T6590A)
4 = 4 pipe system with manual changeover (not available on T6590A)
5 = 4 Pipe system auto changeover (default on T6590B
6 = 2 pipe system 1H1C with Auxiliary Heater. Manual changeover
7 = 4 pipe system, mixed manual and automatic changeover (not available on
T6590A)
2| Valve output type| 0 = NO* ON/OFF (Default)
1 = NC ON/OFF
3| Sensor Type| 0 = Onboard Sensor (Default)
1 = Remote Sensor
4| Pipe sensor (Note: This item will be automatically populated based on
Parameter No.2)| 0 = NO input (Default = Heat
1 = NO input (Default = Cool)
2 = NC input (Default = Heat)
3 = NC** input (Default = Cool)
4 = Analogue input (Default) (NTC20K, T7414C1012)
5| Threshold for pipe sensor cooling| 10 – 18°C (Default)
6| Threshold for pipe sensor heating| 24 – 32°C (Default)
7| Fan control type
Fan stops in deadband
| 0 = Cycle or Constant (Default) (3 speed: Low->Med->High->Auto-> Low)
1 = Constant only (3 speed: Low->Med->High-> Low)
8| Dead band for four pipes| 1 – 5°C (Default = 2°C) (not available on T6590A)
9| Cycles Per Hour (CPH) value for heating| 1 – 12 CPH (Default)
10| Cycles Per Hour (CPH) value for cooling| 1 – 6 CPH (Default)
11| Cycles Per Hour(CPH) value for Auxiliary Heater| 1 – 12 CPH (Default)
12| Display Temperature adjustment| -2 to +2°C (Default)
13| Temperature Display mode| 0 = Room Temperature only
1 = Setpoint only
2 = Room Temperature and Setpoint (Default)
14| Heating setpoint Range Stops| 10 – 32°C (Default)
15| Cooling setpoint Range Stops| 10 – 32°C (Default)
16| Keypad Lockout| 0 = All keys available (Default)
1 = System button Locked out
2 = Fan and System button Locked out
3 = All buttons locked out
17| Remote setback| 1 = Hotel card NO*, with 1 second software delay going
from Unoccupied to Occupied; 2 minute delay going from Occupied to Unoccupied
2 = Hotel card NC*, with 1 second software delay going from Unoccupied to
Occupied; 2 minute delay going from Occupied to Unoccupied
3 = Hotel Card enabled, NO, with 1 second software delay going from
Unoccupied to Occupied; 30 minute delay going from Occupied to Unoccupied
4 = Hotel Card enabled, NC**, with 1 second software delay going from
Unoccupied to Occupied; 30 minute delay going from Occupied to Unoccupied
18| Remote setback heating setpoint| 10 – 21°C (Default)
19| Remote setback cooling setpoint| 22 – 32°C (Default)
20| Activity Sensing (If no key is pressed after a certain period which is
configured in this item, the system will enter Unoccupied mode)| 0 = Disabled
(Default)
1 = 4 Hour Sensing
2 = 12 Hour Sensing
3 = 24 Hour Sensing. NB: Anytime the thermostat is not touched (no single key
pressed), the thermostat will automatically fall back into Unoccupied
setpoints. When any key is pressed, thermostat controls to occupied mode
21| Freeze Protection| 0 = Disabled (Default)
21| 1 = Enabled – Thermostat Cycles On Heat when room temperature reaches 4°C
and disables Heat when room temperature reaches below 8°C. This feature can
not activate if the application is cool only
22| Auto Fan Reset| 1 = Reset back to Auto after 2 hours (Not allowed when
constant fan is selected in Parameter No.7). The start time is calculated
after the initial call for heat
2 = Reset back to Auto after 4 hours (Not allowed when constant fan is
selected in Parameter No.7). The start time is calculated after the initial
call for heat/cool
23| Fan run-on time after auxiliary heater is switched off| 0 – 600 Sec.
(Default)