netvox R718H Wireless Pulse Counter Interface User Manual
- June 6, 2024
- netvox
Table of Contents
netvox R718H Wireless Pulse Counter Interface
Copyright© Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property
of NETVOX Technology. It shall be maintained in strict confidence and shall
not be disclosed to other parties, in whole or in part, without written
permission of NETVOX Technology. The specifications are subject to change
without prior notice.
Introduction
R718H is the Wireless Pulse Counter Interface of Netvox ClassA type device based on LoRaWAN open protocol, compatible with LoRaWAN protocol.
LoRa Wireless Technology:
LoRa is a wireless communication technology famous for its long-distance
transmission and low power consumption. Compared with other communication
methods, LoRa spread spectrum modulation technique greatly extend the
communication distance. It can be widely used in any use case that requires
long-distance and low-data wireless communications. For example, automatic
meter reading, building automation equipment, wireless security systems,
industrial monitoring. It has features like small size, low power consumption,
long transmission distance, strong anti-interference ability and so on.
LoRaWAN :
LoRaWAN uses LoRa technology to define end-to-end standard specifications to
ensure interoperability between devices and gateways from different
manufacturers.
Appearance
Main Features
- Compatible with LoRaWAN
- Pulse counter
- Simple operation and setting
- External equipment of pulse voltage range is 2.4v~3.3
- 2 ER14505 lithium batteries in parallel power supply (3.6V / section)
- Protection class IP65
- Compatible with LoRaWANTM Class A
- Frequency hopping spread spectrum
- Configuration parameters can be configured via a third-party software platform, data can be read and alerts can be set via SMS text and email (optional)
- Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne
- Low power consumption and long battery life
Battery Life:
- Please refer to web: http://www.netvox.com.tw/electric/electric_calc.html
- At this website, users can find battery life time for variety models at different configurations.
- Actual range may vary depending on environment.
- Battery life is determined by sensor reporting frequency and other variables.
Set up Instruction
On/Off
Power on| Insert batteries. (users may need a flat blade screwdriver to open)
Turn on| Press and hold the function key for 3 seconds till the green
indicator flashes once.
Turn off (Restore to factory setting)| Press and hold the function key for 5
seconds till green indicator flashes for 20 times.
Power off| Remove Batteries.
Note:
| 1. Remove and insert the battery; the device is at off state by default.
2. On/off interval is suggested to be about 10 seconds to avoid the interference of capacitor inductance and other energy storage components.
3. At 1st to 5th second after power on, the device is in engineering test mode.
Network Joining
Never joined the network
| Turn on the device to search the network.
The green indicator stays on for 5 seconds: success The green indicator remains off: fail
Had joined the network (Not at factory setting state)
| Turn on the device to search the previous network. The green indicator stays on for 5 seconds: success
The green indicator remains off: fail
Function Key
Press and hold for 5 seconds
| Restore to factory setting / Turn off
The green indicator flashes for 20 times: success The green indicator remains off: fail
Press once
| The device is in the network: green indicator flashes once and sends a report
The device is not in the network: green indicator remains off
Sleeping Mode
The device is on and in the network
| Sleeping period: Min Interval.
When the reportchange exceeds setting value or the state changes: send a data report according to Min Interval.
Data Report
The device will immediately send a version packet report along with an uplink
packet including battery voltage and pulse count.
The device sends data in the default configuration before any configuration is
done.
Default Setting:
MaxTime: Max Interval = 60 min =3600s
MinTime: Max Interval = 60min = 3600s
BatteryChange = 0x01 (0.1v)
FilterTime = 0x02 (10ms)
Pulse Counter Clear Mode:
Pulse Counter has two mode to option
a. Clear When SEND:0x00 (default)
Clear the pulse count after reporting data packet
b. Clear When Roll-Over:0x01 (Enable the mode by command ConfigureCmd)
Accumulate each pulse count, it will clear pulse count reach 0xFFFF then
report an uplink packet (0xFFFF), and restart count. (When device reset or
reboot, it will clear pulse count data, too)
Note:
- The input pulse width is greater than 100ms to accurately count
- The device report interval will be programmed based on the default firmware which may vary.
- The interval between two reports must be the minimum time
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://www.netvox.com.cn:8888/page/index to resolve uplink data.
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
| Max Interval
(Unit:second)
|
Reportable Change
| Current Change≥
Reportable Change
| Current Change<
Reportable Change
---|---|---|---|---
Any number between
1~65535
| Any number between
1~65535
|
Can not be 0.
| Report
per Min Interval
| Report
per Max Interval
Example of ReportDataCmd
FPort:0x06
Bytes | 1 | 1 | 1 | Var(Fix=8 Bytes) |
---|---|---|---|---|
Version | DeviceType | ReportType | NetvoxPayLoadData |
Version– 1 bytes –0x01——the Version of NetvoxLoRaWAN Application Command
Version
DeviceType – 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType – 1 byte –the presentation of the
NetvoxPayLoadData ,according the devicetype NetvoxPayLoadData– Fixed
bytes (Fixed =8bytes)
Device | DeviceType | ReportType | NetvoxPayLoadData |
---|
R718H
|
0x1F
|
0x01
| Battery
(1Byte, unit:0.1V)
| PulseCount
(2byte)
| Reserved(5Bytes,fixed
0x00)
Uplink: 011F0124 00C8 0000000000 Pulse count = 200 ; C8 (Hex)=200 (Dec)
Example of ConfigureCmd
FPort:0x07
Bytes | 1 | 1 | Var(Fix =9 Bytes) |
---|---|---|---|
CmdID | DeviceType | NetvoxPayLoadData |
CmdID – 1 bytes
DeviceType – 1 byte – Device Type of Device
NetvoxPayLoadData – var bytes (Max=9bytes)
Description
|
Device
| Cmd
ID
|
DeviceType
|
NetvoxPayLoadData
---|---|---|---|---
Config
ReportReq
|
R718H
|
0x01
|
0x1F
| MinTime
(2bytes Unit:s)
| MaxTime
(2bytes Unit:s)
| BatteryChange
(1byte Unit:0.1v)
| Reserved
(4Bytes,Fixed 0x00)
Config
ReportRsp
|
0x81
| Status
(0x00_success)
| Reserved
(8Bytes,Fixed 0x00)
ReadConfigRepo
rtReq
|
0x02
| Reserved
(9Bytes,Fixed 0x00)
ReadConfigRepo
rtRsp
|
0x82
| MinTime
(2bytes Unit:s)
| MaxTime
(2bytes Unit:s)
| BatteryChange
(1byte Unit:0.1v)
| Reserved
(4Bytes,Fixed 0x00)
SetFilter
timeReq
|
R718H
|
0x03
|
0x1F
| FilterTime
(1byte,Unit:5ms)
| Reserved
(8Bytes,Fixed 0x00)
---|---|---|---|---|---
SetFilter
timeRsp
|
0x83
| Status
(0x00_success)
| Reserved
(8Bytes,Fixed 0x00)
GetFilter
timeReq
|
0x04
| Reserved
(9Bytes,Fixed 0x00)
GetFilter
timeRsp
|
0x84
| FilterTime
(1byte,Unit:5ms)
| Reserved
(8Bytes,Fixed 0x00)
SetPulseCounter ClearModeReq
|
0x05
| PulseCounterClearMode
(1Byte,0x00_Clear When SEND, 0x01_Clear When Roll-Over)
|
SetPulseCounter
ClearModeRsp
|
0x85
| Status
(0x00_success)
| Reserved
(8Bytes,Fixed 0x00)
GetPulseCounter
ClearModeReq
|
0x06
| Reserved
(9Bytes,Fixed 0x00)
GetPulseCounter ClearModeRsp
|
0x86
| PulseCounterClearMode (1Byte,0x00_Clear When SEND,
0x01_Clear When Roll-Over)
|
Reserved (8Bytes,Fixed 0x00)
-
Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v
Downlink: 011F003C003C010000000 003C(Hex) = 60(Dec)
Response:
811F000000000000000000 (Configuration success)
811F010000000000000000 (Configuration failure) -
Read Device Parameters Configuration:
Downlink: 021F000000000000000000
Response: 821F003C003C0100000000 (Current device parameter) -
Setting the FilterTime =100ms
Downlink: 031F140000000000000000 14(Hex) = 20(Dec), 20*5ms=100ms
Response: 831F000000000000000000 (Configuration success
831F010000000000000000 (Configuration failure) -
Read the FilterTime Configuration:
Downlink: 041F000000000000000000
Response: 841F140000000000000000 (Current device parameter) -
Setting the Pulse Counter Clear Mode = 0x01_Clear When Roll-Over
Downlink: 051F010000000000000000
Response: 851F000000000000000000 (Configuration success)
851F010000000000000000 (Configuration failure) -
Read the Pulse Counter Clear Mode Configuration:
Downlink: 061F000000000000000000
Response: 861F010000000000000000 (Current device parameter)
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
Example#2 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
Example#3 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
Notes :
- The device only wakes up and performs data sampling according to MinTime Interval. When it is sleeping, it does not collect data.
- The data collected is compared with the last data reported. If the data variation is greater than the ReportableChange value, the device reports according to MinTime interval. If the data variation is not greater than the last data reported, the device reports according to MaxTime interval.
- We do not recommend to set the MinTime Interval value too low. If the MinTime Interval is too low, the device wakes up frequently and the battery will be drained soon.
- Whenever the device sends a report, no matter resulting from data variation, button pushed or MaxTime interval, another cycle of MinTime/MaxTime calculation is started.
Filtering time
Pulse filtering time must be multiple of 5ms (can be set)
Installation
-
Wireless Pulse Counter Interface(R718H) has a built-in magnet (see Figure 1 below). When installed, it can be attached to the su rface of an object with iron which is convenient and quick. To make the installation more secure, use screws (purchased) to sec ure the unit to a wall or other surface (see Figure 2 below).
Note:
Do not install the device in a metal shielded box or in an en vironment with other electrical equipment around it to avoid af fecting the wireless transmission of the device. -
Wireless Pulse Counter Interface(R718H) is sent according to the maximum and minimum interval, and the count is automatically cleared after transmission
-
When the count reaches 65535 (0XFF), a report is automatically sent (sending value is 65535), and the report loop is restarted.
Note:-
Input pulse width greater than 100ms can be accurately counted
-
External pulse input level is not higher than 3.3V
Wireless Pulse Counter Interface (R718H)
It can also be applied to the following scenarios: -
Electric meter
-
Water meter
-
Gas Meter
-
Flow meter
When it is necessary to instrumentation equipment with pulse signal output
-
Note:
Please do not disassemble the device unless it is required to replace the
batteries.
Do not touch the waterproof gasket, LED indicator light, function keys when
replacing the batteries. Please use suitable screwdriver to tighten the screws
(if using an electric screwdriver, it is recommended to set the torque as
4kgf) to ensure the device is impermeable.
Information about Battery Passivation
Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density.
However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high. This lithium chloride layer prevents rapid self-discharge caused by continuous reaction between lithium and thionyl chloride, but battery passivation may also lead to voltage delay when the batteries are put into operation, and our devices may not work correctly in this situation.
As a result, please make sure to source batteries from reliable vendors, and the batteries should be produced within the last three months.
If encountering the situation of battery passivation, users can activate the battery to eliminate the battery hysteresis.
To determine whether a battery requires activation
Connect a new ER14505 battery to a 68ohm resistor in parallel, and check the voltage of the circuit. If the voltage is below 3.3V, it means the battery requires activation.
How to activate the battery
a. Connect a battery to a 68ohm resistor in parallel
b. Keep the connection for 6~8 minutes
c. The voltage of the circuit should be ≧3.3V
Important Maintenance Instruction
Kindly pay attention to the following in order to achieve the best maintenance of the product:
- Keep the device dry. Rain, moisture, or any liquid, might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.
- Do not use or store the device in dusty or dirty environment. It might damage its detachable parts and electronic components.
- Do not store the device under excessive heat condition. High temperature can shorten the life of electronic devices, destroy batteries, and deform or melt some plastic parts.
- Do not store the device in places that are too cold. Otherwise, when the temperature rises to normal temperature, moisture will form inside, which will destroy the board.
- Do not throw, knock or shake the device. Rough handling of equipment can destroy internal circuit boards and delicate structures.
- Do not clean the device with strong chemicals, detergents or strong detergents.
- Do not apply the device with paint. Smudges might block in the device and affect the operation.
- Do not throw the battery into the fire, or the battery will explode. Damaged batteries may also explode.
All of the above applies to your device, battery and accessories. If any device is not working properly, please take it to the nearest authorized service facility for repair.