MATelec FSA-60000 3V DC Battery Backup Photoelectric Smoke Alarm Instruction Manual

June 6, 2024
MATelec

MATelec FSA-60000 3V DC Battery Backup Photoelectric Smoke Alarm

Instruction Manual

MATelec FSA-60000 3V DC Battery Backup Photoelectric Smoke
Alarm.jpg

Compatible with the FSA-50000 Wireless Interconnect module
*Sold Separately.

Specifications

FIG 1 Specifications.JPG

THIS SMOKE ALARM MUST BE INSTALLED BY A LICENSED ELECTRICIAN IN ACCORDANCE WITH AUSTRALIAN WIRING RULES

This product must only be used for the purpose described in these instructions and must be installed in accordance with local wiring rules and regulations.

RECOMMENDED LOCATIONS FOR SMOKE ALARMS SUGGESTED SMOKE ALARM LOCATIONS.

  1. Smoke alarms must be installed in accordance with local and national regulations. Please check your State Fire Department requirements prior to installation.
  2. As a minimum, smoke alarms should be located between sleeping areas and potential sources of fire such as a kitchen, heater or basement. In single story homes with one sleeping area, an alarm should be installed in the hallway outside the room. In single story homes with two or more sleeping areas, a minimum one alarm for each area is required. In multilevel dwellings, an alarm should be installed outside and inside each sleeping area, in the basement, and on every level of the home.
  3. Smoke alarms are best installed as close to the centre of the ceiling as possible. As a minimum, the alarms should be located at least 30cm from walls. If wall mounted, it should be at least 30cm from the ceiling. (Diagram 1.)
  4. Larger rooms, in excess of 10m in length, should have multiple alarms installed.
  5. For buildings with a peaked, or cathedral type ceiling, the alarm musty be installed at least 50cm from the apex. (Diagram 2.)
  6. Do not mount the alarm on an external wall of a mobile home, as they may be subjected to
    excessive heat.

FIG 2 LOCATIONS FOR SMOKE ALARMS.JPG

FIG 3 LOCATIONS FOR SMOKE ALARMS.JPG

AVOID THESE LOCATIONS

  1. Kitchens or garages
  2. Any area subjected to relative humidity outside the range of 10%-93%, for example bathrooms
  3. Any area where the temperature may fall below 0°C or exceed 40°C.
  4. Within 1m of any heating or cooling vents
  5. In any bug or insect infested area
  6. In areas of excess dust
  7. Near fluorescent lights – electronic ‘noise’ may cause nuisance alarming

MOUNTING INSTRUCTIONS

  1. Isolate Mains/AC power.
  2. Select optimum location for your smoke alarm/s as per earlier details.
  3. Press the base on the installation position, mark installation holes of the bracket.
  4. Bore two 5mm holes on the markings and install mounting plugs. (See Diagram A)
  5. Follow wiring details as per Diagram D.
  6. Attach the base to the mounting plugs and fix screws into the plugs.(See Diagram B)
  7. Close the alarm body. (See Diagram C)

FIG 4 MOUNTING INSTRUCTIONS.JPG

Wiring Instructions:

FIG 5 Wiring Instructions.JPG

  • All interconnected alarms must be connected to the same sub/circuit
  • A common Neutral must be used for interconnect to function
  • Do not connect the interconnect wires to Active or Neutral

Status Description

FIG 6 Status Description.JPG

FIG 7 Status Description.JPG

Trouble Shooting

FIG 8 Trouble Shooting.JPG

If the problem still exists, please return to your retailers.
If the unit is out of warranty, please replace another new alarm.

Note: If self-test fault warning is existing, but the product can sound alarm when press test button. The product can continue to be used. Need to test weekly by press the test button instead of self-test weekly.

INSTALLING THE FSA-50000 MODULE AND UTILISING WIRELESS INTERCONNECT  (If applicable)

The FSA-50000 Wireless Module has been developed exclusively for the MATelec FSA-60000 and FSA-30000 Smoke Alarms. This enables both wired and wireless smoke detectors to be utilised in one installation. The FSA-60000 Smoke Detector is supplied separate to the FSA-50000 Module. Please contact your dealer for all enquiries. The FSA-60000 comes without the module installed. Only install the module if the alarm is being interconnected. If multiple units are being wire interconnected, then only 1 module per group of wired alarms should be installed.

  1. Isolate Mains/AC power.

  2. Select optimum location for your smoke alarm as per earlier details.

  3. Remove the ‘blank module’ from the smoke alarm.

  4. Insert the FSA-50000 Wireless Module in slot provided.

  5. Insert the battery and close the alarm. The alarm will automatically search for the module after being closed. The red LED flashes continuously while the unit checks if the module is installed.

  6. If no other alarms are found to pair with, the red LED will extinguish after 8 seconds, and unit will beep 3 times in quick succession. The red LED will then flash twice quickly, every 8 seconds. This indicates that while the module has been recognized, the unit is not yet paired.

  7. If module was not installed correctly, or otherwise not recognized by the alarm, the red LED will extinguish after 8 seconds, no beeps will be heard, and the red LED will not flash twice every 8 seconds.

  8. Repeat these steps with all alarms to be interconnected.
    PAIRING THE ALARM

  9. Press the TEST button of the first alarm 3 times in the space of 2 seconds. The Red LED should re main illuminated. This alarm remains the Master.

  10. Move to the next alarm and press the TEST button of this alarm 3 times in the space of 2 seconds. The red LED will illuminate briefly, and the unit will give one loud 0.5 second beep. The unit is now paired.

  11. Repeat this process with all remaining alarms to be paired.

  12. Return to the Master (first) alarm. The Red LED should still be illuminated. Press the TEST button for 1 second, to complete pairing.

  13. All paired units will have the red light flashing once every 40 seconds.

  14. Turn ON Main power

  15. To test the alarms, press the TEST button for at least 2 seconds. The unit will alarm, and the light will flash as long as TEST button is pressed.

  16. All other interconnected alarms should go through their test cycle, with a series of beeps, within a few seconds

The battery of alarms wirelessly interconnected should be replaced at a maximum, every 10 years.

CLEAR NETWORK
If it becomes necessary to unpair an alarm from a network, the following steps should be undertaken:

  1. Isolate Power and Remove the battery from the alarm.
  2. Press and hold the TEST button and reinsert the battery while the button is still pressed. The red LED will illuminate for 3 seconds.
  3. Release the TEST button, after Red LED goes off.
  4. The Red LED should light up again.
  5. Press the TEST button again, within 2 seconds, while the Red LED is illuminated, and release
  6. The alarm will beep once, and the red LED goes out. The alarm is now unpaired.

DEVELOP AN ESCAPE PLAN
As part of your plan, all family members should know and/or practice:

  1. The two quickest ways out of each room
  2. How to exit from upstairs, for homes with a second story. A rope or chain may be required.
  3. An agreed upon meeting place outside, such as the letterbox
  4. The sound of the smoke alarm and practice leaving your home when they hear it.
  5. A fire drill at least every six months including drills at nights. Practice allows you to test your plan before an emergency. You may not be able to reach your children. It is important that they know what to do!

WHAT TO DO IF THE ALARM SOUNDS

  1. Alert any small children and elderly persons.

  2. Leave immediately by your plan of escape. Every second counts, so don’t waste time getting
    dressed or picking up valuables.

  3. In leaving, don’t open any inside door without first feeling its surface. If hot, or if you see smoke seeping through cracks, don’t open that door! Instead, use your alternate exit. If inside door is cool, place your shoulder against it, open it slightly and be ready to slam it shut if heat and smoke rush in.

  4. Stay close to the floor if air is smoky. Breathe shallowly through a wet cloth if possible.

  5. Once outside, go to your selected meeting place and make sure everyone is there.

  6. Call the Fire Brigade on 000.

  7. Don’t return to your home until officials say that it is safe to do so. For further information on fire safety contact your local Fire Brigade.

SERVICE AND WARRANTY

  • The FSA-60000 smoke alarm is warranted for a period of 5 years, to be free of defects in materials or workmanship, under normal use. In the event of a warranty issue, please contact your place of purchase. Please see the warranty card included with the smoke alarm package, for full details of the warranty.

Read More About This Manual & Download PDF:

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MATelec User Manuals

Related Manuals