Altronix AL602ULADA NAC Power Extender User Guide
- June 6, 2024
- Altronix
Table of Contents
- AL602ULADA(J)
- R1002ULADA
- Application Guide
- 1. General Information (Use this in conjunction with respective
- 2. Class A and Class B Hookups:
- Dry Contact Input Wiring
- 3. Non-synchronizable NAC Appliances:
- 4. Using Multiple NAC Power Extenders from an FACP:
- 5. Synchronizing NAC Power Extender Using Built-in Sync Protocol:
- 6. Using a Single FACP Output:
- Output Programming Selection Table:
- Sync Mode Selection Table:
- AL602ULADA, AL802ULADA, AL1002ULADA
- AL602ULADAJ, AL802ULADAJ, AL1002ULADAJ
- R1002ULADA Enclosure Dimensions (H x W x D):
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AL602ULADA(J)
AL802ULADA(J)
AL1002ULADA(J)
NAC Power Extenders
R1002ULADA
Rack Mountable NAC Power Extender
Application Guide
(See Installation Guide for additional information)
More than just power.™
Rev. 062320
1. General Information (Use this in conjunction with respective
Installation Guide):
Altronix AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA, AL1002ULADAJ and R1002ULADA are very versatile devices. They can be used with or without specific synchronization modules provided by some manufacturers. Multiple units can be synchronized by using either the built-in sync mode or a external synchronization module. Please note, that only notification appliances with synchronization capabilities can be synchronized. Units can operate with either one (1) or two (2) outputs from the FACP.
2. Class A and Class B Hookups:
Units can be used with the outputs configured for:
- Two (2) Class A (Fig. 2a).
- Up to Four (4) Class B.
Fig. 2a
Two (2) Class A Hookups
NAC Loop 1 starts on Output 1 and terminates on Output 3. Switch SW1, when ON,
provides proper termination for this loop. NAC Loop 2 starts on Output 2 and
terminates on Output 4, SW2 must be turned ON for proper termination.
Please make sure that all the DIP switches for corresponding outputs are set
the same way.
- Two (2) Class B and one (1) Class A NAC circuits (Fig. 2b).
Fig. 2b
One (1) Class A, two (2) Class B Hookups
For combination of two (2) Class B and one (1) Class A circuit, only one (1) switch (SW1 or SW2) must be turned ON, terminating Class A circuit only.
Dry Contact Input Wiring
Fig. 2c
(A) Addressable Control
Module Trigger Output
Normally Closed Dry Contact
(Non-Supervised Class E)
3. Non-synchronizable NAC Appliances:
When using NAC appliances not designed to support synchronization feature, it is recommended to use separate output circuits for audible notification appliances (horns) and visual notification appliances (strobes). Set DIP switches for the visual notification appliances to follow Input 1 [IN1] and for audible notification appliances to follow Input 2 [IN2]. This will allow, when using two (2) outputs from the FACP, to support silencing of audible notification appliances. When using only one (1) FACP output, set all DIP switches to follow Input 1 [IN1]. The units outputs can each be set for the desired NAC drive signal, such as Code 3 or march time sequence (Output Programming Selection Table, pg. 6). Non-synchronizable Audible Appliances will follow the sequence, when feature is selected.
4. Using Multiple NAC Power Extenders from an FACP:
AL602/AL802/1002ULADA(J)/R1002ULADA units are designed to follow (replicate) the coded sequence, generated by a manufacturer’s sync module. One (1) or more units can be triggered. Connect the output of the FACP module to Input 1 and Input 2 Terminate the input circuit with the EOL or FACP, connecting it to terminals marked [RET +] and [RET- ], or continue the input circuit, connecting to terminals marked [RET +] and [RET- ] to [INP +] and [INP- ] of the next unit, when multiple units need to be triggered.
In case FACP does not have any synchronization capabilities and the sync mode is not used, the notification appliance synchronization will not be provided.
Fig. 4a
-
FACP with Sync Output
-
NAC Power Extender:
DIP switches set to Input to Output follower mode. -
NAC Power Extender:
DIP switches set to Input to Output follower mode.
(A) FACP (Fire Alarm Control Panel with sync capabilities)
(B) Compatible Special Application Devices. See Compatibility List
(C) To FACP EOL or next NAC power extender
(D) For Class A configuration return to FACP
CAUTION: Do not connect any notification appliances on the control circuit interconnecting FACP outputs (sync module outputs) and inputs of NAC Power Extenders. Applications that do not employ synchronization module or FACP with synchronization protocol will not provide NAC sycnchronization between NAC Power Extenders.
5. Synchronizing NAC Power Extender Using Built-in Sync Protocol:
AL602/AL802/1002ULADA(J)/R1002ULADA have built-in protocols to support Amseco, Gentex®, System Sensor®, Wheelock® two-wire synchronizable devices, therefore an external sync module is not required (Output Programming Selection Table, pg. 5). In these modes Input 1 is always used to activate visual notification appliances (strobes) and Input 2 is used to activate and silence audible notification appliances (strobes). Note: Input 1 has to be activated in all the configurations.
Fig. 5a
-
NAC Power Extender:
DIP Switches set for desired Sync Protocol (ex. Gentex®, System Sensor®, Amseco, CooperWheelock®). -
NAC Power Extender:
DIP Switches set for Input to Output Follower Mode
(A) FACP EOL For Class A Configuration return to FACP
When connecting, keep wires on different sides of the screws in order to maintain loop integrity supervision. DO NOT LOOP CONTINUOUS WIRE AROUND THE SCREW.
6. Using a Single FACP Output:
When only one FACP output is available, you may connect both Input 1 and Input
2 to it. Wire [RET1 +] and [RET1- ] to [INP2 +] and [INP2- ].
Both visual and audible notification appliances will be activated
simultaneously (Fig. 6a).
Fig. 6a
- Control Circuit NO Notification Appliances allowed
- EOL or Next Device
- For Class A configuration return to FACP
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 – OUT4)
Function | Switch Positions | Descriptions |
---|---|---|
ON | OFF | |
Input to Output Follower Mode | 1 | 2, 3 |
the corresponding input (i.e. FACP Sync module – maintains synchronization of
notification appliance circuit).
Temporal Code 3 Mode| 3| 1, 2| Enables Temporal Code 3 signal generation
output.
This mode will accept a steady or a pulsing input.
Steady Mode| | 1, 2, 3| A steady output signal will be generated.
This mode will accept steady or pulsing input.
For the above modes DIP Switch 4 determines which Input controls the
corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input
2.
AL800LGK9E Board
Output DIP Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN >OUT SYNC
Sync Mode Selection Table:
Function | Switch Positions | Descriptions |
---|---|---|
ON | OFF | |
Amseco Sync Mode* | 1, 3, 4 | 2 |
series of horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the strobe, and
allowing audible notification appliances (horns) and visual notification
appliances (strobes) to be silienced/ deactivated at the same time.
Gentex® Sync Mode*
Gentex is a registered trademark of Gentex Corporation.
| 1, 2, 3, 4| | This mode is designed to work with the Gentex® series of
horns, strobes, and horn/strobes to provide a means of synchronizing the
Temporal-coded horns, synchronizing the flash timing of the strobe, and
allowing audible notification appliances (horns) and visual notification
appliances (strobes) to be silienced/ deactivated at the same time.
System Sensor® Sync Mode*
System Sensor is a registered trademark of Honeywell.
| 1, 2, 4| 3| This mode is designed to work with the System Sensor® series of
horns, strobes, and horn/strobes to provide a means of synchronizing the
Temporal-coded horns, synchronizing the one-second flash timing of the strobe,
and allowing audible notification appliances (horns) and visual notification
appliances (strobes) to be silienced/deactivated at the same time.
CooperWheelock® Sync Mode*
CooperWheelock is a registered trademark of Cooper Wheelock.
| 2, 3, 4| 1| This mode is designed to work with the CooperWheelock series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the one-second flash timing of the strobe, and allowing audible notification appliances (horns) and visual notification appliances (strobes) to be silienced/deactivated at the same time.
*Note: AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA, AL1002ULADAJ and R1002ULADA will only synchronize horns, horn/strobes and strobes that contain synchronization capability. The same synchronization mode must be selected for all outputs.
AL602ULADA, AL802ULADA, AL1002ULADA
Enclosure Dimensions (BC400):
15.5″ x 12″ x 4.5″ (393.7mm x 304.8mm x 114.3mm)
AL602ULADAJ, AL802ULADAJ, AL1002ULADAJ
Enclosure Dimensions (BC600):
18″ x 14.5″ x 4.5″ (457.2mm x 368.3mm x 114.3mm)
R1002ULADA Enclosure Dimensions (H x W x D):
3.25″ x 19.0″ x 26.5″ (82.6mm x 482.6mm x 673.1mm). Shown with Z Bracket attached.
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056
website: www.altronix.com | e-mail:
info@altronix.com | Lifetime Warranty | Made in U.S.A.
02ULADA Application Guide
F23T
02 ULADA Application Guide