astro AX5835 Minima Slimline Fire Rated Instruction Manual
- June 6, 2024
- Astro
Table of Contents
MN MA SLILI.L
FIRE-RATED
PLEASE READ THE INSTRUCTIONS CAREFULLY BEFORE COMMENCING ASSEMBLY
Live: Normally Brown/ Red Neutral: Normally Blue/ Black
If the external cord of this luminaire is damaged, it must be replaced by the
manufacturer or a qualified person.
NOT SUITABLE FOR COVERING WITH THERMAL INSULATION.
FOR CEILING USE ONLY
Glare guard
CEILING TYPES
Ceiling lining secured directly to timber joists | Fire resistance periods to |
---|---|
Minimum 1 x 15 mm thick Type A or Type F gypsum wallboard to EN 520 | 30 |
minutes
Minimum 212.5 mm thick Type F gypsum Fireline to EN 520| 60 minutes
Minimum 312.5 mm thick Type F gypsum Fireline to EN 520| 90 minutes
These products are suitable to install in fire-protected timber floor and ceiling systems which have previously been successfully tested for at least 30 minutes, 60 minutes, or 90 minutes to EN 1365-2: 2014
JOIST TYPES
Solid softwood or hardwood timber joists manufactured from strength grade C16 or greater, installed at centers not exceeding 600 mm
TURN OFF POWER
1 downlight per 0.72m’: 1 meter minimum spacing
Read User Manual Online (PDF format)