IDEAL 61-657 Dual Range 12-to-1000V NCVT with Flashlight
Introduction
The IDEAL 61-657 Dual Range and 61-647 Single Range Non-Contact Voltage Testers automatically detect and indicate the presence of voltage within specified ranges. The 61-657 detects both low voltage (12 to 50 V AC) and standard voltage (50-1000V AC) via a selectable setting. The 61-647 detects standard voltage (50-1000V AC). Both testers provide non-contact detection of voltage through an antenna enclosed in plastic at the tip of the tester which senses the presence of the electromagnetic field present around live conductors. Each tester also has a flash light that works independently of the testing function and is activated by an independent On/Off button.
WARNING
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety procedures, wear proper PPE in accordance to NFPA 70E. Read and fully understand the instruction manual prior to using this product. Failure to comply can result in serious injury or death.
Contacting IDEAL INDUSTRIES, INC
To contact IDEAL INDUSTRIES, INC., call one of the following telephone
numbers:
IDEAL Industries USA Customer Service
- Phone Number: 800-435-0705
- Email: contactus@idealindustries.com
IDEAL Industries Canada Customer Service
- Phone Number: 905-683-3400
- Email: ideal_Canada@idealindustries.com
IDEAL Industries EMEA:
- Phone Number: +44 (0)1925 444 446
- Email: eur.sales@idealindustries.com
IDEAL Industries Australia:
- Phone Number: +61 3 9562 0175
- Email: InfoAUS@idealindustries.com
Or visit the IDEAL Electrical Website at
www.idealind.com
To register your product, find manuals, watch videos, simply scan this QR
code.
Safety Information
Warning – Identifies conditions and actions that could result in possible
death or serious injury if the hazard is realized.
Caution – Identifies conditions and actions that could result in tester
damage, equipment under test damage or data loss if the hazard is realized.
WARNING:
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety
procedures, wear proper PPE in accordance to NFPA 70E and follow the
guidelines below and the instructions in this manual when operating the
tester. Failure to comply can result in serious injury or death.
- Choking Hazard, Small Parts. Keep Away from Children Sharp Objects Hazard, This is not a toy. It is not for use or play by children. Keep Away from Children. Failure to do so can result in serious injury.
- Only experienced or technically competent consumers should use this equipment. When in doubt, call an experienced electrician to make any and all necessary repairs or installations. At all times, perform any necessary work on a de-energized circuit that has had its circuit breaker turned off and has been locked out.
- Use the Tester only as specified in this manual or protection provided by the Tester can be compromised.
- Before using the Tester, visually inspect it to ensure the case or tip are not cracked and the battery cap is securely in place. Do not use if the Tester appears damaged.
- When using the tester, keep fingers behind the tactile barrier at the base of the tester. (see #6 on page 9)
- This Tester is intended for use by qualified electricians and competent consumers. Follow NFPA 70E Standards for Electrical Safety when using this Tester.
- Do not use without the batteries correctly in place and the screw-on battery cap secured.
- Do not use Tester if it operates incorrectly as protection may be compromised. When in doubt, have the Tester serviced.
WARNING:
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety
procedures, wear proper PPE in accordance to NFPA 70E and follow the
guidelines below and the instructions in this manual when operating the
tester. Failure to comply can result in serious injury or death.
- Have the Tester serviced only by qualified service personnel.•
- Do not use the Tester around explosive gas, dust, or vapor, or during electrical storms, or in wet environments.
- Do not apply more than the rated voltage, as marked on the Tester. Observe CAT Rating of Tester when in use.
- To avoid false readings that can lead to electrical shock and injury, replace the batteries as soon as the low battery indicator appears.
- Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
- Do not work alone so that assistance can be rendered in an emergency.
- Use extreme caution when working around bare conductors or bus bars. Contact with the conductor could result in electric shock.
- Adhere to local and national safety codes. Individual protective equipment must be used to prevent shock and arc blast injury where hazardous live conductors are exposed.
- These are IP67 dust & water-resistant. Following any contact with water, thoroughly dry prior to subsequent use.
- Cancer and Reproductive Harm – www.P65Warnings.ca.gov
CAUTION:
Tester damage can occur if the following guidelines are not adhered to.
- Use the proper settings and voltage ratings for the measurement application.•
- Clean the case and accessories with a damp cloth and mild detergents only. Do not use abrasives or solvents. Make sure the tester is completely dry before use.
- Not intended for insertion into electrical outlet slots.
- Z` Do not apply excessive side or torsional loading to the sensing tip as damage may occur.
Symbols & Descriptions
NOTE: Tester must be used within the designated CAT Rating.
Operation
Identification and Description of Operating Functions for the 61-657 Dual Range 12 to 1000V NCVT w/ Flashlight and 61-647 Single Range 50 to 1000V NCVT w/ Flashlight:
- Power On/Off button (Dual Voltage Range Toggle for the 61- 657 Only)
- Audible Notification On/Off button
- Flashlight On/Off button
- Dual Voltage Range Indicator Light (61-657 Only)
- Dual Voltage Range Legend (61-657 Only)
- Tactile Barrier
- Non-Contact Voltage Sensing Tip
- Flashlight
- Industrial over-folded grip
- Pocket Clip
- Lanyard Tie off point
- Screw On/Off Battery Replacement Cap
Operating Features
Dual Voltage Range Sensing
The 61-657 is capable of sensing 2 different voltage ranges 50 to 1000V AC or
12 to 1000V AC. The low range setting allows the tester to be used to sense
the low voltages (12 to 50V AC) associated with doorbells, thermostats,
irrigation wiring, etc. The low range setting also allows sensing of standard
voltage in tamper-resistant outlets when the tip is located near the Hot
receptacle and/or
Hot Connection point on the outlet. (See Tester Operation – Dual Voltage Range
Sensing, for more information)
Audible Notification Disable
The tester can be operated with a visual-only indication of voltage when
working in noise-sensitive/noise restricted areas. With the tester On, press
the Speaker button for less than 1s. The tester will beep once to indicate the
audible warning is muted and only a visual indication will be provided. To
restore the audible warning, press the speaker button for less than 1s. The
tester will beep twice to indicate the audible warning is active and both a
visual and audible indication will be provided. The tester is set to Audible
Notification On as the default setting.
Flashlight
An LED Flashlight in the tip operates independently of the tester functions
and can be used to illuminate the work area. Press the Flashlight Button to
turn it On/Off. The tester is set to Flashlight Off. The Flashlight will Auto
Power Off after 5 minutes of no voltage detection. Further voltage detection
will reset the APO function to 5 minutes again.
Note: Use of the flashlight will decrease battery life.
Auto Power Off
After 10 minutes of inactivity (no button pressed and no signals detected),
the tester will emit one long beep (~0.5s) and then shut off. Note: if the
flashlight is on, it will be also shut off.
Low Battery Indication
If the battery voltage is less than around 2.4V, the green led in the tip will
flash 3 times and the buzzer will send out one long beep, then turn off the
device.
Tester Operation
Turning The Tester On
Press the Power On/Off button for less than 1s to turn the tester On. The
tester will beep twice, and will light a steady Green LED in the tip of the
tester to indicate Power On. The High Voltage Sensing Mode will be activated
(Default Range) and indicated by lighting a steady Red Dual Voltage Range
Indicator Light.
Dual Voltage Range Sensing
Short presses on the power button toggle the voltage sensing range between 50
to 1000V AC and 12 to 1000V AC. The tester defaults to the High Voltage
Sensing Mode (50 to 1000V AC) when the unit is turned on and is indicated by a
steady Red Indicator Light. Pressing the Power button for less that 1s will
switch the tester to the Low Voltage Sensing Mode (12 to 1000V AC) and is
indicated by a steady Blue Indicator Light.
Turning The Tester Off
Press the Power On/Off button for more than 1s (>2s for the 61-657) to turn
the tester Off. Listen for a long steady beep (~.5s) and watch for LED in the
tip to turn off and for the Range Indicator Light to turn Off. The tester is
now deactivated and is not operational.
Checking for The Presence of AC Voltage
Prior to use, test on known live circuit to verify tester functionality. Place
tip of the tester near an AC voltage source and refer to the NCV Sensing
Indications Table for tester indication during operation.
While the NCV is a helpful function, it is ALWAYS RECOMMENDED that the operator verify that any electrical conductor is completely de-energized and that no voltage is present by measuring for voltage AND CONFIRMING THAT NO VOLTAGE IS PRESENT and that all applicable PPE and lock out tag out procedures be followed before attempting any work on ANY electrical distribution system. Voltages with frequencies higher than 60Hz or electrostatic charges may also be detected by the NCV sensing antenna. Due to the variability of designs across device manufacturers the 61-647 may not detect the presence of voltage in Tamper Resistant Outlets. The 61-657 should be placed in the low voltage detection mode (blue LED) in order to sense the presence of voltage in Tamper Resistant Outlets.
NCV Sensing Indications Table
NCV
Indications
| Ranges (V AC)
---|---
Mode| 12-25V| 26-34V| 35-45V| 46-54V| 55-1000V
Low
(12-1000V AC)
(Audible Notification) (61-657 Only)
| ****
Red Flashing Light in Tip and beeps @ 2Hz
| ****
Red Flashing Light in Tip and beeps from 2Hz to 4Hz
| ****
Red Flashing Light in Tip and beeps @ 4Hz
| ****
Red Flashing Light in Tip and beeps from 4Hz to 12 Hz
| ****
Red Flashing Light in Tip and beeps @ 12Hz
High
(50-1000V AC)
(Audible Notification)
| ****
No Light in Tip, No beeps
| ****
No Light in Tip, No beeps
| ****
Red Flashing Light in Tip and beeps @ 2Hz
| Red Flashing Light in Tip and beeps from 2Hz to 12 Hz| ****
Red Flashing Light in Tip and beeps @ 12Hz
Low
(12-1000V AC)
(Audible Notification Disabled)
(61-657 Only)
| ****
Red Flashing Light in Tip @ 2Hz, No beeps
| ****
Red Flashing Light in Tip from 2Hz to 4Hz, No beeps
| ****
Red Flashing Light in Tip @ 4Hz, No beeps
| ****
Red Flashing Light in Tip from 4Hz to 12Hz, No beeps
| ****
Red Flashing Light in Tip @ 12Hz, No beeps
High
(50-1000V AC)
(Audible Notification Disabled)
| ****
No Light in Tip, No beeps
| ****
No Light in Tip, No beeps
| ****
Red Flashing Light in Tip @ 2Hz, No beeps
| ****
Red Flashing Light in Tip from 2Hz to 12Hz, No beeps
| ****
Red Flashing Light in Tip @ 12Hz, No beeps
Note: Indications above may be subject to variability caused by humidity, insulation thickness, distance, and other factors.
Functions Operation Table
Indication | Response | Default Function | Operation |
---|---|---|---|
On Off | Meter On | RED LED | Push Button |
Audible | Beeps | On | Push Button |
Flashlight | Flashlight On | Off | Push Button |
Sensing Range | Red LED | High Range | Push Button |
Functions Indication Table
Function | Description |
---|---|
Power On | Steady Green light in Tip, 2 Short Beeps |
Power Off | No Light, Long Beep |
Tester Auto Power Off | Green Light Flashes, 1 Beep |
Red LED | 50-1000V AC Range |
Blue LED | 12-1000V AC Range |
Audible OFF | One Beep |
Audible ON | Two Beeps |
Flashlight Button | Flashlight On or Off |
Electrical Specifications
Function | Range |
---|---|
AC Voltage Sensing High Mode | 50V AC to 1000V AC |
AC Voltage Sensing Low Mode (61-657 Only) | 12V AC to 1000V AC |
Frequency | 50Hz or 60Hz |
Operating Temperature: | 32ºF to 104ºF (0ºC to 40ºC) (<80%RH) |
--- | --- |
Operating Altitude: | 6500 ft (2000 m) |
Storage Temperature: | 14ºF to 122ºF (-10ºC to 50ºC) (<80%RH) |
Mechanical Specifications
Dimensions: (L x W x H)| 6.4 in. x 1.0 in. x 1.2 in. (166 mm x 26.3 mm x 31
mm)
---|---
Weight:| 0.16 LBS (0.08 KG)
Power Source:| (2) 1.5V AAA Batteries
Ingress Protection Rating:| IP67 dust and water-resistant
Flashlight:| >500LUX @ 4.0 in
EMC/EMI
CISPR 22 3rd Edition. Class B Limits. EN 55032
CISPR 32
CISPR 11
FCC 15. 107 with reference to Section 15.109 (g).
ICES-003
EN 61326-2-2 Sec 6.4.
USA (FCC)
47 CFR 15 subpart B. This product is considered an exempt device per clause
15.103.
Safety
Complies with the following:
IEC 61010-1, Edition 3 (2010-06) +AMD1 (2016-12)
ANSI/UL/IEC EN 61010-1, Edition 3 (2016-04-29)
CSA-C22.2 No. 61010-1-12 Edition 3 (2019-07-19)
IEC 60529
Overvoltage CAT IV 1000V.
Any voltages exceeding the defined maximum voltage measurement categories
described above are outside the normal use of the equipment and protection
cannot be guaranteed.
Pollution Degree Class 2
Maintenance and Service
Tester Inspection
Before using the Tester, visually inspect it to ensure the case or tip are not
cracked and the battery cap is securely in place. Do not use if the Tester
appears damaged.
Battery Inspection/Replacement
Maintenance and Storage
When not in use, turn the meter off. If the tester will not be used for more
than a month remove the batteries for storage. Clean the case with a damp
cloth and mild detergent. Do not use abrasives or solvents. If the meter is
exposed to water ensure the tester is completely dry before use. Do not expose
to chemicals or solvents.
Service and Replacement Parts
This unit has no user-serviceable parts.
Disposal of Waste, Electrical & Electronic Equipment
In order to preserve, protect and improve the quality of the environment,
protect human health and utilize natural resources prudently and rationally,
the user should return the unserviceable product to relevant facilities in
accordance with statutory regulations. The crossed-out wheeled bin indicates
the product needs to be disposed separately and not as municipal waste.
Do not dispose of this product as unsorted municipal waste. It must be
properly disposed of in accordance with local regulations. Please see
www.epa.gov or
www.erecycle.org for additional information.
Disposal of Used Batteries/Accumulators There are no batteries in this
product.
TWO YEAR LIMITED WARRANTY
This tester is warranted to the original purchaser against defects in material
and workmanship for a period of two (2) years from date of purchase. With
proof of purchase from an authorized IDEAL distributor, a defective tester
will be repaired or replaced with the same product or a functionally
equivalent product, at the option of IDEAL INDUSTRIES, INC. during the
warranty period, subject to verification
of the defect or malfunction. Warranty does not cover consumables such as
fuses, batteries, and excludes defects caused by leakage from batteries,
abuse, mishandling, dropping, ordinary wear and tear, misuse, neglect,
unauthorized repair, improper use, alterations, accidents or any causes beyond
IDEAL’s reasonable control. Consequential or incidental damages are not
recoverable under this warranty. Some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you. This LIMITED WARRANTY gives you specific legal
rights, which vary from state to state. This warranty constitutes the sole and
exclusive remedy of the purchaser and the exclusive liability of IDEAL, and is
in lieu of any and all other warranties, and expressly disclaims all other
warranties, implied, or statutory as to merchantability, fitness for purpose
sold, description, quality productiveness, or any other matter. No agent,
distributor or other supplier has the authority to modify or amend this
warranty or make other representations or warranties other than those
contained in this warranty without express written authorization from IDEAL.
For warranty service, call IDEAL customer service at
1-800-435-0705.
Made in China.
Scan the barcode on the right to see the new IDEAL T &M Product Line
IDEAL INDUSTRIES, INC. Sycamore, IL 60178, U.S.A. 800-435-0705 www.Idealind.com ND 9110-1