IDEAL 61-547 AC/DC Test and Measurement Voltage Indicator Instructions
- June 6, 2024
- IDEAL
Table of Contents
IDEAL® Test and Measurement
61-547 AC/DC Voltage Indicator
Introduction
The IDEAL 61-547 AC/DC Voltage Indicator is an auto indicating tester that indicates the voltage level in predetermined steps via integral leads. It auto-selects AC or DC voltage from 24 to 600 AC and 12 to 600 DC and also indicates DC polarity.
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety procedures, wear proper PPE in accordance to NFPA 70E. Read and fully understand the instruction manual prior to using this product. Failure to comply can result in serious injury or death.
Contacting IDEAL INDUSTRIES, INC.
To contact IDEAL INDUSTRIES, INC., call one of the following telephone numbers:
IDEAL Industries USA Customer Service
- Phone Number: 800-435-0705
- Email: contactus@idealindustries.com
IDEAL Industries Canada Customer Service
- Phone Number: 905-683-3400
- Email: ideal_Canada@idealindustries.com
IDEAL Industries EMEA
- Phone Number: +44 (0)1925 444 446
- Email: eur.sales@idealindustries.com
IDEAL Industries Australia
- Phone Number: +61 3 9562 0175
- Email: InfoAUS@idealindustries.com
Or visit the IDEAL Electrical Website at
www.idealind.com
To register your product, find manuals, watch videos, simply scan this QR
code.
Safety Information
Warning – Identifies conditions and actions that could result in possible
death or serious injury if the hazard is realized.
Caution – Identifies conditions and actions that could result in meter
damage, equipment under test damage or data loss if the hazard is realized.
WARNING
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety procedures,
wear proper PPE in accordance to NFPA 70E and follow the guidelines below and
the instructions in this manual when operating the meter. Failure to comply
can result in serious injury or death.
- Choking Hazard, Small Parts. Keep Away from Children. Sharp Objects Hazard, This is not a toy. It is not for use or play by children. Keep Away from Children. Failure to do so can result in serious injury.
- Only experienced or technically competent consumers should use this equipment. When in doubt, call an experienced electrician to make any and all necessary repairs or installations. At all times, perform any necessary work on a de-energized circuit that has had its circuit breaker turned off and has been locked out.
- Use the Meter only as specified in this manual or protection provided by the Meter can be compromised.
- Before using or connecting the Meter, visually inspect it to ensure the cases are not cracked and the back case is securely in place. Do not use if the Meter appears damaged.
- Before using the test leads, inspect carefully for damaged insulation, exposed metal or cracked probes. Check test leads for continuity. Do not use leads if they appear damaged.
- Use only approved test leads. Do not use improvised connections that could present a safety hazard.
- When using the probes, keep fingers behind the finger guards on the probes.
- Connect the common test lead before connecting the live test lead. When disconnecting test leads, disconnect the live test lead first.
- This Meter is intended for use by qualified electricians. Follow NFPA 70E Standards for Electrical Safety in the Workplace when using this Meter.
- Do not use Meter if it operates incorrectly as protection may be compromised. When in doubt, have the Meter serviced.
- When servicing the Meter, use only specified replacement parts.
WARNING
Arc Flash and Shock Hazard, Proper PPE Required. Follow all safety procedures, wear proper PPE in accordance to NFPA 70E and follow the guidelines below and the instructions in this manual when operating the meter. Failure to comply can result in serious injury or death.
- Have the Meter serviced only by qualified service personnel?
- Do not use the Meter around explosive gas, dust, or vapor, or during electrical storms, or in wet environments.
- When measuring, keep fingers behind the Tactile Barrier. See “The Meter” on pg. 8 and 9.
- Do not apply more than the rated voltage, as marked on the Meter, between the terminals or between any terminal and earth ground.
- Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
- Always ensure that test leads are secured so that they cannot be accidentally snagged or tripped over.
- Do not work alone so that assistance can be rendered in an emergency.
- Use extreme caution when working around bare conductors or bus bars. Contact with the conductor could result in electric shock.
- Adhere to local and national safety codes. Individual protective equipment must be used to prevent shock and arc blast injury where hazardous live conductors are exposed.
- These meters are IP42 dust & water-resistant. Following any contact with water, thoroughly dry meter and test lead prior to subsequent use.
- ****Cancer and Reproductive Harm –www.P65Warnings.ca.gov
CAUTION
Meter damage, equipment under test damage or data loss can occur if the following guidelines are not adhered to.
- Use the proper terminals, function, and range for the measurement application.
- Clean the case and accessories with a damp cloth and mild detergents only.
Do not use abrasives or solvents. Make sure the meter is completely dry before use.
Symbols & Descriptions
SYMBOL | DESCRIPTION |
---|---|
Arc Flash and Shock Hazard | |
Shock Hazard | |
**** | Warning or Caution |
Choking Hazard | |
AC (Alternating Current) | |
DC (Direct Current) | |
Earth Ground | |
CAT III | IEC Measurement Category III |
CAT III has protection against transients in equipment in fixed-equipment
installations such as distribution panels feeders, and short branch circuits.
Also included are lighting systems in larger buildings.
V| Voltage AC or DC
| Double Insulation
| Do not dispose of this product as unsorted municipal waste. It must be
properly disposed of in accordance with local regulations. Please see
www.epa.gov or mwarecycle.org for additional information.
| Conforms to applicable North American Safety Standards
| Conforms to applicable Australian Safety Standards
| Conforms to European Directives
NOTE: The Measurement Category (CAT) and voltage rating of any combination of test probe, test probe accessory, current clamp accessory, and the Meter is the LOWEST rating of any individual component.
Operation
Identification and Description of Operating
Functions for the 61-547 AC/DC Voltage Indicator:
- DC Volts Level Indication
- Tactile Barrier
- DC Volts Polarity Indication
- Probe Holders
- Integral 18-inch Test Leads
- Ergonomic Non-Slip Grip
- AC Volts Indication
- PPE Level Marker
- AC Volts Levels Indication
- Hanging Strap Clip
Operating Features
High Voltage Warning (HI-V)
The meter indicates PPE by showing a PPE warning on the meter face. When
measuring >36V AC on the VAC function and >36V DC when on the VDC function.
Using Test Leads
WARNING: Arc Flash and Shock Hazard, Proper PPE Required.
Follow all safety procedures, wear proper PPE in accordance to NFPA 70E and
follow the guidelines below and the instructions in this manual when operating
the meter with the integral test leads. Test Leads must be rated for the
electrical environment the meter is being used in and have a voltage rating of
at least the voltage of the circuit to be measured. Failure to comply can
result in serious injury or death.
- Choking Hazard, Small Parts. Keep Away from Children. Sharp Objects Hazard, This is not a toy. It is not for the use or play by children. Keep Away from Children. Failure to do so can result in serious injury.
- These meters are IP42 dust & water-resistant. Following any contact with water, thoroughly dry meter and test lead prior to subsequent use.
CAT II 600V, (with a cap on)
WARNING:
- Use only approved test leads. Do not use improvised connections that could present a safety hazard.
- Prior to using the test leads, inspect them carefully for damaged insulation, exposed metal or bent probes. Check test leads for continuity. Do not use leads if they appear damaged.
- When using the probes, keep fingers behind the finger guards on the probes.
- Connect the common test lead before connecting the live test lead. When disconnecting test leads, disconnect the live test lead first.
- Always ensure that test leads are secured so that they cannot be accidentally snagged or tripped over.
This meter has integral test leads. They are not replaceable. The lead set must comply with requirements for Overvoltage and Measurement Categories CAT III 600V.
Meter Operation
Measuring AC ( ) or DC ( ) Voltage
Functions Operation Table
Indication | Response | Default Function | Operation |
---|
Illuminated
Light| ACV/DCV| ACV| Auto selects AC or DC voltage and indicates DC polarity.
Functions Indication Table
Function | Description |
---|---|
PPE | Visual indication that you have exceeded 36 volts AC or DC |
ACV
Indication| Visual confirmation of the detection of AC voltage
DC V
Indication| Visual confirmation of the detection of DC voltage
DC Polarity| DC polarity indication via “+” or “2
Electrical Specifications
Function | Range | Steps | Accuracy |
---|---|---|---|
61-547 | ±(a%+b) | ||
AC Voltage (V) | 24-600V | 24, 48, 120, 208, 240, | |
277, 480, 600 steps | N/A | ||
DC Voltage (V) | 12-600V | 12, 24, 36, 48,110, | |
220, 380, 600 steps | N/A | ||
- Overload Protection: 600VRMS AC/DC.
- Voltage level indication is approximate. We recommend using a digital multimeter if a precise reading is required.
Operating Temperature: | 32ºF to 104ºF (0ºC to 40ºC) (<80%RH) |
---|---|
Operating Altitude: | 6500 ft (2000 m) |
Storage Temperature: | 14ºF to 122ºF (-10ºC to 50ºC) (<80%RH) |
Intended for indoor use.
Mechanical Specifications
Dimensions: (L x W x H)| 6.12 in. x 2 in. x 1.7 in. (155.5 mm. x 50 mm. x 42
mm.)
---|---
Weight:| 0.29 LBS (0.13 KG)
Display:| 8 Segment LEDs
Power Source:| No Batteries Required
Ingress Protection Rating:| IP42 dust and water-resistant
EMC/EMI
CISPR 22 3rd Edition. Class B Limits.
EN 55032
CISPR 32
CISPR 11
FCC 15. 107 with reference to Section 15.109 (g).
ICES-003
EN 61326-2-2 Sec 6.4.2.101
USA (FCC)
47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Safety
Complies with the following:
IEC 61010-1, Edition 3 (2010-06) +AMD1 (2016-12)
ANSI/UL/IEC EN 61010-1, Edition 3 (2016-04-29)
CSA-C22.2 No. 61010-1-12 Edition 3 (2019-07-19)
IEC 61010-031 Hand-held Probe Assemblies (2015-05)+AMD1(2018-05)
IEC 61010-2-033 (2019-06)
UL1436
Overvoltage CAT III 600V.
Any voltages exceeding the defined maximum voltage measurement categories
described above are outside the normal use of the equipment and protection
cannot be guaranteed.
Pollution Degree Class 2
Maintenance and Service
Equipment Maintenance and Service
Meter Inspection
Do not use if meter appears damaged. Visually inspect the meter to ensure the
case and jaws are not cracked.
Test Lead Inspection
Inspect and replace test leads if insulation is damaged, metal is exposed, or
probes are cracked. Pay particular attention to the insulation surrounding the
connectors.
Battery Inspection/Replacement
This unit uses no batteries.
Maintenance and Storage
Switch off and disconnect the meter completely before carrying out any
maintenance. Clean the case with a damp cloth and mild detergent. Do not use
abrasives or solvents. Keep away from liquids and ensure the meter is
completely dry before use.
Service and Replacement Parts
This unit has no user-serviceable parts.
Probe Storage
Disposal of Waste, Electrical & Electronic Equipment
In order to preserve, protect and improve the quality of the environment,
protect human health and utilize natural resources prudently and rationally,
the user should return the unserviceable products to relevant facilities in
accordance with statutory regulations. The crossed-out wheeled bin indicates
the product needs to be disposed of separately and not as municipal waste.
Do not dispose of this product as unsorted municipal waste. It must be
properly disposed of in accordance with local regulations. Please see
www.epa.gov or
www.erecycle.org for additional information.
Disposal of Used Batteries/Accumulators
There are no batteries in this product.
TWO YEAR LIMITED WARRANTY
This tester is warranted to the original purchaser against defects in material
and workmanship for a period of two (2) years from the date of purchase. With
proof of purchase from an authorized IDEAL distributor, a defective tester
will be repaired or replaced with the same product or a functionally
equivalent product, at the option of IDEAL INDUSTRIES, INC. during the
warranty period, subject to verification of the defect or malfunction.
Warranty does not cover consumables such as fuses, batteries, and excludes
defects caused by leakage from batteries, abuse, mishandling, dropping,
ordinary wear, and tear, misuse, neglect, unauthorized repair, improper use,
alterations, accidents, or any causes beyond IDEAL’s reasonable control.
Consequential or incidental damages are not recoverable under this warranty.
Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation or exclusion may not apply to
you. This LIMITED WARRANTY gives you specific legal rights, which vary from
state to state. This warranty constitutes the sole and exclusive remedy of the
purchaser and the exclusive liability of IDEAL, and is in lieu of any and all
other warranties, and expressly disclaims all other warranties, implied, or
statutory as to merchantability, fitness for the purpose sold, description,
quality productiveness, or any other matter. No agent, distributor, or other
supplier has the authority to modify or amend this warranty or make other
representations or warranties other than those contained in this warranty
without express written authorization from IDEAL. For warranty service, call
IDEAL customer service at
1-800-435-0705.
Made in China.
References
- U.S. Environmental Protection Agency | US EPA
- Electronic Waste Management - CalRecycle Home Page
- P65Warnings.ca.gov
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>