AERECO S-CO2 Ambient Air Sensor Instruction Manual
- June 6, 2024
- AERECO
Table of Contents
CO2 AMBIENT AIR SENSOR
INSTALLATION AND OPERATING INSTRUCTIONS
DESCRIPTION
This module measures carbon dioxide (CO2) in the range of 0 to 2 000 ppm and is equipped with a low consumption sensor. The sensing element uses the NDIR Infra-Red technology (no cross-sensitivity to any other gas than CO2) and is self-calibrated: a dual-beam measurement enables the module to be used in any kind of room occupancy (no CO2 back to bottom level needed). Output signal: Analog (0-10V).
APPLICATIONS
- HVAC: Demand Controlled Ventilation, fan control, damper control, air conditioning control, CO2 level indicator, etc.
- BMS: CO2 level indicator, Indoor air quality monitoring, etc.
WARNINGS
PLEASE READ THE FOLLOWING INSTRUCTIONS BEFORE THE INSTALLATION:
- In case of non-compliance with advice and warnings contained in this manual, the manufacturer can not be considered responsible for damages to persons or property.
- The installation and electrical connections must be carried out by a qualified technician according to the manufacturer’s instructions and in compliance with the characteristics of the product
- Before carrying out any operation on the appliance, unplug or disconnect it from the power supply, and ensure it can not be accidentally restored.
- Power cable modification or replacement must only be carried out by qualified personnel or by After-sales Service.
INSTALLATION
Sensors must be installed on the wall, at a height of at least 1.5 meters from the floor, or at the ceiling, and must respect the following recommendations:
- keep the sensor away from any direct solar radiation,
- keep the sensor away from draughts (door, window, supply, etc.),
- avoid placing the sensor in dead zones (behind curtains, furniture),
- keep the sensor away from heat sources and from occupants
- if the sensor is located at the ceiling, keep it away from any air supply unit.
STEPS
- Remove the front cover (A).
- Unclip the electronic card (B) and the plastic protection (D) from the base (C).
- Fix the base (C) by the mean of 2 screws (not supplied). The screws and plug must be chosen according to the type of the support.
- Connections: use PVC wires S minimum = 0.25 mm² for all the wires.
On the electronic card (B), connect the wires as follows:
Connectors > | V+ | S1 | S2 | S3 | S4 | GND |
---|---|---|---|---|---|---|
Supply (2 wires) | 12 VDC | 0 V |
∙ 0 – 10 V output : 0 V = 0 ppm ; 10 V = 2 000 ppm
- Clip the electronic card inside the base (C)
- Put the cover (A) on the base (C)
- Connect the wires to the external devices (12 VDC supply and device driven by 0-10 V output)
- Only once all the connections have been made, plug on the supply of the system.
CAUTION!
Never connect the 12 VDC supply to S1 or S2 and the 0 V supply to GND,
otherwise S1 and S2 output will be crashed.
A protection is implemented to protect the product in case of wrong
connection, when the following mistakes occur:
- Inversion of the supply wires (GND and V+).
- 12 V supply connected to S3 and S4 and 0 V supply on GND.
TECHNICAL DATA
Measurement principle| Non-Dispersive Infrared Technology (NDIR), dual Source
Infrared System
---|---
Working range| 0… 2 000 ppm CO2
Accuracy at 25°C and and 1 013 mbar| ± (50 ppm +2 % of measuring value)
Response time| < 195 s
Temperature dependence| typ. 2 ppm CO2/°C (0…50°C)
Long term stability| typ. 20 ppm/year
Measuring time interval| 60 s
Supply voltage| 12 VDC +/- 10 %.
Average power consumption| 120 mA (reading), 10 mA (nominal).
Peak current max.| 1 A (use for fuse sizing)
Working and storage conditions| -40…60°C 5…95 % RH (not condensating) 85…110
kPa
Output 0-10 V| 0 to 10 V. 0 V = 0 ppm ;
10 V = 2 000 ppm
Output data
Voltage (S3 and S4)| 0 to 10 V
Current (S3 and S4)| 400 mA
MAINTENANCE
Check frequently that the product is clean and remove dust if needed. No
calibration is required.
Caution: Never touch the sensing element (white pastille on the sensor)
otherwise the detection may be damaged.
WARRANTY
The product is guaranteed two years. Its validity is submitted to conformed installation, use and maintenance.
This product is manufactured by Aereco S.A. in France
62 rue de Lamirault
Collégien
77615 MARNE LA VALLEE CEDEX 3
FRANCE
www.aereco.com
TF5701_B
The sensor is manufactured in Germany.