resideo 5800COV Carbon Monoxide Detector Installation Guide

June 6, 2024
resideo

Quick Installation Guide
This device is intended for use with Resideo control panels that support 5800 series devices. Check the control for compatibility with this device.
NOTE: This device must be installed by a qualified technician.
FEATURES

  • 10-year life Carbon Monoxide (CO) sensor
  • CO Detector End-of-Life reporting (detector needs replacing)
  • Low Battery Detection
    See Installation Instructions (R800-26839) – www.resideo.com and the Limitations of Carbon Monoxide Detectors (P/N K14670V1).

LED Indicators
The 5800COV CO detector features a multi-color top LED:
Green = Supervisory indication; blinks during power on, reset, and during normal operation
Amber = Signal maintenance and trouble events
Red = CO Alarm condition
Side LED windows to indicate alarms:
Blue = CO alarm

The carbon monoxide alarming circuit of this device is designed to detect carbon monoxide gas from ANY source of combustion. The carbon monoxide alarming circuit of this device is NOT designed to detect smoke, fire, or any other gases.
WARNING: This product is intended for use in ordinary indoor residential areas. It is not designed to measure compliance with commercial and industrial standards.

POWER UP

  • Remove the battery pull tab. Be sure the battery is seated properly to avoid a low battery condition after 15 seconds.
  • Upon power-up, Green LED Blinks every 2 seconds / Sounder is Silent.

resideo 5800COV Carbon Monoxide Detector

ENROLLING

The detector must be enrolled in the control panel before it can operate in the system. Alarms and trouble conditions from the detector are reported on one protection zone,  which is programmed as carbon monoxide zone type (zone type 14 for Resideo residential controls).

  1. Enter the control’s Zone Programming mode.

  2. Enter the alarm zone number to be programmed.

  3. Enter the applicable zone type when prompted.

  4. When prompted, enter Input Type 03 (3 on some controls) – Supervised RF Transmitter.

  5. When prompted for the serial number, do the following:
    a. Remove the detector from its base (rotate the detector counter-clockwise on the base until it snaps open).
    NOTE: Detector must be removed from its base to enroll.
    b. Press the detector’s CO TEST/HUSH button twice (for each press, hold the button down for several secs).
    c. Reinstall the detector onto its base (twist the detector clockwise until it snaps into place).
    d. Check that the detector is enrolled as loop 1.

  6. If End-of-Life monitoring is desired:
    VISTA-15P/20P, LYNX Touch, and Lyric – automatically sent
    VISTA-128/250 Series – program a separate zone for the CO serial number.
    Loop 2 = Zone Type (Choose a zone type based on the desired operation i.e.; 24 hr Trouble or Auxiliary)
    Input Type = 03 (Supervised)

Zone Device Type Zone Response Type
CO Det. Carbon Mono. Det. Carbon Monoxide
  1. Exit Programming mode when programming is complete, and test the detector. Refer to the Testing Section of this document.
    Refer to the control panel’s installation instructions for additional information.

TO SILENCE THE DETECTOR
Press the CO TEST/HUSH button. The detector sounds again after 5 minutes if the alarm condition continues.
Note: The detector cannot be silenced if the CO concentration exceeds 350ppm.

MOUNTING

After enrolling and before mounting permanently, conduct a Go/No Go test (refer to the control panel
instructions) to verify adequate signal strength with the device in its intended mounting location. Adjust the device location and orientation as necessary. Refer to the Installation Guide (R800-26839) for full mounting instructions.
NOTE: This device should not be located within 5 ft (1.5 m) of any cooking appliance.

resideo 5800COV Carbon Monoxide Detector - MOUNTING

Operation Modes

MODE Status LED (Top) LED Windows (Side) Sounder
Power Up Blink Green once Dark Silent
Normal (Standby) —- Dark Silent
CO Alarm Blink Red every 10 seconds Blink Blue Temp-4
CO Alarm Silence Blink Red every 8 seconds Blink Blue Silent

FUNCTIONAL TESTING
CANNED CO NOTE: Detector sounds an alarm when using canned CO only when in Functional Test mode (canned CO does not cause alarm sounding when in normal mode).
The product must be tested at least once each year

resideo 5800COV Carbon Monoxide Detector - MOUNTING 1

  • Use UL/ANSI Approved canned CO.

PERIODIC CLEANING

NOTE: Notify the proper authorities that the CO detector is undergoing maintenance and the system will temporarily be out of service.

resideo 5800COV Carbon Monoxide Detector - PERIODIC
CLEANING

BATTERY REPLACEMENT

Caution: The battery used in this device may present a fire or chemical burn hazard if mistreated. Do not recharge, disassemble, heat above 212°F (100°C) or dispose of it in fire.  Use only Panasonic CR123A Lithium batteries. The use of other batteries may present a risk of fire or explosion. Keep used batteries away from children. Dispose of used batteries properly.
Remove the old battery. Wait 10 seconds and then replace it with a new battery.
NOTE: Constant exposure to high or low temperature or high humidity may reduce battery life.

resideo 5800COV Carbon Monoxide Detector - BATTERY
REPLACEMENT

NOTE: Batteries are available at your local retailer or distribution center.

LED Indication & Sounder During Test and Trouble

MODE Status LED (Top) Side LED Windows Sounder
CO Test I Blink Red during alarm Dark Temp-4 (two times)
Functional CO Test 1 – Waiting for gas entry Blink Green once every second
Dark Silent
Functional CO Test -Successful gas by Blink Red every 10 seconds Blink Blue
every 10 secs Trap-4
Low Battery Blink Amber every 45 seconds Dads Chirps every 45 seconds after

7 days
CO Trouble| Double Blink Amber every 8 seconds| Dark| Silent
CO End of Life2– First 29 days| Double Blink Amber every 4 seconds| Dark| Silent
CO End of Life2– After 30 days| Double Blink Amber every 4 seconds| Dark| Chirp every 45 seconds

  1. Test activated by pressing and releasing the CO TEST/HUSH button; Detector is functioning properly (within proper sensitivity). See the Functional Test section for  Functional Test activation and procedure. If Test mode is activated and the LED and Sounder do not function, check for maintenance or trouble conditions.
  2. Starts chirping after 30 days, and continues until the battery is replaced or dies.

SPECIFICATIONS

Battery: ……………………….. 1 x 3V, CR123A Lithium/Litio; Panasonic CR123A only
Audible Signal: ……………………………………………………..85dBA
Dimensions: ………………………………… 6.2 in. Diameter x 1.99 in. Depth
Weight: …………………………………………………….. 14.3 oz; 406 g
Tamper: ……………………. Cover
Operating Temperature: ……………………………. 32° to 100° F
Storage Temperature: ………….. 14° to 158° F
Relative Humidity: ………….. 95% max, non-condensing 2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747