LEX Products PowerHOUSE Power Distribution Units User Manual
- October 27, 2023
- LEX Products
Table of Contents
LEX Products Power HOUSE Power Distribution
Introduction
The Power HOUSE™ line of Power Distribution Units (PDUs) meet stringent requirements for either indoor or outdoor site applications. This user manual reviews the proper use of the wide range of locking and non-locking inlet, feed-thru and receptacle versions available. Please take time to review all precautions and warnings in the manual prior to making the proper connections for use. Store this manual in a safe location for future reference.
Unpacking and Inspection
Before you begin your installation check the shipment carefully to confirm it arrived complete and undamaged.
- Check the contents against the packing list to ensure the devices are the correct models
- Check the unit for loose or broken components, which might have resulted from shipping
- Inspect for signs of damage to wiring devices or circuit breakers
If there is any damage to the Power HOUSE™ PDU, contact Lex Products toll free at 800.643.4460 or email info@lexproducts.com.
Power HOUSE™ PDU Components (Typical)
Setting Up Power HOUSE™ Power Distribution Units (PDUs)
Locating PDUs
- The Power HOUSE™ PDUs are designed to be used in indoor or outdoor locations
- Review labels attach to enclosure for rating
- ‘TYPE 1’ indicates Indoor use only, ‘TYPE 3R’ indicates either Indoor or Outdoor use
- Each Power HOUSE™ PDU should rest on its own base on a level surface with suitable ventilation
- DO NOT locate any Power HOUSE™ PDU in any area prone to standing water
Making and Breaking Connections on PDUs
WARNING:
- Before making or breaking connections to any Power HOUSE™ PDU make certain the power source feeding the system is OFF
- DO NOT exceed the voltage rating of the device as identified on the label attached to the enclosure
NOTE:
If using the feed thru feature, connect the feed thru BEFORE the input
connection is made
- Single-pole Cam Connectors
- When MAKING the connection, begin with the GREEN ground connection, then the WHITE neutral connec-tion and finish with the remaining HOT connections
- Firmly insert cam device into connector and rotate clockwise until fully engaged and locked
- When BREAKING the connection, begin with the HOT connections, then the WHITE neutral connection and finish with the GREEN ground connection
- NEMA Locking Connector
- Fully insert the female connector into the male inlet
- Turn connector clockwise until it is fully locked
- LSC 19 Multi-pin Connector
- Align female connector with male inlet and insert, ensuring connection is fully seated
- Spin the locking collar of male inlet until snug
- NEMA Straight Blade Connections
- Fully insert the male plug into the female receptacle
Powering Up PDUs
- Best practices dictate that loads are applied gradually the first time the system is set up NOTE: PowerHOUSE™ PDUs are shipped with breakers in the ‘O/OFF’ position
- Turn on the power source
- Beginning with the PDU closest to the power source, move the first individual circuit breaker to the ‘I/ON’ position
- Ensure the devices fed by that circuit are ON, tracing the electrical path to the final device fed by that circuit
- Repeat steps 2 and 3 for the remaining circuit breakers
NOTE:
If the circuit breaker cannot be energized or trips, check the system for
continuity, short circuits and overload, and make the necessary corrections
before proceeding
Troubleshooting Guide
If there is no power at receptacles:
- Ensure that connections are in place and tight
- Ensure that power source is live
- a. Activate if not on
- Ensure that circuit breakers are ‘I/ON’
- If a circuit breaker trips, identify source of short circuit or overload and correct before resetting circuit breaker
- a. Check to see if the circuit is overloaded and reduce loads as needed
- b. Check for short circuits in the cabling or load device and correct as needed
- For those receptacles that include a GFCIs:
- a. Ensure the GFCIs are set by pressing the ‘RESET’ button
- If a GFCI trips, identify source of current leakage and correct before resetting the GFCI
- a. Check to see if the circuit is overloaded and reduce loads as needed
- b. Check for short circuits in the cabling or load device and correct as needed
- If there is still no power at receptacles:
- a. Remove PDU from use
- b. Contact Lex Products for next course of action
Technical Support
Lex Products is available to help answer any product related inquiries. For any questions or technical advice, please call toll free 800-643-4460 or email info@lexproducts.com.