envirovent energiSava 250 Whole House Heat Recovery Unit Instruction Manual
- October 27, 2023
- envirovent
Table of Contents
- envirovent energiSava 250 Whole House Heat Recovery Unit
- Safety
- Diagrams
- About the energiSava® 250
- Box Contents
- Pre – Installation Checklist
- Installation
- Commissioning
- Wi-Fi App myenvirovent
- Wireless Remote Control
- Technical Specification
- Post-Installation Checklist
- Filter Maintenance
- Spares/Accessories
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
envirovent energiSava 250 Whole House Heat Recovery Unit
Safety
Read and understand these instructions carefully before beginning installation. The unit should only be installed by a competent person.
Electrical Connection
The unit requires a continuous electrical power supply. Connection to the
fixed wiring must be made outside the unit in a suitable location. The unit
must be able to be disconnected from the mains supply after installation. The
unit must be earthed and a suitable isolator having a minimum contact
separation of 3.0mm must be used to provide isolation for the unit.
The power cable running into the unit must remain the supplied flexible cable.
If the power cable becomes damaged, it must be replaced by EnviroVent, an
authorised service agent for your region/country, or a similarly qualified
person in order to avoid a hazard. Do not remove or tamper with any electronic
components inside the unit.
All wiring must comply with Building Regulations and the current IET Wiring
Regulations (BS7671 in the UK) or equivalent standards for other countries.
The final installation should be examined and tested by a qualified
electrician.
Location
Check there is space for the unit in your chosen location including room for
access and future servicing of the unit. The unit must not affect the
operation of open-flue appliances. Consider the external vent locations in
relation to open flues from appliances e.g. boilers. You must ensure the
external supply grilles are positioned away from open flues to avoid drawing
harmful gases into the property. Consult your local regulations or a qualified
gas engineer.
Users
This unit is not intended for use by persons [including children] with reduced
physical, sensory or mental capabilities or lack of experience and knowledge,
unless they have been given supervision and usage instruction by a person
responsible for their safety. Children should be supervised to ensure they do
not play with the unit. Cleaning and user maintenance must not be performed by
children.
Diagrams
Overall unit dimensions and minimum area required for access & maintenance (mm).
The energiSava® 250 spigots are compatible with ø125mm duct.
WIRING
The local isolator must be connected to the mains as part of the fixed wiring. Connect the cores of the power cable to the matching terminals on the local isolator (3A fuse spur or similar).
The black switch live core of the mains cable can be wired to a switch input such as a light switch. When the switch is turned on, the boost function is engaged. When the switch is turned off, the unit will return to normal running mode. In this configuration a triple pole isolator must be used.
About the energiSava® 250
The energiSava® 250 is an MVHR unit (Mechanical Ventilation with Heat Recovery). It is ideal for medium to large sized properties with a kitchen and up to 5 additional wet rooms. The unit is capable of delivering a maximum airflow of 280m3/h (78l/s) and a maximum system pressure in excess of 224Pa.
The unit will help to create a fresh and healthy living environment by supplying filtered air into a property through supply valves. Moist, stale air is removed out of the property through extract valves.
The heat exchanger inside the unit transfers waste heat energy from the extracted air to the supplied air in order to improve the indoor air quality of the property and reduce heating costs.
When outdoor temperatures are low, the frost protection feature automatically reduces the supply air flow rate to ensure the heat exchanger inside the unit does not freeze.
The Intellitrac® humidity tracking function monitors the humidity levels in the extracted air and will automatically increase the supply and extract air flow rates when the humidity levels rise. Once the humidity levels are lower the air flow rates will return to the normal rate.
The automatic, thermal bypass helps to control temperature entering the home on warmer days.
The energiSava® 250 includes a switch live function. When wired through the lighting switch of a room (such as a bathroom) the unit will enter boost mode whenever the light is turned on.
Box Contents
EnergiSava® 250
- 1x energiSava® 250 unit
- 1x Remote control
- 1x Instruction guide
- 1x User guide
- 2x Mounting brackets
- 10x Screws 8g x 2.0”
- 10x Plasterboard plugs
- 2x Wing nuts
- 1x Screw 10g x 0.5”
- 1 x Condensate drainage kit
EnergiSava® 250 App
- 1x energiSava® 250 app unit
- 1x Instruction guide
- 1x User guide
- 1x App guide
- 2x Mounting brackets
- 10x Screws 8g x 2.0”
- 10x Plasterboard plugs
- 2x Wing nuts
- 1x Screw 10g x 0.5”
- 1 x Condensate drainage kit
EnergiSava® 250 RS & Basic
- 1x energiSava® 250 unit
- 1x Wired Remote Switch (RS only)
- 1x Instruction guide
- 1x User guide
- 2x Mounting brackets
- 10x Screws 8g x 2.0”
- 10x Plasterboard plugs
- 2x Wing nuts
- 1x Screw 10g x 0.5”
- 1x Condensate drainage kit
Pre – Installation Checklist
- Does the unit fit in the space where it will be installed?
- Is there room to connect ducts to the spigots without tight duct bends?
- Is there room to access and replace the filters after installation?
- Are there any obstructions above or below the locations where the input and extract valves are to be fitted?
- Is the mounted surface strong enough to support the unit?
- Is the mounting surface level?
- Are there adequate facilities to connect the unit condensate drain to the internal waste system of the property?
Installation
- Hold the unit up to the chosen location and check there is space for ducts, condensate drainage, filter and keypad access.
- Once you are satisfied with the position, line up the two brackets using the printed template then secure them to the mounting surface.. Use 10 8gx2.0” screws and 10 plasterboard plugs.
- Mount the unit onto the brackets ensuring that it is fully supported.
- Apply the two wing nuts onto the threaded studs then insert the self-tapping screw into the hole and tighten it. This will ensure the unit cannot be accidentally knocked off the brackets.
- Fit the external supply and extract terminations.
- Fit the supply and extract valves inside the property.
- Fit the ductwork between the external terminations, the MVHR unit and the supply and extract valves.
- Connect each duct path to the spigot.
- Make a water-tight connection between the two drainage connectors on the unit and the waste water system in the property. A suitable non-return device must be fitted to ensure air and waste water from the drain system do not flow back up into the unit. The drainage must be fitted with a minimum 5 degree fall away from the unit.
- With the mains supply isolated, wire the unit to the local isolator as per the wiring diagram and in accordance with the local wiring regulations. When the power is turned on, air will begin flowing into the property after a few seconds.
- If you are installing a remote switch (-RS) unit:
a) Open the switch ensuring the ribbon cable remains connected to the PCB.
b) Screw the switch to the wall in an accessible location.
c) Replace the lid and tighten the two screws.
Commissioning
All maintenance and building works should be complete before commissioning
this MVHR unit. This will avoid any other major disturbance to the
installation or high volumes of dust or debris being drawn into the system. Do
not commission the MVHR unit until it is fully installed including power,
ductwork, internal valves and external vents.
MVHR systems must be commissioned in accordance with Approved Document F of
the Building Regulations for England and Wales. Further good practice advice
for the installation of MVHR systems can be found in the latest edition of the
Domestic Ventilation Compliance Guide for England and Wales. For MVHR
commissioning guidance in other countries, please refer to the relevant local
Building Regulations for that country.
- Determine the required ventilation rates. For guidance see Approved Document F of the building regulations for England and Wales.
- During normal running mode, press the SET button for 4 seconds to enter commissioning mode. (Humidity and temperature sensor input is disabled temporarily while the unit is in commissioning mode).
- LEDs B C D will light and LED A will flash indicating that the extract boost flow rate is being modified.
- Fully open all supply/extract valves then measure the air flow rate at all system extract points using a calibrated air flow meter capable of measuring in l/s or m3/hr.
- Add the extract rates from all rooms together then compare this value to the calculated whole building (boost) extract ventilation rate.
- Use the + and – buttons to increase or decrease the flow rate in order to meet the calculated whole building extract ventilation rate.
- Now adjust the individual valves to extract at the appropriate rate for each wet room. Once this step has been completed it may be necessary to adjust the unit boost rate again to account for any increase in pressure.
- Press the SET button once to move on to the next flow rate. The flashing LED indicates which flow rate is being modified.
- A: Extract Boost
- B: Supply Boost
- C: Extract Trickle
- D: Supply Trickle
- Commission the unit in the order shown below, using the previous steps for adjusting air flow rates and valves.
(When maximum speed setting is reached, the LED will flash faster. When the minimum speed setting is reached the LED will flash slowly).
Step | Flow Rate | Actions |
---|---|---|
1 | Extract Boost | Lock the valves. |
Record the air flow rates.
2| Supply Normal (Trickle)| Lock the valves.
Record the air flow rates.
3| Supply Boost| Do not adjust the valves. Record the air flow rates.
4| Extract Normal (Trickle)| Do not adjust the valves. Record the air flow
rates.
When commissioning is complete for all four flow rates, press SET for 4 seconds to return to normal running mode. If this is not done, the unit will automatically return to normal running mode after 60 minutes of inactivity and the current settings will be saved.
Wi-Fi App myenvirovent
App enabled units can be controlled using the my envirovent app on Apple and Android devices. A separate instruction guide for the my envirovent app is included in the box. The guide can also be accessed from within the app. Once the unit has been installed, refer to this guide for connection and further settings. The SSID and password information for the unit is printed on the back page of the app guide and also on a label attached to the bottom of the unit.
Wireless Remote Control
To view the current status of the unit:
Press any button to wake the remote control and the relevant LEDs will
light up according to the current status of the unit.
To manually activate or deactivate the boost function:
- Press any button to wake the remote control.
- Press the button again, the boost LED will flash (red). After 2 seconds the unit will enter boost mode (default setting is 20 minutes) then automatically return to trickle mode.
- If the switch live connection is turned on then boost cannot be cancelled until the switch live connection is turned off.
- To deactivate the boost mode, repeat the above steps.
To switch between auto and manual summer bypass modes:
- Wake the remote control.
- Press and hold the button for 5 seconds, the filter LED will flash green.
- Press the button once to switch to edit the summer bypass mode.
- Press and hold the button for 5 seconds to switch between summer bypass modes.
- Auto = Bypass LED constant, Manual = bypass LED flashing.
To manually activate or deactivate the summer bypass function (in manual bypass mode):
-
Press any button to wake the remote control.
-
Press the button again twice. The bypass LED will flash (red).
After 2 seconds the unit will enter bypass mode for 24 hours then automatically return to the normal running mode. -
To deactivate the summer bypass mode, repeat the above steps.
Filter indicator and reset:
- If on waking the remote control the filter LED flashes (green), the filters need to be replaced. Contact EnviroVent to order new filters.
- After replacement filters have been installed, wake the remote control.
- Press and hold the button for 5 seconds, the filter LED will flash green.
- Press and hold the button for 5 seconds again to reset the filter, the filter LED will flash rapidly for 2 seconds to confirm the filter reset.
Pairing an extra remote control:
- Turn the unit off at the isolation point.
- Restore the power to the unit. For 20 seconds from restarting, the unit will be in pairing mode.
- Press the button on the new remote control once within the 20 seconds and the remote control will pair to the unit.
- If LED 2 lights green, the pairing has succeeded.
Fault indication:
If on waking the remote control all LEDs are flashing (red), a fault has
occurred with the MVHR unit. If it persists, call EnviroVent on 01423 810 810
for further help.
When the remote control battery needs to be replaced, remove the two screws then open the remote control. The battery is located on the back of the front cover. Replace the battery (ensuring the polarity is correct) then screw the rear cover back on. The switch will remain paired with the unit after battery replacement. The remote control uses 1x CR2032 battery. Dispose of the discarded battery in a safe manner.
Technical Specification
Spigot diameters | 125mm |
---|---|
Maximum air flow rate | 78l/s (280m3/h) |
Maximum power consumption | 150W |
Electrical Supply | 230V Single Phase 50/60Hz |
Ingress protection rating | IPX2 |
Filter grade | ISO Coarse 45% (G3) |
Boxed unit weight | 16kg |
Unboxed unit weight | 14kg |
Airflow Performance
Post-Installation Checklist
- Installation instructions have been understood. Contact EnviroVent on 01423 810 810 if you require further technical help.
- The ductwork diameter is 125mm or larger throughout the property.
- The installation system uses rigid duct or a suitable semi-rigid duct system such as EnviroVent fast track.
- Minimal amounts of flexible duct have been used in the installation.
- All ducts, valves, vents and drainage points are connected, mechanically fixed and sealed.
- Both filters are inserted into the filter slots on the unit.
- The unit is securely fixed with adequate space left for servicing.
- Condensate drain is securely connected to the waste water system, a non return device is correctly fitted and pipework has been water tested before connection to the MVHR unit.
- All major building works have been completed prior to commissioning.
- Supply and extract air flow rates have been commissioned with a calibrated anemometer (other suitable devices can be used) to meet Approved Document F of the
- Building Regulations for England and Wales.
- Commissioning air flow rate data has been recorded.
- The occupants of the property are familiarised with the operation and maintenance requirements of the system.
Filter Maintenance
- Filters must be inspected every 6 months and replaced at least every 12 months. If filter maintenance is not carried out, it can invalidate the warranty.
- Isolate the unit from the mains supply
- Remove the filter caps, replace both filters then reinsert filter caps.
- Engage the mains supply then reset the filter indication by pressing the minus button for 10 seconds. The filter change indication can also be reset via the remote control as shown on page 16.
- Not maintaining the filters during the life of the product can invalidate the warranty. Filter change indication duration is factory set to 12 months.
Spares/Accessories
Item Description | Order Code |
---|---|
Replacement Filter | FILTER-ES250 |
125mm white supply valve | 1DIFSUPPLY125WH |
125mm white extract valve | 1DIFEXTRACT125WH |
150mm white supply valve | 1DIFSUPPLY150WH |
150mm white extract valve | 1DIFEXTRACT150WH |
Spare remote control | SWH-W-MVHR |
Spare condensate drainage kit | KITCONDENSATE-ES250 |
Condensate non-return valve (ceiling) | 1ACHEPVOVALVE32 |
Warranty
We appreciate you choosing this quality EnviroVent product, which is designed
and manufactured in Harrogate, North Yorkshire. We are confident that you will
be delighted with the performance of the system and the resulting improvement
in air quality in your home after it has been installed.
This unit is covered by a 2-year warranty, subject to the replacement of
filters every 12 months, or more frequently as required, dependant on the
environmental conditions. You should not dismantle or remove any parts of the
product other than those instructed in this guide. Tampering with the unit
will void the warranty. The valves should be checked periodically to ensure
there is air flowing through the system.
EnviroVent Supply & Installation
If your product has been supplied and installed by EnviroVent Ltd it is
covered with two-year parts and labour warranty. If you detect a fault, please
contact us on 01423 810810. You will be given guidance over the phone, or an
arrangement may be made for a member of our team to visit (call-out charges
may apply if a fault cannot be identified).
Supply Only
If your product has been supplied by EnviroVent and installed by a third party
it is covered by a two-year parts only warranty. If you detect a fault and the
product has been installed in accordance to the fitting/wiring instructions,
relevant guidance documents and by a competent and qualified person (proof may
be required), please return the product to the place of purchase for a
replacement.
Warranty Conditions & Exclusions
Please note that a receipt will be required as proof of purchase. Products
bought from an unapproved source, including but not limited to auction
websites, are not covered by the warranty.
- The system must be correctly installed and operated according to the instructions contained in the user guide supplied.
- The warranty will be rendered invalid if the system has been serviced, maintained, repaired, taken apart or tampered with by any person not authorized, which in any way contradicts the instruction guide set out by EnviroVent.
- The warranty does not cover accidental damage, misuse or abuse.
- The warranty is in addition to your statutory or legal rights.
Your unit serial number
For warranty conditions and exclusions, visit
www.envirovent.com/warranty
EnviroVent Limited EnviroVent House Hornbeam Business Park Harrogate
HG2 8PA
T / 01423 810 810
E / info@envirovent.com W /
envirovent.com
Boxed unit weight : 16kg
Unboxed unit weight: 14kg
E&OE | MKT ENV379-05.05.21 -V10
Due to our policy of continuous innovation and improvement EnviroVent reserves
the right to alter products specification and appearance without notice.