Nokeval Kube-Sky-RHT-PM0413 LoRa Based Instruction Manual
- June 5, 2024
- Nokeval
Table of Contents
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Nokeval Kube-Sky-RHT-PM0413 LoRa Based
Introduction
The Kube-Sky-RHT series consists of several models of wireless indoor air
quality transmitters. All models have a LoRa-based Nokeval Sky radio with a
very good range.
Models
The Kube-Sky-RHT is the basic model. It measures temperature and humidity
only. With moderate settings, the battery life will exceed five years.
When the model name has a –CO2 suffix, the device also measures carbon dioxide
concentration up to 5000 ppm. This model needs to see fresh air at least once
a week to be able to auto calibrate itself. The minimum time spent in the
fresh air should be at least five measurement intervals. This model is not
suitable for premises that are continuously occupied; such premises result in
carbon dioxide measurements showing smaller values than should. The CO2
model can be used with batteries but the battery life will be shorter than on
the basic model. An external power supply can be used to overcome this.
The model with the -Lux suffix has a coarse light level (illuminance) sensor.
The model with -PIDVOC suffix has a high-quality photoionization detector for
detecting volatile organic compounds. The sensor is factory calibrated for
isobutylene, and it can operate in a continuous exposure unlike many sensors
that will auto-zero themselves. The sensitivity goes to tens of ppb. This
model must be powered by an external supply.
The model with -DP suffix is equipped with a differential pressure sensor. The
device has a relay for controlling e.g. a signal lamp when the differential
pressure exceeds or falls to meet a configured limit. The differential
pressure can be measured with a battery or external power.
The models with -PM0413 and -PM0440 suffixes are equipped with a particulate
matter sensor. The -PM0413 can measure a particulate matter of sizes between
0.4-12.4µm, and the -PM0440 model can measure between 0.35-40µm. The PM2.5 and
PM10 values are international standard values for particulate matter. The
-PM0440 model also provides a non-standard PM40 value which includes all
particulate matter up to 40µm. These models must be powered by an external
supply.
Sky radio
The Sky devices use the Semtech LoRa modulation technique that allows
unforeseen wireless range in a battery-powered transmitter. The protocol used
is defined by Nokeval, called Sky, which means that this device is not
compatible with the LoRaWAN infrastructure.
The modulation has some parameters to define its operation. With the “maximal”
settings, a very long range can be reached, but at the expense of high battery
and radio band consumption. One radio transmission can last approx. 2 seconds
(compared to 20 ms of the Nokeval MTR series). This means that the number of
transmitters within the range must be limited in order to avoid collisions and
to allow radio time for each. It is not practical to use a short interval
between transmissions; 10 to 30 minutes is the recommended interval range.
When the maximal range is not necessary, the parameters must be adjusted for
lower battery and band consumption. All the devices within one network must
share the parameters, because the receiver can only listen with one set of
parameters at a time. The parameters must be selected according to the most
distant device. It is also possible to adjust the transmission power. The
devices that are closer to the receiver can use a lower power setting.
Before using the 433 MHz radio, make sure it is legal in your country.
Installation
Mounting
Place the device to the measuring location with one of the following ways:
- Select the installation place so that air can flow freely on all sides of the transmitter and that it represents the air that is to be measured. Avoid heat sources and direct sunlight.
- Mount the Kube wall holder with two countersunk screws (ST 3.0 x 20). Mount the holder with its hooks pointing upwards.
- Place the Kube freely on any surface.
Power supplies
The RHT model comes with batteries installed, ready to be used.
The CO2 and dP models are supplied with the batteries outside the device. Open
the enclosure (with the two screws on the bottom) and insert the batteries in
the holders, the + end to the holder with a red plastic piece.
The RHT, CO2, Lux, and dP models can alternatively be operated with an
external supply. When an external supply is used, the batteries can be omitted
or used as a backup supply.
The PIDVOC and PM models don’t work without an external power supply.
The external supply can be connected with two alternative ways:
- Use the micro USB socket in the bottom of the device.
- Connect a 5 V DC power in the round holes of the push-in spring connector J11 with 0.2-0.5 mm2 conductors, the positive wire to the left. Strip the wires approximately 6 mm. The wires can be detached by pushing a small flat screwdriver or some other spike in the rectangular holes.
To check that the device is powered, push the button once and check that the indicator LED lights green or red.
Settings
The device usually works with its default settings, but you can change the
settings:
- Connect a micro-USB cable to the connector, and the other end of the cable to a computer.
- If Windows requests for a driver, download it at www.nokeval.com > Support, unzip it to a temporary folder, and show that directory as the location for the driver. If there are problems during the installation, try pushing the Kube button every 5-15 seconds or keeping it pressed so that Kube will not shut down its USB port.
- Launch the Mekuwin program (available for free at www.nokeval.com).
- In Mekuwin, choose Port=Kube (COMxx). If the port is not visible, try pushing the Kube button to wake it up.
- Choose Protocol = Modbus, Address = 1.
- Click Direct.
- A new window will open. It has branches for different settings.
The configuration menu is presented in the picture below. The different versions may have slight differences and lacking features. The menu is divided to submenus for each quantity group (Temp+Humi, Pressure, Gases, Particles). In addition to those, there are submenus for wireless network settings, alarm function settings, relay settings, and general settings.
Commissioning the radio
To get the radio working with your receiver, adjust the following settings in
the Sky menu to match the corresponding settings of your receiver, otherwise
the communication will fail:
- Network (default 1)
- Effort (default 4)
- Channel (default 1)
- Key (default empty)
The address of this Kube can be seen in the Address box. The address is
factory set and can’t be changed here.
If you want to ensure that every measurement is delivered despite of radio
collisions and disturbances, set the following settings (this will typically
double the battery consumption):
- Quality = Buffering (default Unidirectional which means send and forget)
- Destination = the radio address of your (nearest) receiver
To learn about the more detailed radio settings, see the chapter Detailed radio settings on page 17.
Setting the measurement intervals
Each quantity group (Temp+Humi, Pressure, Gases, Lux, Particles) has a setting
to define how often to start the sensors and take a measurement. The setting
is named Period and is set in seconds. Do not use unnecessarily short interval
as it both consumes the batteries quickly and increases the likelihood of
radio collisions. See Estimated battery life on page 22.
The defaults are:
- Temperature+humidity: 900 sec i.e. 15 min
- CO2: 1800 sec i.e. 30 min
- Lux: 900 sec i.e. 15 min
- VOC: 3600 sec i.e. 1 hour
- Pressure (dP): 300 sec i.e. 5 min
- Particles: 900 sec i.e. 15 min
The allowed range is 5…7200 seconds. A quantity group can be switched off by setting its Period to 0.
Other settings and considerations
The next chapters cover the different sensors, their menus and other things to
consider. There is also a chapter detailing the radio settings. In the typical
use, especially with the RHT and CO2 models, it is not necessary to read them.
Which logical channels carry which quantity is specified on page 19. This
information may be needed when configuring the receiving system.
You may also find useful to check the chapter Maintenance on page 20 to
understand the button, the LED and some other aspects.
Protecting the settings
To protect the settings from being easily adjusted, enter a password at
General / Code (up to six digits or letters). Next time taking a Mekuwin
session the settings can’t be adjusted without knowing the password.
If the password is set but lost, disconnect an external power supply, remove
at least one battery, interconnect the second (from top) and fifth contact of
the card edge connector with e.g. tweezers, keep the button pushed, and
connect a battery or an external supply. After a second you may remove the
tweezers and release the button. Now the password is temporarily reset until
the next power off.
RHT measurement
Principle
The temperature is measured with a digital sensor on the circuit board. The
humidity is measured with a capacitive polymer sensor.
Settings in the Temp+Humi menu
Period
See Setting the measurement intervals on page 7.
Temp unit
Temperature unit °C or °F. The humidity is always in %RH.
Recalibration
These sensors do not normally need regular recalibration.
Differential pressure measurement
Principle
The sensor inside the Kube has two hose outlets. Inside the sensor, these are
connected through a small orifice. A pressure difference between the outlets
will cause a small flow of air, which is measured. One of the outlets is
brought out of the enclosure via an internal hose. Kube can measure up to 125
Pa in either direction.
Pressure connection
Connect a hose with an internal diameter of 5 mm in the hose connection at the
bottom of the case. The pressure is delivered via an internal hose to the
pressure sensor. The internal hose can be moved among the two outlets to
select which way the pressure is to be measured.
Upper outlet The external hose in higher pressure than the Kube itself: a positive reading.
Lower outlet The Kube in higher pressure than the external hose: a positive reading.
dP settings
The pressure sensor has no other settings than the measurement interval
(Setting the measurement intervals on page 7).
Alarm and relay settings
The Kube can give an alarm of too high or too low (or both) differential
pressure. There are two alarm comparators. If any of them is alarming, the
relay will operate. Configure the alarms and the relay with these settings:
Alarm / 1…2 / Active
Switching alarm on/off.
Alarm / 1…2 / Type
This setting determines the direction of the alarm:
- Low = alarms when the pressure is too low.
- High = alarms when the pressure is too high.
Alarm / 1…2 / Level
The level of the differential pressure when the alarm should be
activated/deactivated (this can also be a negative value, depending on which
way the differential pressure is measured). The allowed range is
-125…125 Pa.
Alarm / 1…2 / Hyst
The amount of hysteresis added to the set level. The hysteresis is applied on
both sides: e.g. Level=10, Hyst=2, the alarm changes its state at 12 and 8.
Relay / Activation delay
Sets the delay for the alarm activation (i.e. alarm trigger detected / alarm
activated). The allowed range is 0…65535 seconds. By setting the delay to
value 0, alarm is activated immediately.
Relay / Deactivation delay
Sets the delay for the alarm deactivation (i.e. alarm deactivation trigger
detected / alarm deactivated). The allowed range is 0…65535 seconds. By
setting the delay to value 0, alarm is deactivated immediately.
Relay / NC
- No (default) = normally open, the relay contacts are normally not conducting but will conduct when an alarm occurs
- Yes = opposite to previous
Relay connector
Inside the enclosure, there is a four-terminal spring-loaded relay connector,
the terminals from left to right:
- Common/ground (do not use)
- Unused (an option for 24 VDC power input, not usable)
- Relay
- Relay
The relay contacts are between terminals 3 and 4. In addition, by shunting the
jumper next to the connector, terminals 2 and 3 will be internally
interconnected.
A cable gland is provided for a cable having an outer diameter of 2.5 to 3 mm.
Recalibration and maintenance
The sensor doesn’t typically need recalibration. Should the sensor orifice
become clogged, max 1 bar of air can be used to try to flush it.
Illuminance measurement
Principle
The illuminance sensor peeks out of the front cover. It is not a precise
luxometer, but gives an idea of the light level. Its spectral response and
angular sensitivity are not on the same level as in actual luxometers. The
angular sensitivity is shown in the graph.
Settings in the Lux menu
Period
See Setting the measurement intervals on page 7.
CO2 measurement
Principle
The CO2 sensor is based on the NDIR principle, measuring CO2 concentration
using 4300 µm light which is absorbed by CO2.
Auto calibration
An auto-calibration is necessary for most CO2 sensors; without it, they drift over time and eventually give incorrect readings. The auto calibration can work properly only if the device is exposed to fresh air for at least some hours each week, in practice, the room must be unoccupied now and then and its ventilation on.
Settings
The CO2 settings are in the Gases / CO2 menu.
-
Sampling time
This setting determines how many seconds the CO2 concentration is measured. The bigger the value, the less noisy reading, but the battery is exhausted faster (unless externally powered). A good value is 30 seconds when externally powered, or 15 for battery power. The default value is 15 seconds. -
Autocal / Period (h)
This setting determines how many hours pass before the device performs an auto-calibration. A good, and also the default, the period setting is 192 hours which is a little more than a week as the device timer is not accurate, assuming that the fresh air occurs only once a week.
If you do not want the auto-calibration, set Period to 0 (zero). Then it is advisable to perform a manual calibration regularly. -
Autocal / Base level
The device looks for the lowest reading from the period and if that differs from this setting, the device adjusts the future measurement readings down or up as needed. This is what the auto-calibration means. The base level is typically 400, which is the clean air concentration or a little more. -
Autocal / Max adjust
This setting limits the maximum adjustment that is done at a time. The good value is 50. The default value is 100. -
Manual
This menu allows manually calibrating the CO2 offset. Enter the real CO2 level and press the Now button. Wait for a moment (2x Sampling time). Check that the reading corresponds to expected after it has been updated.
PID VOC measurement
Principle
The volatile organic compound concentration is measured with a photoionization
detector (PID). An ultraviolet lamp (10.6 eV) ionizes the VOC molecules, which
allows a weak current to flow from one electrode to another. These sensors are
expensive but give a good sensitivity for VOCs and low sensitivity for
humidity and other gases.
Calibration and cleaning
An automatic baseline calibration is not usually needed, nor provided by the
Kube. If one was used, the device would not be able to measure continuous VOC
concentrations as the automatic calibration would cancel them off.
Manual calibration with two known concentrations should be performed
regularly. In a clean atmosphere, e.g. an office, the interval can be relaxed
even to some years, but the more contaminated air, the more often the sensor
needs service.
In dirty atmospheres, the lamp and the other parts of the sensor may need
cleaning, and at some stage, replacement. Refer to the Alphasense PID-AH2
maintenance instructions.
Settings
The VOC settings are under Gases/VOC.
-
Warmup
The photoionization sensor needs some time to stabilize its lamp. The time is defined with this setting, in seconds. The default is 30 seconds. Too short time will give inaccurate readings. Too long time will wear the lamp and heat up the temperature sensor leading to too high-temperature readings. -
Sampling time
This setting defines how long the sensor is read and averaged. The longer time, the lower noise. The default 10 seconds is adequate in most cases. -
Coefficient
The default calibration for the VOC is with isobutylene in ppms. The VOC sensor reacts to other gases with a different sensitivity. If the target gas is known, the VOC reading can be corrected for it by setting a coefficient (multiplier) for the reading. Similarly, a different measurement unit can be obtained by adjusting the coefficient. Some examples: Main gas \ Unit| ppm| µg/m3
---|---|---
Isobutylene| 1|
Toluene| 0.56| 2110
Cleaning
The sensor may need a longer lamp operating time now and then to keep it
clean. This menu has three settings to define the periodic self-cleaning:
- Interval (hours): How often to perform the cleaning. One week (168 hours) is recommended.
- Duration (seconds): How long to keep the lamp on. 1200 seconds recommended.
- Temp lockout (seconds): As the cleaning will heat the device, the temperature and humidity measurements will be locked out during and after the cleaning to avoid incorrect readings. This setting defines the lockout time after the cleaning, 1200 seconds by default.
Particle measurement
Principle
A small fan sucks air from the opening in the cover. Inside the device, the
air passes through a laser beam. The particles will cause a flash when passing
the laser, allowing them to be counted and their sizes
(diameter) estimated.
The mass of the particles is estimated by assuming that they have a density of
1.65 g/ml and by making assumptions of their shape. The result is not accurate
if the density, shape, or refractive index deviates significantly from the
estimates used in the calibration.
Settings
Period
See Setting the measurement intervals on page 7.
Sampling time
This setting determines how many seconds particulate matter is measured. The
bigger the value, the less noisy reading. A good value, and also the default,
is 30 seconds. Outside the sampling time, the laser and the fan are stopped.
Particles / Bin details
Option to get detailed amounts of particles in each bin separately in addition
to the PM2.5, PM10, and PM40 values. Typically not needed. The default is off.
Particles / Bin 0 … Bin 23
Requires the Bin details setting to be enabled. The radio transmission of each
detail bin can be separately enabled with these settings. Note that the bin
ranges are different between PM0413 and PM0440, and that PM0413 only uses the
first 16 bins. The bins are listed in Quantity channels on page 19. Unlike the
PM values, which estimate the particulate mass, these bins count pieces per
litre.
Channel | Particle sizes µm |
---|---|
26 | 0.35 … 0.46 |
27 | 0.46 … 0.66 |
28 | 0.66 … 1.0 |
29 | 1.0 … 1.3 |
30 | 1.3 … 1.7 |
31 | 1.7 … 2.3 |
---|---|
32 | 2.3 … 3.0 |
33 | 3.0 … 4.0 |
34 | 4.0 … 5.2 |
35 | 5.2 … 6.5 |
36 | 6.5 … 8.0 |
37 | 8.0 … 10.0 |
38 | 10 … 12 |
39 | 12 … 14 |
40 | 14 … 16 |
41 | 16 … 18 |
42 | 18 … 20 |
43 | 20 … 22 |
44 | 22 … 25 |
45 | 25 … 28 |
46 | 28 … 31 |
47 | 31 … 34 |
48 | 34 … 37 |
49 | 37 … 40 |
Maintenance
The sensor doesn’t need periodic recalibration. If it appears to have dust
deposited inside, compressed air can be used with extreme care to blow it
clean.
Detailed radio settings
The Sky menu contains the settings for the wireless network.
Network: To prevent mixing the different networks (and users) data, the
network address should be set to some value not used nearby. All the devices
within one network must share the same value. The receiver will only accept
packets that have the matching network address. If an encryption key is used,
it is not necessary to use a unique network address. Default 1.
Effort: This single setting controls the LoRa bandwidth and spreading
parameters as in the table below. The bigger the value, the longer the range.
But it will consume more battery and radio band. Increasing the effort one
step will approximately add 2.5 dB in the link budget, but also double the
battery consumption caused by the radio.
The selectable Efforts are tabulated below. The LoRa bandwidth and spreading
factor are mentioned for curiosity. The estimated ranges are for reference
only, in real world the range depends heavily on the objects on the radio
path. No range can be guaranteed, a single metal wall may stop the radio
signal totally.
Effort setting| LoRa bandwidth| LoRa spreading
factor
| Estimated indoor range| Estimated real world outdoor range 30
dB/decade
---|---|---|---|---
1| 250 kHz| 7| | 1100 m
2| 250 kHz| 8| | 1300 m
3| 250 kHz| 9| | 1600 m
4 (default)| 250 kHz| 10| 30…300 m| 1900 m
5| 250 kHz| 11| | 2300 m
6| 250 kHz| 12| | 2800 m
7| 125 kHz| 12| | 3500 m
The default Effort is 4, which is good for many tasks. Each device in the
network must share the value.
The Effort setting can be set to the Custom position; then it is possible to
set the bandwidth and spreading parameters independently, as well as adjust
the frequency steplessly from 433.3 to 434.5 MHz. Normally this should not be
necessary.
Power: The transmission power; 10 means the maximum power and each step
reduces one dB. A lower value should be selected to conserve the battery and
to avoid disturbing other users of the band whenever possible. However, this
setting will not affect the battery consumption as much as the Effort setting,
which means that the first means to lower the battery consumption should be to
lower the effort if possible. While each device in the network must share the
Effort setting, the Power can be adjusted individually. In practice, Effort is
defined by the most distant device, and the Power of the nearer devices can be
lowered.
Channel: The radio frequency channel. If several LoRa/Sky networks exist
within the same area, a different frequency should be selected for each
network. The radiofrequency is 433.3 + 0.2 MHz *
(channel-1), i.e. the first channel is 433.3 MHz, the second is 433.5 etc.
Channel 4 uses 433.9 MHz which is the most crowded frequency on this band, so
it should be avoided.
Quality: This setting has three options affecting the reliability of the
packet delivery:
- Unidirectional (default): This device will transmit each reading once not expecting any acknowledgment. If the packet is lost due to a collision with another transmission or any disturbance, it is lost.
- Bidirectional: After transmitting a packet, this device will listen for an acknowledgment from a receiver and retransmit up to two times if not getting acknowledged. If there is no acknowledgment, this device will discard the packet and try only once for the next time. This setting increases the probability of successful delivery significantly but does not guarantee it.
- Buffering: This device will keep retransmitting each reading until acknowledged. The readings will be buffered until delivered as far as the buffer is not full. The buffer can hold approx. 1000 packets (400 in devices manufactured before autumn 2019). When the buffer is more than half full, the measurement intervals will be temporarily increased to slow down the filling of the buffer.
Each device can have an individual choice.
Destination : When using the Bidirectional or the Buffered quality, the
receiver that is supposed to acknowledge must be manually defined. Enter the
radio address of the receiver here. The system can have several receivers,
each picking the same radio packets, but only one must be selected to
acknowledge to avoid collisions.
Key : An authentication and encryption key for the radio. If
authentication is not desired, leave this blank. Then it is quite easy to
eavesdrop and disrupt the radio traffic. To get a secured operation, enter any
text string (up to 16 characters). Use the same key in the receiver, and
consequently in all the other transmitters. Once set, the key can’t be viewed
in the menu, it is replaced by *.
Address : The radio address of this device. Can’t be changed.
Buffer** : Displays how many percentages of the buffer is used. Should be 0
when the network is operating smoothly. This is for viewing only, can’t be
manually adjusted.
Quantity channels
The device sends the measurement quantities using the logical channels as in the table below. Note that each Kube model will send only the quantities it can measure, and which have not been disabled.
Channel | Physical quantity | Unit |
---|---|---|
1 | Temperature | °C or °F |
2 | Relative humidity | %RH |
3 | Illuminance | lux |
4 | Absolute air pressure | mbar (i.e. hPa) |
5 | Carbon dioxide concentration | ppm |
6 | Volatile organic compound |
concentration
| ppm isobutylene unless configured otherwise
7| Differential pressure| Pa
21| PM1 particulate matter| µg/m3
22| PM2.5 particulate matter| µg/m3
23| PM10 particulate matter| µg/m3
24| “PM40” particulate matter| µg/m3
26…49| Particle bins, see chapter Particle
measurement on page 15
| pcs/litre
These channel numbers are used when configuring the device for the Ovaport service or any other type of receiving system.
Maintenance
Checking the status
Press the button to light up the indicator located next to the USB connector.
If it lights green, everything is fine. If the indicator blinks red, count the
number of blinks and compare to the table below. Use the firmware version
marked on the label.
Red blinks | Meaning | What to do |
---|---|---|
V1.0-1.11 | V1.12 | |
2 | 2 | Battery low |
external power supply and backup batteries are not
necessary).
3| 3| Radio error – the radio is not
operating
| Contact the supplier.
4| 4| Network error – the device is not acknowledged by the receiver| Check
that the Sky settings match the receiver (also the Destination), and that the
receiver is operating and not
too far away.
5| 5| Internal A/D converter failure| Contact the supplier.
6| 6, 7| Temperature/humidity sensor
failure
| Contact the supplier.
7| 8| Absolute pressure sensor failure| Contact the supplier.
8| 9| Absolute pressure sensor failure| Contact the supplier.
9| 10| Sensor module failure (CO2,
VOC etc)
| Contact the supplier.
If the indicator doesn’t light up at all, the device is not operating, probably due to lack of power. Check the battery or other power supply.
Active state
By pressing the button twice, the device goes to an active state and the
indicator lights up green. In this state the measurement readings are taken
and transmitted frequently:
- Temperature, humidity, illuminance, and pressure every 15 seconds
- CO2, VOC, and particles every 60 seconds
This may be useful when troubleshooting the system.
Press the button once to exit this state. Even without pressing the button,
the device will return to its normal state in 15 minutes.
Replacing the batteries
- Remove the device from the wall holder by pushing it upwards.
- Remove the two PZ1 screws and open the cover.
- Replace the batteries with two new LR6 (alkaline AA) batteries observing the polarity as marked on the circuit board. Avoid touching the electronics.
Cleaning
If there is visible dust inside the device, blow it away with pressurized air
while avoiding too strong pressure. The enclosure exterior can be wiped with a
damp cloth, but no drop of liquid must enter the device.
Monitor menu
In the Mekuwin Mon menu, you can monitor the measurement readings. The sensors
are kept continuously on. The values update at the rate the sensor can produce
new readings, e.g. 15 sec with CO2 at its default sampling time.
- Temperature: The temperature reading in °C or °F according to the Temp unit setting.
- Humidity: The relative humidity reading in %RH.
- Lux: The illuminance in lux.
- CO2: The carbon dioxide concentration in ppm.
- different: The differential pressure reading in Pa.
- VOC: The volatile organic compound measurement reading in ppm (or another unit if a coefficient used). PM1, PM2.5, PM10, and PM40: Particle masses in µg/m3.
- Batt: The estimated remaining battery capacity in percent.
- ExtPow: Is an external power supply connected.
- RelayState: The state of the alarm relay.
- Switches: The button status for the manufacturer’s testing.
Cal menu
The calibration menu settings are only for the manufacturer’s use. They are
not explained in this manual.
Specifications
Environment
Storage -30…+60 °C, non-condensing
Operation temperature 0…+60 °C
Operation humidity Non-condensing Protection class
IP20
Enclosure material Plastic (ABS+PC)
Measurements
Weight
- RHT and -Lux: 130 g with batteries
- RHT-CO2: 160 g with batteries
- RHT-PIDVOC: 120 g
- RHT-dP: TBD
- RHT-PM0413: 150 g
- RHT-PM0440: 270 g
Dimensions
- RHT and -Lux: 95 x 75 x 27 mm
- RHT-CO2: 95 x 75 x 47 mm
- RHT-PIDVOC: 95 x 75 x 47 mm
- RHT-dP: 95 x 75 x 47 mm
- RHT-PM0413: 95 x 75 x 47 mm
- RHT-PM0440: 95 x 75 x 87 mm
- Wall mount +1 mm
Internal batteries
Type 2 pcs LR6 (AA 1.5 V alkaline). For the estimated battery life, high- quality batteries should be used, e.g. Energizer EN91.
Estimated battery life in years
Uni = unidirectional radio, Bi = bidirectional radio (ensures each reading to
be delivered)
Model | Period | Effort and bidirectionality | |
---|---|---|---|
1 Uni | 4 Uni (default) | 4 Bi | |
RHT and -Lux | 300 s (5 min) | 13 | 7 |
900 s (15 min) default | 14 | 11 | 11 |
1800 s (30 min) | 14 | 13 | 13 |
RHT-CO2 | 300 s (5 min) | 1.0 | 0.9 |
900 s (15 min) | 2.8 | 2.6 | 2.6 |
1800 s (30 min)
default
| 5| 4| 4| 3
RHT-dP| 300 s (5 min)
default
| 5| 4| 4| 2.1
900 s (15 min)| 5| 4| 4| 3
1800 s (30 min)| 5| 5| 5| 4
External supply USB
Connector Micro USB type B 5 ±0.5 V max 200 mA, no suspend function
External supply with a cable
- Connector Push-in spring connector for 0.2-0.5 mm2 conductors
- Voltage 5 ±0.5 V DC
- Consumption Average about 3 mA, momentarily max 200 mA
Sky radio
- Antenna Internal
- Center frequency 433.3…434.5 MHz user adjustable
- Bandwidth ma x 300 kHz OBW, all transmissions fit within 433.05-434.79 MHz
- Transmitting power max 10 dBm E.R.P.
- Open space range up to 5 km
- Indoor range 30 to 300 m typically with default Effort setting
Temperature measurement
- Measurement range -20…+50 °C
- Accuracy ±0,5 °C in the range of +10…+50 °C
- Step response time Approx. 45 mins to 90% of step change, still air
Humidity measurement
- Measurement range 0…100 %RH non-condensing
- Accuracy Typically ±3 %RH at a humidity of 20…80 %RH and at a temperature of +15…+30 °C
Illuminance measurement
- Measurement range 0…2000 lux or wider
- Accuracy ±20% at 50…2000 lux at 20…30 °C with a typical indoor lighting spectrum, light coming directly from front
Carbon dioxide concentration
- Measurement range 400…5000 ppm
- Accuracy ±50 ppm + 3% of reading
- Autocalibration Must see fresh air (unoccupied room) once a week
Volatile organic compound concentration
- Sensor type Photoionization detector 10.6 eV
- Measurement range 0…10 ppm isobutylene (C4H8)
- Accuracy ±50 ppb + 20% of the reading on isobutylene
- Other gases A coefficient can be entered in the settings to optimize for other target gases
- Autocalibration No autocalibration, is suitable for continuous exposure, however, must be periodically recalibrated and serviced
dP measurement
- Measurement range -125…+125 Pa
- Maximum burst pressure 3 bar
- Accuracy ±0.2 Pa +4% of reading; add 6% of reading for 1 m tube
- Alarm relay 30 VDC, max 2 A
PM0413 measurement
- Measurement range 0…1.2 million particles per litre (up to 10,000 particles per second)
- Particle sizes 0.4…12.4 μm
- Particle type For max accuracy assumed to be spherical, density 1.65 g/ml, refractive index 1.5
- Values measured PM1, PM2.5, PM10, raw counts for 16 size bins
- PM10 range 0.01…1 500 000 μg/m3
PM0440 measurement
- Measurement range 0…2.8 million particles per liter (up to 10,000 particles per second)
- Particle sizes 0.4…40 μm
- Particle type For max accuracy assumed to be spherical, density 1.65 g/ml, refractive index 1.5
- Values measured PM1, PM2.5, PM10, non-standard PM40, raw counts for 24 size bins
- PM10 range 0.01…1 500 000 μg/m3
Warnings
The device must not be disposed of in household waste. Observe local regulations concerning the disposal of electrical waste. The device may contain a battery
Manufacturer
Nokeval Oy Rounionkatu 107 FI-37150 Nokia
Finland
Phone +358 3 342 4810 WWW http://www.nokeval.com/ Email
sales@nokeval.com
EU Declaration of Conformity
Object of declaration: wireless measuring device
Model/Type:
- Kube-Sky-RHT
- Kube-Sky-RHT-CO2
- Kube-Sky-RHT-DP
- Kube-Sky-RHT-PIDVOc
- Kube-Sky-RHT-PMO413
- Kube-Sky-RHT-PM0440
- Wireless 433.92MHz temperature, humidity, O2, differential pressure, VoC and
Description:
particle transmitters based on LoRa modulation.
Manu facturer:
Nokeval Oy
Rounionkatu 107, 37150 Nokia, Finland
www.nokeval.com
tel. +358 33424 800
support@nokeval.com
This declaration of conformity is issued under the sole responsibility of the
manufacturer.
The object of the declaration described above is in conformity with the
relevant Union harmonization legislation:
- Directive (RED) 2014/53/EU
- Directive (RoHS) 2011/65/EU
The conformity is given based on the following harmonized standards:
The conformity is given based on the following harmonized standards:
RED:
- EN 300 220-2 V3.1.1 (2017-02)
- EN 301 489-1 V2.1.1 (2017-02)
- EN 301 489-3 V2.1.1 (2017-03)
EMC:
EN 61326-1:2013
LVD:
EN 61010-1:2010
RoHS:
EN 50581:2012
The product is marked with a CE mark to indicate compliance.
Product is designed and manufactured in Final and.
Signed for and on behalf of Nokeval Oy:
At Nokia 16.10.2018
Jani Vähàsöyrinki, Managing Director
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>