BATTERY BACKUP POWER BBP-AR-33-EBP Battery Cabinet Installation Guide

June 5, 2024
BATTERY BACKUP POWER

BATTERY BACKUP POWER BBP-AR-33-EBP Battery Cabinet

BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-pro

Cabinet Overlook

  • Dimension (D x W x H): 780 mm x 250 mm x 840 mm
  • Net weight for empty cabinet: 255kgBATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-1

Preparation

Mechanical Overview

  • Battery cabinet The “F” marks the front side of the battery cabinet.
  • Battery shelf The cabinet includes four trays, from L1 (bottom) to L4 (top).BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-2

Battery Requirement

  • Lead-Acid cell type and quantity : 12V 9.4Ah x 80 pieces
  • Maximum size for lead-acid battery (L x W x H ) :65.8x 98.6x 152 mm.

Cable SpecificationBATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-
Cabinet-4

Note: PE-Wiring 6 AWG, Nut Torque: 105.9 lbf-in.

GND Connection Diagram

Please refer the below assembly step before operating.

  1. Remove the back cover on the rear panel.
  2. Take off the knockouts.
  3. Connect the ground wire then use nut to fix.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-7

Caution:

  • UPS and Remote Battery Supply Cabinet employed battery case with HB flame class: “Not for use in a computer room as define in the standard for the Protection
    of Electronic Computer/Data Processing Equipment ANSI/NFPA 75”.

  • Battery replacement and remote battery supply cabinet installation shall be handled by SERVICE PERSONNEL only. Remote battery supply cabinet installation with UPS.

  • Disconnection of all AC source and the DC source is required to de-energize this unit before servicing.

Battery WiringBATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-
Cabinet-8BATTERY-BACKUP-POWER-BBP-AR-33
-EBP-Battery-Cabinet-9

Installation

  1. Remove the carton and foam.
  2. Remove fixing plates on the two sides of the UPS by removing all screws as shown below.
  3. Take out top and side panels by removing all screws as shown below. BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-12
  4. Remove two (for 20K) and two (for 15K) battery fixing bars on the left side of the UPS.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-13
  5. Please install 10 battery packs as shown below to the bottom layer (L1). Be sure to keep the terminal sides of all batteries up.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-14
  6. Install another 10 battery packs as shown below to the third layer (L2). Be sure to keep the terminal sides of all batteries up. BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-15
  7. Install another 10 battery packs as shown below to the second layer (L3). Be sure to keep the terminal sides of all batteries up.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-16
  8. Install another 10 battery packs as shown below to the top layer (L4). Be sure to keep the terminal sides of all batteries up.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-17
  9. Put two (for 20K) and two (for 15K) fixing battery bars back to the original place.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-18
  10. Prepare to install the battery on the right side and first remove two (for 20K) and two (for 15K) battery fixing bars.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-19
  11. Battery installation is from L1 to L4 according to the step5 to step8.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-20
  12. Put two (for 20K) and two (for 15K) fixing battery bars back to the original placeBATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-21
  13. Use one cable A to connect #10 and #11 batteries (for 15K and 20K). Use one more cable A to connect #30 and #31 batteries as shown below (only for 20K).BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-22
  14. On the left side of the UPS, use 36 pieces (for 20K) and 17 pieces (for 15K) of cable B72 PCS (for 20K) and cable B34 PCS (for 15K) to connect two terminals on all batteries as shown below.
  15. Use one cable A to connect #10 and #11 batteries (for 15K and 20K). Use one more cable A to connect #30 and #31 batteries as shown below (only for 20K).BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-25
  16. On the right side of the UPS, use one meter to measure the positive pole of #40 battery and the negative pole of#21 battery. (DC voltage should be within 120V~130V)BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-26
  17. Measure the positive pole of #20 battery and the negative pole of #1 battery. (DC voltage should be within 120V~130V).BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-27
  18. On the right side of the UPS, use one meter to measure the positive pole of #40 battery and the negative pole of#21 battery. (DC voltage should be within 120V~130V)BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-28
  19. On the left side of the UPS, use one meter to measure the positive pole of #1 battery and the negative pole of#20 battery. (DC voltage should be within 120V~130V)BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-29
  20. On the left side of the UPS, there are 6 cables (for 20K) and 4 cable (for 15K) with label marks. Please follow below chart to connect each cable.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-29
  21. On the right side of the UPS, there are 6 cables (for 20K) and 4 cable (for 15K) with label marks. Please follow below chart to connect each cable.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-30
  22. Put top and side panels back to original place as shown below.BATTERY-BACKUP-POWER-BBP-AR-33-EBP-Battery-Cabinet-31