TENEO LoRaWAN CO2 Stoplicht User Manual
- June 5, 2024
- TENEO
Table of Contents
Manual
LoRaWAN CO2 stoplicht
Version: 2. 0
Manual LoRaWAN CO2 stoplicht
Versioning
Version: | Date: | Description: | Author: |
---|---|---|---|
1.0 | November 30th, 2020 | Publication first version | I. Heideman |
2.0 | January 26th, 2021 | Publication second version: added information | |
about firmware versions, new downlinks, other label information, etc. | I. |
Heideman
Registry
Understanding: | Definition: |
---|---|
LoRaWAN | Abbreviation for: Long Range Wide Area Network. A Low Power, |
Wide Area (LPWA) network protocol specifically developed to connect wireless
battery-powered ‘things’ to the Internet in regional, national or global
networks. (More information see: www.lora-alliance-org/about-
lorawan).
Node| A node is a device equipped with a transmitter. This transmitter
uses LoRaWAN modulation, which gives the device the possibility to realize
communication via the LoRaWAN network.
Gateway| A device that takes care of the translation and therefore also
the connection of two incompatible networks with each other. In this case, the
gateway provides the connection between the respective LoRaWAN network and the
internet.
Backend| A backend is a program or part of a program that is invisible
to the user. It can possibly be addressed via a command-line interface. The
interaction with users does not take place directly with the backend but via
the graphical user interface or frontend of the program.
OTAA| Abbreviation for Over the Air Activation. OtAA uses a join
procedure to activate a node on a network.
Uplink| A LoRaWAN message sent by the node to the gateway.
Downlink| A LoRaWAN message sent from the gateway to the node.
Hexadecimal| Sixteen-part system with numbers 0 to F is indicated by 0x
before the number. Example: 0xFF is a hexadecimal notation of the decimal
number 255.
1. Foreword
This document is intended as a user manual for the LoRaWAN CO2 Stoplicht from
Teneo Sales B.V. The purpose of this document is to provide a clear overview
of how the LoRaWAN CO2 Stoplicht can be installed, used and maintained.
In addition, any hazards and/or risks are pointed out in order to inform the
user as well as possible about the LoRaWAN CO2 Stoplicht.
In addition to this user manual, a ‘Quick Start Guide’ can also be used; this user manual always prevails over the Quick Start Guide.
The Quick Start Guide and all other documents referred to in this guide can be downloaded from: www.co2-stoplicht.online/downloads.
Figure 1: Product photo LoRaWAN CO2 Stoplicht.
2. Introduction
2.1. Product description
The LoRaWAN CO2 stoplicht is a product that measures CO2 level, temperature
and humidity and transmits these measured values via the LoRaWAN wireless
communication network.
In addition, the CO2 stoplicht has LEDs that change color when the measured
CO2 value exceeds a certain threshold.
On the basis of this direct feedback by the LEDs, (extra) can then be ventilated, to ensure that the air quality in the measured room returns to the desired level.
The thresholds are based on the requirements for CO2 meters according to Article 3.5 of the Bouwbesluit 2012 from the Netherlands¹, but can also be adjusted remotely by means of a downlink.
2.2. Product specifications
Category: | Part: | Specification: |
---|---|---|
Physically | Dimensions: | H: 166 mm, Ø: 85 mm |
Material: | ABS | |
Weight: | 310 grams | |
IP-rating: | IP 20 | |
Conditions of use | Temperature: | – 20 °C to 50 °C |
LoRa WAN | Transmission power: | 14 dBm |
Class: | A (baseline) | |
Activation method | OTAA | |
Frequency | EU 868 MHz (863 – 870 MHz) | |
Encryption | AES128 | |
Power Supply | 5V DC | |
CO 2 sensor | Sensor: | SCD30 (Sensirion) |
Measuring range | 400 ppm – 10,000 ppm | |
Accuracy | ± 30 ppm | |
Humidity sensor | Measuring range | 0% – 100% RH |
Accuracy | ± 3% RH | |
Temperature sensor | Unit | Celsius |
Measuring range | – 20 °C – + 50 °C | |
Accuracy | ± 0.5°C |
¹ Source: https://rijksoverheid.bouwbesluit.com/Inhoud/docs/wet/bb2012_reg/hoofdstuk-3/artikel-3.5
3. Operation
3.1. Preparation
| Warning!
---|---
In case of extreme heat (temperature > 70 °C), the node may be damaged.
Therefore, do not use hot air heating sources near (< 1.5 meters) of the
sensor.
The CO2 stoplicht is supplied with USB-A to micro USB cable. A 5 V USB power supply can then be used for this, this 5V power supply is not included with the stoplicht.
In the photo below you can see the contents of one box of CO2 stoplicht.
Figure 2: Contents box CO2 stoplicht.
3.2. Installation/Assembly
The CO2 stoplicht can be placed on the tables or surfaces, but in addition, the CO2 stoplicht with the supplied wall mounting bracket can also be attached to walls or other surfaces.
For mounting the wall bracket and attaching the stoplicht there is a square hole in the back of the stoplicht, through this square hole the CO2 stoplicht can be hooked to the wall bracket.
On the next page of this manual we see with photos an explanation of how exactly the stoplicht can be fixed.
Figure 3 and 4 : Mounting wall mounting bracket correctly.
In order to secure the stoplicht, it is important that the wall bracket is fixed in such a way that the hook points upwards; as also shown in Figure 4.
The stoplicht can then be attached to this. This will look like the one shown below in Figure 5.
Figure 5: Example of CO2 stoplicht attached to the wall by wall bracket.
It is also possible to equip the wall bracket with an anti-theft protection.
This security can be purchased at an additional cost.
3.3. Usage
The CO2 stoplicht can be put into operation by plugging the power supply into the wall socket.
Then the stoplicht starts up and immediately starts performing the first CO2 measurement. It may take a while (± 20 seconds) for the LEDs to light up.
3.4. Error messages
The sensor is equipped with the functionality to send status messages. The node does this by sending a status message on Port 223; as also described in Chapter 5.1 of this Manual.
3.5. De-commissioning
When the sensor is replaced or removed, for example because the sensor no longer functions, the CO2 stoplicht must be replaced in its entirety.
For other information see also section 6.1.2. WEEE 2012/19/EU.
4. LoRaWAN
The sensor is equipped with LoRaWAN for the communication of the sensor data to the user (other than through the LEDs). The sensor is configured at the EU 863-870 MHz bandwidth.
At LoRaWAN, the node has a so-called ‘join procedure’ in which the node logs on to the LoRaWAN network in question. There are two ways in which a node can join the network; by means of Over the Air Activation (OTAA) or Activation by Personalization (ABP). Teneo’s nodes only support the OTAA’s procedure. OTAA is generally seen within the LoRa protocol as the most robust and secure way of joining the network.
For the purpose of being able to set up the sensors in a LoRaWAN backend and for the unique identification of each sensor on the LoRaWAN network, a set of unique ‘keys’ isused: namely the DeviceEUI, AppKey and AppEUI.
The DeviceEUI and AppKey differ for each device individually, while the AppEUI may be the same per set of sensors.
These different keys are structured and recognizable as follows:
– DeviceEUI, for example: 00FBE52F1ECD66C5 (EUI-64);
– AppKey, for example: C56A32026BD0FDDAB93DA22FA87623A0;
– AppEUI, for example: 00FBE52F1ECD66C6 (EUI-64);
These three keys are all preconfigured by Teneo and cannot be changed by the user. These keys are made available to the user to connect the sensors with a specific back-end.
The DeviceEUI of each sensor also stares on each sticker, as shown in the example below.
Legenda:
- Model/type nummer;
- Device EUI;
- Firmware versie;
Furthermore, (from CO2 stoplichts with firmware version V1.20 onwards) a model/type number can be found on the label with the relevant firmware version (which is programmed in the CO2 stoplicht) is mentioned and a QR code can optionally be displayed.
This QR code can be scanned for any other information. For the AppKey and AppEUI, your supplier can be contacted if necessary. If your product has been delivered directly by Teneo, it can be further consulted in Teneo’s client portal via https://www.clientportal.teneo-iot.nl.
In addition, other information can be mentioned in this QR code, but it only serves for internal reference and is not necessary for the commissioning of the sensor in question.
5. Payload
5.1. In advance
In this document, all bits are read as “Little-endian”. This means that all bits are read from right to left. Bytes are read from left to right. Both bytes and bits start from the number 0.
Example with the decimal number 279716668:
In hexadecimal:
Binary:
5.1.1. Definitions:
– Node: The device with the microcontroller developed by Teneo.
– Uplink: A message from the node to the LoRaWAN network.
– Downlink: A message from the LoRaWAN network to the node.
– Payload: The data sent or received by the node.
– 0xA3: The hexadecimal number A3, decimal is 163 and binary this is 1010
0011.
– Unsigned int: A positive integer.
– Int: An integer (positive or negative).
– RFU: Reserved For Future Use.
– Float: A decimal number (positive and negative).
5.2. Firmware versions
Since the launch of the CO2 stoplicht, several firmware improvements have been
made.
The following is a table with a brief overview of the different firmware
versions, the release date of this firmware and a brief description of the
changes/improvements.
Firmware version: | Release date: | Content: |
---|---|---|
V1.10 | 19-11-2020 | Initial release/launch. |
V1.20 | 17-12-2020 | Improved measurement of temperature and humidity. |
V1.30 | 21-01-2021 | Automatic calibration default enabled |
Manual calibration option added
Added downlinks for setting air pressure and altitude above sea level
Default thresholds LEDs adjusted(green: up to 1000 ppm, orange: 1001 to 1400
ppm, red: 1401 ppm or higher).
5.3. Uplinks
Uplink messages from a Teneo LoRaWAN sensor consist of two components: the port and the payload. Each uplink payload starts with one header byte.
5.3.1. Port:
The port is a number with a range of 1 to 223. The value of the port indicates the type of message.
5.3.2. Header byte:
Our software gives a header with each message as the last byte of the payload. The header consists of a type and parameters:
Bit | Description |
---|---|
7..6 | Header Type |
5..0 | Parameters |
The following types are defined:
Value (bit 7..6) | Name | Description |
---|---|---|
00 | Default | If there is nothing to report, this header type is used. |
This type has no parameters.
01| MultiMessage| LoRa messages have a limited length. With
MultiMessage, a full message is distributed across multiple uplinks because it
doesn’t fit in 1 uplink. The current version of the program will not go over
that. MultiMessage does not occur.
10| Status| Status messages are given when the node starts up or
something has gone wrong. These messages always go to port 223.
11| Power| When battery protection is used, these messages indicate the
state in which it is located. These messages always go to port 223.
Default message:
Bit number | Name | Description |
---|---|---|
3..0 | System voltage | Indicates the tension of the node. Calculation: |
System voltage = 2 + Batterydisplay/ 10.
The most commonly used header is a standard header with a battery display. This header will be used unless otherwise described. For example, the default header looks like this: 0000 1100 or 0x0C.
The first two bits( 00 00 1100) indicate that it is a default message.
The second two bits (00 00 1100) have no meaning in this case.
The last four bits (0000 1100 )contain the battery display. These first
four bits represent the number 12. This means that the system voltage is: 2 +
(12/10) = 3,2 Volts.
Other header types:
The MultiMessage is not explained because no large messages are sent.
Also, the Status messages are not explained further in this documentation.
5.3.3. Message (according to V1.10 and V1.20):
With firmware versions V1.10 and V1.20, the node can send the following uplink messages:
Port | Message type | Description |
---|---|---|
1 | CO2 Measurement | This message displays the calibration option and CO2 |
measurement, along with an optional temperature and humidity measurement.
223| Status| Port 223 sent status messages.
Port 1: CO2 Measurement:
Byte | Length | Description |
---|---|---|
0 | 1 | Header |
1 | 1 | RFU |
2..5 | 4 | CO2 display |
6..7 | 2 | Temperature display |
8..9 | 2 | Humidity display |
These values are not the actual values of the measurements, they must first be converted. For this calculation see the relevant chapters.
The CO2 sensor controls the current measurement values.
This message is sent with an adjustable interval (period time).
For example, this message looks like this: 0x0F 00 00 01 53 3B 07 53 11 4D
The meaning of this post is:
Byte 0:0x0F = System voltage: 3.5 V
Byte 1:0x00 = RFU
Byte 2..5:0x00 01 53 3B = 868.43 PPM
Byte 6..7:0x07 53 = 18.75 degrees Celsius
Byte 8..9:0x11 4D = 44.29% RH
Header:
Bit number | Description |
---|---|
3..0 | Battery view |
The system voltage is calculated as follows:
2+ (Battery display/10)
If the battery display in the message is 0x0C (12), the system voltage
calculation becomes:2 + (12/10) = 3.2 V.
Measured CO2 value:
Byte number | Length | Description |
---|---|---|
2..5 | 4 | CO2 display |
This byte shows the measured CO2 value. To convert this value to the actual
measured value, this calculation must be used:
CO2 in PPM = CO2 value /100
0x0001533B: This has a decimal value of 86843.
86843/100 = 868.43 PPM
Measured temperature:
Byte number | Length | Description |
---|---|---|
6..7 | 2 | Temperature value |
The temperature can be negative, to convert it, the MSB must be looked at.
If this MSB is 1 then the temperature is: – (65536 - temperature value) /100.
If this MSB is 0 then the temperature is: temperature value /100.
For example, at value 0x0753: is binary: 0 001 0001 0100 1101, last bit is
0 so:
0x0753 = decimal 1875: the temperature = 1875/100 = 18.75 degrees Celsius.
For example, at value 0xFCE0: is binary: 1 111 1100 1110 0000, last bit is
1 so:
0xFCE0 = decimal 64736: temperature = – (65536 – 64736) / 100 = -8.00 degrees
Celsius.
Humidity measured:
Byte number | Length | Description |
---|---|---|
8..9 | 2 | Humidity value |
This byte shows the measured humidity value. To convert this to the actual value, this calculation must be used:
Humidity % RH = Humidity value / 100
For example, the display = 0x114D = 4429.
Humidity = 4429/100 = 44.29% RH.
5.3.4. Message (according to firmware version V1.30):
The node can send the following uplink messages:
Port | Message type | Description |
---|---|---|
1 | CO2 Measurement | This message displays the calibration option and CO2 |
measurement, along with an optional temperature and humidity measurement.
223| Status| Port 223 sent status messages.
Port 1: CO2 Meting:
Byte | Length | Description |
---|---|---|
0 | 1 | Header |
1 | 1 | Calibration option & Automatic self-calibration |
2..5 | 4 | CO2 display |
6..7 | 2 | Temperature display* |
8..9 | 2 | Humidity display* |
This value is not the actual values of the measurements, they must first be converted. For this calculation see the relevant chapters.
The CO2 sensor controls the current measured values, along with a calibration option in byte 1 to indicate whether the CO2 value is derived from an additional calibration. In addition to this option, it is also indicated whether automatic calibration is on, this can be seen by whether bit 3 is on
Byte 1 = 0x09 = 0000 1001 : Air pressure calibration option, automatic
calibration on.
Byte 1 = 0x02 = 0000 0010 : Height calibration option, automatic calibration
off.
*The temperature and humidity are optionally controlled, see “downlinks FPORT 10” for more information. If both are not sent along, the message is 4 bytes shorter.
This message is sent with an adjustable interval (period time).
For example, this message looks like this: 0x0F 08 00 01 53 3B 07 53 11 4D
The meaning of this post is:
Byte 0:0x0F = Systemvoltage: 3.5V.
Byte 1:0x0 8 = No additional calibration option, automatic calibration is on
Byte 2..5 0x00 01 53 3B = 868.43 PPM
Byte 6..7 0x07 53 = 18,75 C;
Byte 8..9 0x11 4D = 44.29 %RH
Header:
Bit number | Description |
---|---|
3..0 | Battery view |
The system voltage is calculated as follows:
2+ (Battery display/10)
If the battery display in the message is 0x0C (12), the battery voltage
calculation becomes:2 + (12/10) = 3.2 V.
Calibration option:
Byte number | Length | Description |
---|---|---|
1 | 1 | Calibration option |
This byte indicates which calibration option is set.
0x00 (binary 0000 0000) = No calibration option, automatic calibration off.
0x01 (binary 0000 0001) = Air pressure calibration, automatic calibration
off.
0x02 (binary 0000 0010) = Altitude compared to sea level calibration,
automatic calibration off.
0x08 (binary 0000 1000) = No calibration option, automatic calibration on.
0x09 (binary 0000 1001) = Air pressure calibration option, automatic
calibration on.
0x0 A (binary 0000 1010) = Altitude compared to sea level calibration option,
automatic calibration on.
Measured CO2 value:
Byte number | Length | Description |
---|---|---|
2..5 | 4 | CO2 display |
This byte shows the measured CO2 display. To convert this display to the measured value, this calculation must be used: CO2 in PPM = CO2 display/100
0x0001533B: This has a decimal value of 86843.
86843/100 = 868.43 PPM
Measured Temperature:
Byte number | Length | Description |
---|---|---|
6..7 | 2 | Temperature display |
The temperature can be negative, to convert it, the MSB must be looked at.
If this MSB is 1, the temperature is: -(65536 temperature display)/100.
If this MSB is 0 then the temperature is: temperature display /100.
For example, at value 0x0753: is binary: 0 001 0001 0100 1101, last bit is
0 so:
0x0753 = decimal 1875: the temperature = 1875/100 = 18.75 degrees Celsius.
For example, at value 0xFCE0: is binary: 1 111 1100 1110 0000, last bit is
1 so:
0xFCE0 = decimal 64736: temperature = -(65536-64736)/100 = -8.00 degrees
Celsius.
Measured Humidity:
Byte number | Length | Description |
---|---|---|
8..9 | 2 | Humidity display |
This byte shows the measured humidity display. To convert this to the actual value, this calculation must be used:
Humidity %RH = Humidity display/100
For example, the display = 0x114D = 4429.
Humidity = 4429/100 = 44,29 %RH.
5.4. Downlinks
In order to change the settings of the node, downlinks can be sent to the node. As with the uplinks, the FPort indicates what type of message it is, but no header needs to be sent.
The following downlinks can be sent:
FPort | Message type | From version: | Description |
---|---|---|---|
1 | Period time | V1.10 | Adjusts the time between two standard downlink |
messages.
8| Air pressure compensation| V1.30| An air pressure compensation for
the CO2 measurements, expressed in millibar.
9| Height compared to sea level compensation| V1.30| The height of the
CO2 stoplicht specified for the CO2 sensor for compensation relative to the
sea level, expressed in meters.
10| Display temperature/ humidity| V1.30| Setting for displaying
temperature, humidity or both.
11| LED Borders Green/Orange/Red| V1.10| Specify the limit values for
when the red, orange, and green LEDs should turn on/off.
12| Automatic and manual calibration| V1.30| Turning the automatic
calibration and/or manual calibration function of the CO2 sensor on/off.
13| Settings behavior| V1.10| Setting whether the LEDs should be used
In the table above, version indicates from which firmware version this downlink is incorporated into the CO2 stoplicht. So when it says “V1.10” here, this means that this downlink can be used at all stoplichts with V1.10 or newer. When “V1.30” is displayed here, this means that this downlink can be used at all stoplichts with V1.30 or newer.
FPort 1: Period time
Byte | Length | Description |
---|---|---|
0..3 | 4 | Period time in seconds |
The period time message is used to set how much time (in seconds) there is between two default messages. This set time is the desired time, it can vary by several percent. The minimum period time will always be LoRaWAN’s waiting time (derived from the duty cycle).
Payload = 0x00 00 0E 10 = 3600 seconds (A message every hour)
FPort 8: Air pressure compensation
Byte | Length | Description |
---|---|---|
0..1 | 2 | Air pressure in millibar |
Here an air pressure can be specified that the CO2 sensor uses to make a more
accurate measurement.
The air pressure must be specified in millibar. If set, the calibration option
of the CO2 Measurement uplink will be set to 0x01. The sensor can never take
into account both air pressure and height. If these are both set, this
setting will be used.
If the value 0 is set, this calibration will not be used.
Payload: 0x0411: 0411 = 1041 so there is a compensation of 1041 millibars
FPort 9: Altitude relative to sea level
Byte | Length | Description |
---|---|---|
0..1 | 2 | Altitude above sea level in meters |
Here the height of the sensor can be adjusted (in meters above sea level). This will be used as an additional calibration value when calculating the CO2 value. If this calibration is set, the calibration option in the CO2 measurement uplink will be on 0x02. If air pressure compensation is set, this setting will not be used, so only if air pressure is set to 0 will this calibration be calculated.
If the value 0 is set, this calibration will not be used. Negative values are not possible.
Payload: 0x0342: 0342 = 834 so there is an altitude compensation of 834 meters above sea level
FPort 10: Temperature/humidity display
Byte | Length | Description |
---|---|---|
0 | 1 | Display byte of temperature and humidity. |
Here it can be adjusted whether the sensor sends the temperature and/or
humidity.
If they are both not sent along, the CO2 measurement will be 4 bytes shorter.
If 1 of the 2 is set, the other value will be at its default value.
This default value is for temperature: 0x7FFF and for humidity 0xFFFF.
Bit number | Name | Description |
---|---|---|
7..2 | RFU | – |
1 | Humidity display | Indicates whether the humidity is controlled. |
0 | Temperature display | Indicates whether the temperature is controlled. |
Humidity display:
This bit indicates whether the humidity is given, if it is set to 0 together with temperature display, the uplink will be 4 bytes shorter.
If it is at 0 but temperature at 1, then the humidity sent will always be 0xFFFF.
Bit 1 = 1: control humidity.
Bit 1 = 0: Do not control humidity.
Temperature display:
This bit indicates whether the humidity is given, if it is set to 0 together with temperature display, the uplink will be 4 bytes shorter.
If it is at 0 but humidity at 1, then the controlled temperature will always be 0x7FFF.
Bit 0 = 1: control the temperature.
Bit 0 = 0: Do not send temperature.
Payload: 0x03(binary:00000011): temperature and humidity are sent along with the CO2 value.
FPort 11: LED borders Green/Orange/Red:
Byte| Length| Description| Default V1.20:| Default
V1.30:
---|---|---|---|---
0..1| 2| Minimum value green| 0x0000| 0x0000
2..3| 2| Maximum value green| 0x041A| 0x03E8
4..5| 2| Minimum value orange| 0x041B| 0x03E9
6..7| 2| Maximum value orange| 0x060D| 0x0578
8..9| 2| Minimum value red| 0x060E| 0x0579
10..11| 2| Maximum value red| 0xFFFF| 0xFFFF
Here the limit values of the green/orange/red LEDs can be set, if the CO2 measurement is equal or between these 2 values, the corresponding LED will turn on *.
If both values of a certain LED are set to 0, the LED will never be on.
The example below uses the default values.
Example:
Payload 0x0000 03E8 03E9 0578 0579 FFFF:
- This setting only has an effect if the LED indicator in the behavior setting is turned on see “FPort 13 Behavior Settings”.
FPort 12: Automatic and manual calibration
Byte number | Length | Description |
---|---|---|
0 | 1* | Automatic calibration on/off |
0..2 | 3* | Manual calibration incl. reference value of manual calibration |
in ppm
- The length of this downlink is 1 byte when automatic calibration is turned on or off and 3 bytes when manual calibration is used.
With this downlink, the automatic calibration or manual calibration can be turned on. How these can be set is described here.
Byte 0 = 0x00: Automatic calibration off
Byte 0 = 0x01: Automatic calibration on
Byte 0..2= 0x02 nnnn: Re-forced (manual) calibration; nnnn is the calibration
CO2 value in PPM, converted to hex.
Automatic calibration:
By turning on automatic calibration, the sensor will recalibrate itself in a
week. It is important that the sensor remains on continuously, otherwise the
calibration may take longer.
The automatic calibration continues until it is switched off again with 0x00.
A manual calibration does not affect the on or off of the automatic
calibration.
Note: When switching on/using automatic calibration, the CO 2 stoplicht
must be in fresh air (400 ppm) for at least 1 hour a day.
Most buildings have their air quality in order in such a way that usually once
a day (during the night) the air quality level is at/around 400 ppm.
Manual calibration:
With the manual calibration, a new calibration value can be set, this can be done by setting byte 0 to 0x02 and then setting a ppm value in byte 1..2.
Payload 0x01: The automatic calibration is turned on, can be turned off with 0x00
Payload 0x020190: The manual calibration is set with a value of 400ppm(0x0190).
FPort 13: Settings behavior
Byte | Length | Description |
---|---|---|
0 | 1 | Behavior settings |
With this setting, the ‘behavior’ of the sensor can be determined.
The byte has a limited meaning:
0x01: LEDs are off
0x02: LEDs are on. This is the default setting
Example:
Payload: 0x02 (binary:00000010): stoplicht mode is on and the LEDs are used.
6. Regulations
6.1. CE Certification
6.1.1. EU Declaration of Conformity
Manufacturer: Teneo Sales B.V.
Product: LoRaWAN CO2 Stoplicht
Type designation: 01COS
Batch/serial number: TBV20-01COS-01LR
Teneo Sales B.V. hereby declares that the “LoRaWAN CO2 stoplicht” complies with the Radio Equipment Directive (2014/53/EU).
The full text of the Declaration of Conformity is available on our website: www.co2-stoplicht.online/downloads.
6.1.2. WEEE 2012/19/EU:
The node, including all components, must not be disposed of in household
and/or industrial waste. Users are obliged to dispose of the end-of-life node
in accordance with the requirements of the WEEE Regulation (waste electronic
and electrical equipment) in order to contribute to the protection of the
environment and the reduction of waste (recycling).
For further information on how this can be done, please contact a certified
collection party.
Teneo Sales B.V. is a member of Wecycle and Stibat in order to fulfil its obligations as a producer, following the WEEE Regulations.
© Copyright 2021 Teneo Sales BV.