SONBUS SM5391B RS485 Interface Outdoor Temperature and Humidity Illuminance Integrated Sensor User Manual
- June 5, 2024
- SONBUS
Table of Contents
- SONBUS SM5391B RS485 Interface Outdoor Temperature and Humidity
- Technical Parameters
- Product Size
- How to wiring
- Application solution
- How to use
- Communication Protocol
- Read and modify device address
- Read and modify baud rate
- Read and modify correction value
- Disclaimer
- Contact Us
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SONBUS SM5391B RS485 Interface Outdoor Temperature and Humidity
Illuminance Integrated Sensor
SM5391B uses the standard RS485 bus MODBUS-RTU protocol, easy access to PLC, DCS, and other instruments or systems for monitoring temperature, humidity, and Illuminance state quantities. The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability can be customized RS232, RS485, CAN,4 20mA, DC0~5V\10V, ZIGBEE, Lora, WIFI, GPRS, and other output methods.
Technical Parameters
Technical parameter | Parameter value |
---|---|
Brand | SONBEST |
Temperature measuring range | -50℃~120℃ |
Temperature measuring accuracy | ±0.5℃ @25℃ |
Humidity measuring range | 0~100%RH |
Humidity accuracy | ±3%RH @25℃ |
Illuminance measuring range | 0~20 0000Lux |
Illuminance allow deviation | ±7% |
Repeatability test | ±5% |
Illuminance detection chip | Import digital |
Wavelength range | 380nm~730nm |
Communication Interface | RS485 |
Default baud rate | 9600 8 n 1 |
Power | DC6~24V 1A |
Running temperature | -40~80°C |
Working humidity | 5%RH~90%RH |
Product Size
How to wiring
Application solution
How to use
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the default baud rate is 9600,8,n,1 .
Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the
upper computer sends the command: 01 03 00 00 00 03 05 CB.
Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 00 | 00 03 | 05 CB |
For the correct query frame, the device will respond with data: 01 03 06 00 7B 00 00 00 00 C5 7F , response format:
Address| Function
Code
| Length| Data 1| Data 2| Data 3| Check Code
---|---|---|---|---|---|---
01| 03| 06| 00 79| 00 7A| 00 7B| C5 7F
Data description: The data in the command is hexadecimal, take data 1 as an
example, 00 79 is converted to decimal value as 121, assuming the data
magnification is 100, then the real value is
121/100=1.21, Others and so on. For illuminance, since each parameter occupies
2 bytes and the actual resolution of illuminance in the 200,000 range is lower
than 10, we use 20,000 or 20,000 to express 200,000, that is The magnification
is 10. For example, when the read data is 839, the actual illuminance value is
8390LUX.
Common data address table
Configuration
Address
| Register Address| Register
Description
| Data Type| Value Range
---|---|---|---|---
40001| 00 00| temperature| Read Only| 0~65535
40002| 00 01| humidity| Read Only| 0~65535
40003| 00 02| Illuminance| Read Only| 0~65535
40101| 00 64| Model Code| Read/Write| 0~65535
40102| 00 65| total number of
measuring points
| read/write| 1~20
---|---|---|---|---
40103| 00 66| device address| read/write| 1~249
40104| 00 67| baud rate| read/write| 0~6
40105| 00 68| communication
mode
| read/write| 1~4
40106| 00 69| protocol type| read/write| 1~10
Read and modify device address
Read or query device address
If you don’t know the current device address and there is only one device on
the bus, you can query the device address through the commandFA 03 00 66 00 01
71 9E.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
FA | 03 | 00 66 | 00 01 | 71 9E |
FA means 250 is the general address, when you don’t know the address, you can use 250 to get the real device address, 00 66 is the device address register. For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 01 79 84, and its format parsing is shown in the following table:
Device Address | Function Code | Start Address | Model Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 01 | 79 84 |
In the response data, the first byte 01 represents the real address of the current device.
device address
For example, if the current device address is 1 and we want to change it to
02, the command is: 01 06 00 66 00 02 E8 14.
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 66 | 00 02 | E8 14 |
After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27 , and its format analysis is shown in the following table:
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
02 | 06 | 00 66 | 00 02 | E8 27 |
In the response data, after the modification is successful, the first byte is the new device address. Generally, after the device address is changed, it will take effect immediately. At this time, the user needs to change the query command of his software accordingly.
Read and modify baud rate
Read baud rate
The default factory baud rate of the device is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol. For example, to read the baud rate ID of the current device, the command is: 01 03 00 67 00 01 35 D5 , the format is parsed as follows.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 67 | 00 01 | 35 D5 |
Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200. For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 03 F8 45, and its format analysis is shown in the following table:
Device Address | Function Code | Data Length | Baud Rate Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 03 | F8 45 |
According to the baud rate code, 03 is 9600, that is, the baud rate of the current device is 9600.
Change the baud rate
For example, change the baud rate from 9600 to 38400, that is, change the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 16 .
Device Address | Function Code | Register Address | Target Baud Rate | Check Code |
---|---|---|---|---|
01 | 06 | 00 67 | 00 05 | F8 16 |
Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5. The new baud rate will take effect immediately, and the device will lose response at this time, and the baud rate of the device needs to be checked and accordingly Modified.
Read and modify correction value
Read correction value
When there is an error between the data and the reference standard, we can
reduce the display error by adjusting the correction value. The correction
difference can be modified in a range of plus or minus 1000, that is, the
value range is 0-1000 or 64535 -65535. For example, when the displayed value
is too small by 100, we can correct it by adding 100. The command is: 01 03 00
6B 00 01 F5 D6 . In the command, 100 is hexadecimal 0x64 ;If you need to
reduce it, you can set a negative value, such as -100, the corresponding
hexadecimal value is FF 9C, the calculation method is 100 65535=65435, and
then converted to hexadecimal, it is 0x FF 9C. Device The correction value
starts from 00 6B. We take the first parameter as an example to illustrate.
When there are multiple parameters, the correction value is read and modified
in the same way.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 6B | 00 01 | F5 D6 |
In the response data, the first byte 01 represents the real address of the current device, and 00 6B is the first state correction value register. If the device has multiple parameters, other parameters operate in the same way as this The same, generally, temperature and humidity have this parameter, and lighting generally does not have this parameter.
Change the correction value
For example, if the current state is too small, we want to add 1 to its real
value, and add 100 to the current value. The correction operation command is:
01 06 00 6B 00 64 F9 FD .
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 6B | 00 64 | F9 FD |
After the operation is successful, the device will return the information: 01 06 00 6B 00 64 F9 FD , after the successful change, the parameters will take effect immediately.
Disclaimer
This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.
Contact Us
- Company: Shanghai Sonbest Industrial Co., Ltd
- Address: Building 8,No.215 North east road, Baoshan District, Shanghai,China Web: http://www.sonbest.com
- Web: http://www.sonbus.com
- SKYPE: soobuu
- Email: sale@sonbest.com
- Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
References
- Home-上海æœåšå®žä¸šæœ‰é™å…¬å¸
- Home-SONBEST -SONBUS.COM| THE SENSOR COMPANY
- Home-SONBEST -SONBUS.COM| THE SENSOR COMPANY
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>