Price Industries Disio Display Thermostat User Guide
- June 5, 2024
- Price Industries
Table of Contents
**Price Industries Disio Display Thermostat User Guide
**
General Description
The 24 VAC Disio Display thermostat is a thermostat/controller designed to provide control for the following 3 main applications:
- Reheat (DX – 50)
- Pressure Dependent Damper Control (DX – 1XX)
- Fan Coil (2 pipe and 4 pipe) (DX – 3XX)
The Disio Display thermostat works as a standalone control thermostat. Disio Display thermostats ordered with optional BACnet can be connected to a BACnet network through its native BACnet MS/TP connection for remote control and monitoring. A USB-C jack on the bottom of the controller allows connection to a Windows based laptop for easy onsite configuration and monitoring using the free Disio Setup software. Download the Disio Setup software for Windows computers at disio.io/setup/.
Location
- Mount the thermostat in a place that is convenient for the end user, but please note the following:
- Do not mount the thermostat in direct sunlight (across from a window)
- Do not install on an outside wall
- Keep away from heat generating equipment (monitors, heaters, photocopiers, etc.)
- Be sure thermostat is mounted to allow vertical air circulation (i.e. Do not cove.
Connection Description
Connection Type
| Connection Label|
Description
---|---|---
Power| H| 24 VAC Hot (50/60 Hz, 6 VA plus external loads)| NOTE: Polarity
on power is important and must be observed on all devices.
C| 24 VAC Common| NOTE: Polarity on power is important and must be
observed on all devices.
Universal Outputs|
O1 – O4
| Configurable for:
- 24 VAC On/Off (0.50 Amps Max per O/P) Switched Hot (Default)
- 24 VAC Floating Point Modulation (Damper / Water Valve)
- 0-10 VDC Modulation, 10mA max per O/P (Damper / Water Valve / SCR Electric Heat)
Universal Inputs| ****
I1 – I4
| Configurable for:
- Binary Input – Contact Closure
- Thermistor Input (10k Type J), accuracy of +/- 1-2° F from 70° F to 82° F
- Voltage Input (0-10 VDC)
BAC net MS/TP| +| BAC net MS/TP Connection, Positive (+)
–| BAC net MS/TP Connection, Negative (-)
BC| BAC net MS/TP Connection, NETCOM, (BC)
Outputs Switched Jumper| BO Source| Outputs will either send 24 VAC hot or
common depending on jumper position Jumper ships in the switched hot position
by default
Disio Setup Jack| USB-C| Allows connection to a Windows laptop with the free
Disio Setup software to install new sequences, and monitor all inputs,
outputs, and control functions in real time
Typical Wiring Diagrams
7 Segment Key
Application
Reheat
LGB/Linear Gate Bypass
Fan Coil
Fan Coil 2-Pipe
Fan Coil 4-Pipe
Fan Status
Fan Off
Fan Low
Fan Medium
Fan High
Fan
Temperature Units
Celsius
Fahrenheit
Room Temperature
Cooling Load (1-99%)
Heating Load (1-99%)
Neutral (0)
Pipe Temperature
Water Temperature Cold
Water Temperature Hot
Water Temperature Neutral
No Probe
Discharge Air
No Probe
Outdoor Air
No Probe
Damper Position (0-99%)
Damper Target (0-99%)
Supply Air Temperature
No Probe
Note: Values of 99% are equal to 100%
Example: Damper Position 100% = Damper Fully Open
Can’t find the wiring for your specific application?
Contact US:
Visit us at disio.io/display for a complete list of sequences and wiring diagrams for the Disio Display Thermostat. Download the Disio Setup software for Windows computers at disio.io/setup/
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>