SEALEVEL PIO-24.PCI PCI Digital Input or Output Interface User Manual
- June 5, 2024
- SEALEVEL
Table of Contents
- SEALEVEL PIO-24.PCI PCI Digital Input or Output Interface
- Introduction
- Before You Get Started
- Software Installation
- Physical Installation
- Digital I/O Interface
- Programming the PIO-24.PCI
- Electrical Characteristics
- Specifications
- Example Circuits
- Appendix A – Troubleshooting
- Appendix B – How To Get Assistance
- Appendix C – Silk Screen – 8008 PCB
- Appendix D – Compliance Notices
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SEALEVEL PIO-24.PCI PCI Digital Input or Output Interface
Introduction
The PIO-24.PCI, part number 8008, digital I/O interface provides 24 channels
of buffered drive digital I/O 8255 mode zero. The PIO-24.PCI can be utilized
for a variety of control and automation applications including control and
monitoring of TTL devices (e.g., LEDs, small solenoids, small relays) and
interfacing to solid-state relay racks (SSRs) for high-power AC or DC loads.
The PIO-24.PCI’s 24 digital I/O channels are accessed via a 50-pin header
connector with an industry-standard pinout. The header provides 24 bits of
digital I/O divided into three eight-bit groups. Each eight-bit group may be
individually configured via software command as input or output to best match
your particular application requirements.
The PIO-24.PCI is designed to be used with a variety of Operating Systems
including Windows, Linux, and DOS. The SeaI/O API (Application Programmer
Interface) available on Sealevel’s website provides a variety of useful high-
level function calls implemented as a Windows dynamic link library (DLL) and
as a Linux kernel module and library. In addition to the API, SeaI/O includes
sample code and utilities to simplify software development.
Other Sealevel PCI Digital I/O Products
Model No. | Part No. | Description |
---|---|---|
PIO-32.PCI | (P/N 8010) | – 32 TTL Inputs/Outputs |
PIO-48.PCI | (P/N 8005) | – 48 TTL Inputs/Outputs |
PIO-96.PCI | (P/N 8009) | – 96 TTL Inputs/Outputs |
DIO-16.PCI | (P/N 8002) | – 8 Reed Relay Outputs/8 Opto-isolated Inputs |
REL-16.PCI | (P/N 8003) | – 16 Reed Relay Outputs |
DIO-32.PCI | (P/N 8004) | – 16 Reed Relay Outputs/16 Opto-isolated Inputs |
ISO-16.PCI | (P/N 8006) | – 16 Opto-isolated Inputs |
REL-32.PCI | (P/N 8007) | – 32 Reed Relay Outputs |
PLC-16.PCI | (P/N 8011) | – 8 Form C Relay Outputs/ 8 Opto-isolated Inputs |
Before You Get Started
What’s Included
The PIO-24.PCI is shipped with the following items. If any of these items are
missing or damaged, please
contact Sealevel for replacement.
• PIO-24.PCI Adapter
Advisory Conventions
- Warning: The highest level of importance used to stress a condition where damage could result to the product, or the user could suffer serious injury.
- Important: The middle level of importance used to highlight information that might not seem obvious or a situation that could cause the product to fail.
- Note: The lowest level of importance used to provide background information, additional tips, or other non-critical facts that will not affect the use of the product.
Optional Items
Depending upon your application, you are likely to find one or more of the
following items useful for interfacing the PIO-24.PCI to real-world signals.
All items can be purchased from our website (http://www.sealevel.com) or by
calling 864-843-4343.
For TTL Applications
- Terminal Block Kit – (Part Number KT107) Kit includes the TB07 screw terminal block and CA167 ribbon cable for connecting the PIO-24.PCI’s 50-pin header connector to your I/O. 6” Snap track and DIN rail clips are included for DIN rail mounting.
- IDC 50 to IDC 50 Pin 40″ Ribbon Cable (Part Number CA167) Interfaces the PIO-24.PCI’s 50-pin header connector to your I/O.
- Simulation/debug module (Part Number TA01) Module allows monitoring status of output pins and controlling state of input pins. An LED corresponding to each port bit illuminates to indicate state. Eight position DIP-switches are used to generate input status changes.
For High-Current, High-Voltage Applications
- IDC 50 to IDC 50 Pin Ribbon Cable (Part Number CA167) 40” cable connects the PIO-24.PCI to solid-state relay racks equipped with a 50-pin header interface.
- IDC 50 to IDC 50 Pin Ribbon Cable (Part Number CA135) 40” cable connects the PIO-24.PCI to solid-state relay racks equipped with 50-pin edge connector.
Solid State Relay Racks:
- Quad six position relay rack (Part Number PB24HQ) Relay rack can accept up to six QSSRs for a total of 24 channels. Features a 50-pin header connector for easy interface via 50-conductor ribbon cables.
- Quad four position relay rack (Part Number PB16HQ) Relay rack can accept up to four QSSRs for a total of 16 channels. Features a 50-pin header connector for easy interface via 50-conductor ribbon cables.
Quad Solid State Relay Modules:
- AC Input (Part Number IA5Q) Provides 4 channels of discrete I/O interface to monitor AC inputs up to 140V @ 10mA.
- DC Input (Part Number IB5Q) Provides 4 channels of discrete I/O interface to monitor DC inputs from 3.3V to 32V.
- AC Output (Part Number OA5Q) Provides 4 channels of discrete I/O interface to control AC outputs up to 140V @ 3A.
- DC Output (Part Number OB5Q) Provides 4 channels of discrete I/O interface to control DC outputs up to 60V @ 3A.
Simulation/debug module (Part Number TA01)
Module simulates the operation and load characteristics of a standard
24-channel relay rack. An LED corresponding to each port bit illuminates to
indicate state. Eight position DIP-switches are used to generate input status
changes.
Software Installation
Windows Installation
Do not install the Adapter in the machine until the software has been fully
installed.
Only users running Windows 7 or newer should utilize these instructions for
accessing and installing the appropriate driver via Sealevel’s website. If you
are utilizing an operating system prior to Windows 7, please contact Sealevel
by calling 864.843.4343 or emailing
support@sealevel.com to receive access to the legacy
driver download and installation instructions.
- Select the download for the SeaIO Classic for Windows (Software: SeaIO Classic V5 – Windows – Sealevel.) The setup file will automatically detect the operating environment and install the proper components. Next (depending on your browser) select the ‘Run this program from its current location’ or ‘Open’ option. Follow the information presented on the screens that follow. During setup, the user may specify installation directories and other preferred configurations. This program also adds entries to the system registry that are necessary for specifying the operating parameters for each driver. An uninstall option is also available to remove SeaIO files and registry/INI file entries from the system. If installing in NT, skip to step 11. ‘Windows NT Card Installation.’ Go to the “Add New Hardware Wizard” in the Control Panel. When the Wizard asks if you want Windows to search for the new hardware, choose “No, I want to select the hardware from a list.”
- Scroll through the list of categorized hardware and select ‘SeaIO Devices.’ If this is the first SeaIO device you may need to select ‘Other Devices’ and ‘Sealevel Systems, Inc.’ instead of ‘SeaIO Devices.’
- Click “Next.”
- Select the card model and press “Next.”
- The Wizard will guide you through a few more informational prompts; continue to click “Next” until it is completed.
- Your card’s resource assignments may be adjusted through the Device Manager (if, for instance, you need to change the I/O port address Windows assigned when you installed the card).
- Windows software installation is complete.
- Windows NT Card Installation: After accomplishing steps 1, bring up the Control Panel and doubleclick on the SeaIO Devices icon. To install a new card, click “Add Port.” Repeat this procedure for as many SeaIO cards as you wish to install.
Linux Installation
- You MUST have “root” privileges to install the software and drivers.
- The syntax is case sensitive.
- Users can obtain a README file included in the SeaIO Linux package which contains important installation and configuration instructions that makes the Linux installation more user friendly.
- Login as “root”
- Select download for the version of SeaIO Classic for Linux (Software: SeaIO Classic – Linux – Sealevel.)
- Copy seaio.tar.gz to your home directory by typing: cp seaio.tar.gz ~
- Change to your home directory by typing: cd
- Unzip and Untar the drivers and software by typing: tar -xvzf seaio.tar.gz
- Change to the SeaIO directory by typing: cd seaio
- User must download and compile a Linux kernel source.
- Now compile and prepare the drivers for use by typing: make install
- Using your favorite text editor, edit the /etc/seaio.conf
- Within the quote marks, insert cardtype=0xYourSeaIOcardType io=0xCardBaseAdress
- Save the file and exit your editor.
- With the system off and unplugged, install your SeaIO PCI card.
- Plug system back in and boot Linux. Login as “root”.
- Load the SeaIO driver by typing: seaioload
- The driver has enabled the card and is ready to use
To set up Linux to automatically load the driver; refer to a Linux manual
concerning your specific distribution for help.
For additional software support, please call Sealevel Systems’ Technical
Support, 864-843-4343. Our technical
support is free and available from 8:00 AM – 5:00 PM Eastern Time, Monday
through Friday. For email support contact:
support@sealevel.com
Physical Installation
The adapter can be installed in any 5V PCI expansion slot.
Do not install the Adapter in the machine until the software has been fully installed.
- Turn off PC power. Disconnect the power cord.
- Remove the PC case cover.
- Locate an available 5V PCI slot and remove the blank metal slot cover.
- Gently insert the PCI adapter into the slot. Make sure that the adapter is seated properly.
- After the adapter has been installed, the cables should be routed thru the opening in the bracket. This bracket also features a strain relief function that should be used to prevent un-expected cable removal.
- Replace the screw you removed for the blank and use it to secure the adapter into the slot. (This is required to ensure FCC Part 15 compliance.)
- Replace the cover.
- Connect the power cord
Digital I/O Interface
The PIO-24.PCI’s 24 digital I/O channels are accessed via an industry-standard 50-pin header connector. The header provides 24 bits of digital I/O divided into three eight-bit ports. Each port may be individually configured via software command as input or output.
50-pin Header Connector
You will need to install the bracket assembly and cable to the PIO-24.PCI
prior to installing it in the PC. The PIO-24.PCI’s bracket features a unique
cable clamp that provides a solid strain relief to prevent inadvertent cable
removal. The 50-pin connector has the following pin out which is compatible
with a wide variety of solid state relay racks:
Programming the PIO-24.PCI
Sealevel’s SeaI/O software is provided to assist in the development of reliable applications for the Sealevel Systems family of digital I/O adapters. Included on the SeaI/O CD are driver functions for use in accessing the I/O as well as helpful samples and utilities.
Programming for Windows
The SeaI/O API (Application Programmer Interface) provides a variety of useful
high-level function calls implemented in a Windows dynamic link library (DLL).
The API is defined in the help file (Start/Programs/SeaIO/SeaIO Help) under
“Application Programmers Interface.” This help file also includes detailed
information dealing with installation / removal of the software and
information about latency, logic states, and device configuration. For C
language programmers we recommend using the API to access the PIO-24.PCI. If
you are programming in Visual Basic, using the ActiveX control included with
SeaI/O is advised.
Samples and Utilities
A variety of sample programs and utilities (both executable and source code)
are included with SeaI/O. Further documentation on these samples can be found
by selecting “Start/Programs/SeaIO/Sample Application Description.”
Information about where the files are physically stored on your disk is also
included in this same file.
Programming for Linux
SeaI/O for Linux consists of two major parts: a kernel module and a library.
The kernel module is a simple IO pass-through device, allowing the library to
handle the more sophisticated functions provided to SeaI/O users. It is
provided in a ‘tarball’ format and can easily be compiled and included in the
kernel build.
Direct Hardware Control
In systems where the users program has direct access to the hardware (DOS) the
tables that follow give
the mapping and functions that the PIO-24.PCI provides.
Reading the Inputs
The inputs are active true. If an input is driven high (2V to 5.25 V) it will
read as a logical one, if driven lown (0V to 0.8V) it will read as a logical
zero. If an input is not driven it will read as a one due to the 10K ohm pull
up resistors on each port.
Reading the Outputs
The value that is currently being used to drive the outputs will be returned.
Presetting an Output Port
Each port has an output register associated with it. This register may be
written and retains its value whether the port is configured as an input or an
output. To preset the value of an output port the program should write to the
port when it is configured as an input then configure it as an output.
Writing the Outputs
The outputs are active true. Writing a one (1) corresponds to 5V while writing
a zero (0) corresponds to 0V, at the output.
Register Description
Address| | Mode| D7| D6| D5| D4| D3|
D2| D1| D0
---|---|---|---|---|---|---|---|---|---|---
Base+0| Port A1| RD/WR| PA1D7| PA1D6| PA1D5| PA1D4| PA1D3| PA1D2| PA1D1|
PA1D0
Base+1| Port B1| RD/WR| PB1D7| PB1D6| PB1D5| PB1D4| PB1D3| PB1D2| PB1D1|
PB1D0
Base+2| Port C1| RD/WR| PC1D7| PC1D6| PC1D5| PC1D4| PC1D3| PC1D2| PC1D1|
PC1D0
Base+3| CW Port 1| WR| CW1D7| 0| 0| CW1D4| CW1D3| CW1D2| CW1D1| CW1D0
Base+4| Interrupt Port 1| RD/WR| 0| 0| 0| 0| 0| IRQEN1| IRQC11| IRQC10
Base+5| IntStat Port 1| RD| 0| 0| 0| 0| 0| 0| 0| IRQST1
I/O Control Word
Each port may be configured as either Input or Output. This is accomplished by
writing the correct Control Word (CW) to the proper register.
Control Word (X = 0) | Hex Value | Port Setup |
---|---|---|
7 | 6 | 5 |
Upper | C Lower | |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
1 | X | X |
Interrupt Control
When enabled interrupts are generated on port bit D0 of each A port. n = port
number
IRQENn | interrupt enable | 1 = enabled | 0 = disabled ( 0 on power up ) |
---|
IRQCn0
IRQCn1
| Interrupt mode select, see table below
Interrupt mode select, see table below
Interrupt Mode Select Table
IRQCn1 | IRQCn0 | INT Type |
---|---|---|
0 | 0 | Low level |
0 | 1 | High level |
1 | 0 | Falling edge |
1 | 1 | Rising edge |
Interrupt Read
Reading the INTSTAT port (Base+5) clears any interrupt pending.
IRQST1 | (D0) Interrupt status | 1 = interrupt pending, 0 = none |
---|
Electrical Characteristics
The PIO-24.PCI uses 74LS245 octal bi-directional transceivers to provide TTL input/output capabilities. Each bit is pulled to +5V through a 10K ohm pull-up resistor to insure each bit is at a known state when not driven.
Specifications
Inputs
Logic High | Min 2VDC |
---|---|
Logic Low | Max 0.8VDC |
Outputs
Logic High | Min 2VDC @ 15 mA |
---|---|
Logic Low | Max 0.5VDC @ 24 mA |
Temperature Range
Operating | 0°C – 70°C |
---|---|
Storage | -50°C – 105°C |
Power Requirements
Supply line | +5 VDC |
---|---|
Rating | 1A |
Example Circuits
Appendix A – Troubleshooting
The adapter should provide years of trouble-free service. However, in the event that device appears to not be functioning incorrectly, the following tips can eliminate most common problems without the need to call Technical Support.
- Read this manual thoroughly before attempting to install the adapter in your system.
- Use Device Manager under Windows to verify proper installation.
- Use the SeaI/O control panel applet for card identification and configuration.
- Identify all I/O adapters currently installed in your system. This includes your on-board serial ports, controller cards, sound cards etc. The I/O addresses used by these adapters, as well as the IRQ (if any) should be identified.
- Configure your Sealevel Systems adapter so that there is no conflict with currently installed adapters. No two adapters can occupy the same I/O address.
- Make sure the Sealevel Systems adapter is using a unique IRQ The IRQ is typically selected via an on-board header block. Refer to the section on Card Setup for help in choosing an I/O address and IRQ.
- Make sure the Sealevel Systems adapter is securely installed in a motherboard slot.
- If you are utilizing an operating system prior to Windows 7, please contact Sealevel‘s Technical support as directed below to receive more information regarding the utility software which will determine if your product is functioning properly.
- Only users running Windows 7 or newer should utilize the diagnostic tool ‘WinSSD’ installed in the SeaCOM folder on the Start Menu during the setup process. First find the ports using the Device Manager, then use ‘WinSSD’ to verify that the ports are functional.
- Always use the Sealevel Systems diagnostic software when troubleshooting a problem. This will help eliminate any software issues and identify any hardware conflicts.
If these steps do not solve your problem, please call Sealevel Systems’ Technical Support, 864-843-4343. Our technical support is free and available from 8:00 A.M.- 5:00 P.M. Eastern Time Monday through Friday. For email support contact support@sealevel.com.
Appendix B – How To Get Assistance
Please refer to Troubleshooting Guide prior to calling Technical Support.
- Begin by reading through the Trouble Shooting Guide in Appendix A. If assistance is still needed please see below.
- When calling for technical assistance, please have your user manual and current adapter settings. If possible, please have the adapter installed in a computer ready to run diagnostics.
- Sealevel Systems provides an FAQ section on its web site. Please refer to this to answer many common questions. This section can be found at http://www.sealevel.com/faq.asp.
- Sealevel Systems maintains a web page on the Internet. Our home page address is https://www.sealevel.com/. The latest software updates, and newest manuals are available via our web site.
- Technical support is available Monday to Friday from 8:00 A.M. to 5:00 P.M. Eastern Time. Technical support can be reached at 864-843-4343.
RETURN AUTHORIZATION MUST BE OBTAINED FROM SEALEVEL SYSTEMS BEFORE RETURNED MERCHANDISE WILL BE ACCEPTED. AUTHORIZATION CAN BE OBTAINED BY CALLING SEALEVEL SYSTEMS AND REQUESTING A RETURN MERCHANDISE AUTHORIZATION (RMA) NUMBER.
Appendix C – Silk Screen – 8008 PCB
Appendix D – Compliance Notices
Federal Communications Commission (FCC) Statement
This equipment has been tested and found to comply with the limits for Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in such case the user
will be required to correct the interference at the users expense.
EMC Directive Statement
Products bearing the CE Label fulfill the requirements of the EMC directive
(89/336/EEC) and of the low-voltage directive (73/23/EEC) issued by the
European Commission. To obey these directives, the following European
standards must be met:
- EN55022 Class A – “Limits and methods of measurement of radio interference characteristics of information technology equipment”
- EN55024 – “Information technology equipment Immunity characteristics Limits and methods of measurement”.
This is a Class A Product. In a domestic environment, this product may cause
radio interference in which case the user may be required to take adequate
measures to prevent or correct the interference.
Always use cabling provided with this product if possible. If no cable is
provided or if an alternate cable is required, use high quality shielded
cabling to maintain compliance with FCC/EMC directives.
Warranty
Sealevel’s commitment to providing the best I/O solutions is reflected in the Lifetime Warranty that is standard on all Sealevel-manufactured I/O products. We are able to offer this warranty due to our control of manufacturing quality and the historically high reliability of our products in the field. Sealevel products are designed and manufactured at its Liberty, South Carolina facility, allowing direct control over product development, production, burn- in and testing. Sealevel achieved ISO-9001:2015 certification in 2018.
Warranty Policy
Sealevel Systems, Inc. (hereafter “Sealevel”) warrants that the Product shall
conform to and perform in accordance with published technical specifications
and shall be free of defects in materials and workmanship for the warranty
period. In the event of failure, Sealevel will repair or replace the product
at Sealevel’s sole discretion. Failures resulting from misapplication or
misuse of the Product, failure to adhere to any specifications or
instructions, or failure resulting from neglect, abuse, accidents, or acts of
nature are not covered under this warranty. Warranty service may be obtained
by delivering the Product to Sealevel and providing proof of purchase.
Customer agrees to ensure the Product or assume the risk of loss or damage in
transit, to prepay shipping charges to Sealevel, and to use the original
shipping container or equivalent. Warranty is valid only for original
purchaser and is not transferable. This warranty applies to Sealevel
manufactured Product. Product purchased through Sealevel but manufactured by a
third party will retain the original manufacturer’s warranty.
Non-Warranty Repair/Retest
Products returned due to damage or misuse and Products retested with no
problem found are subject to repair/retest charges. A purchase order or credit
card number and authorization must be provided in order to obtain an RMA
(Return Merchandise Authorization) number prior to returning Product.
How to obtain an RMA (Return Merchandise Authorization)
If you need to return a product for warranty or non-warranty repair, you must
first obtain an RMA number. Please contact Sealevel Systems, Inc. Technical
Support for assistance:
Available Monday – Friday, 8:00AM to 5:00PM EST
Phone 864-843-4343
Email support@sealevel.com
Trademarks
Sealevel Systems, Incorporated acknowledges that all trademarks referenced in
this manual are the service mark, trademark, or registered trademark of the
respective company.
References
- Sealevel - I/O & Computing Products, Engineering and Manufacturing
- FAQs - Sealevel
- Sealevel - I/O & Computing Products, Engineering and Manufacturing
- Software: SeaIO Classic - Linux - Sealevel
- Software: SeaIO Classic V5 - Windows - Sealevel
- WinSSD Software Utility Overview - Sealevel
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>