PLEASE READ THE INSTRUCTIONS CAREFULLY BEFORE COMMENCING ASSEMBLY
Live: Normally Brown / Red Neutral: Normally Blue / Black
If the external cord of this luminaire is damaged, it must be replaced by the manufacturer or a qualified person.

NOT SUITABLE FOR COVERING WITH THERMAL INSULATION.

FOR CEILING USE ONLY

Glare guard

astro Pinhole Slimline Flush Fire-Rated - fig 3

astro Pinhole Slimline Flush Fire-Rated - fig 4

CEILING TYPES

Ceiling lining secured directly to timber joists Fire resistance periods to
Minimum 1 x 15 mm thick Type A or Type F gypsum wallboard to EN 520 30

minutes
Minimum 2 x 12.5 mm thick Type F gypsum FireLine to EN 520| 60 minutes
Minimum 3 x 12.5 mm thick Type F gypsum FireLine to EN 520| 90 minutes

These products are suitable to install in fire-protected timber floor and ceiling systems that have previously been successfully tested for at least 30 minutes, 60 minutes or 90 minutes to EN 1365-2 : 2014

JOIST TYPES

Solid softwood or hardwood timber joists manufactured from strength grade C16 or greater, installed at centers not exceeding 600 mm

astro Pinhole Slimline Flush Fire-Rated - fig 5

astro Pinhole Slimline Flush Fire-Rated - fig 6

astro Pinhole Slimline Flush Fire-Rated - fig 7

astro Pinhole Slimline Flush Fire-Rated - fig 8

astro Pinhole Slimline Flush Fire-Rated - fig 9