Honeywell OSD-3230 Conventional Optical Smoke Detector User Guide

June 3, 2024
Honeywell

Honeywell OSD-3230 Conventional Optical Smoke Detector

Important Warnings

General
  • Before using the device read this manual carefully. Keep it just In case of necessity.
  • Abide all the rules and precautions stated in the manual. Follow all the Instuctions one by one.
  • Keep the devices away from water and moisture
Conditions

Do not energize the device above or below the given limits of extreme hot or cold conditions,
Temperature: Between -10°C and +SS°C
Relative Humidity: %95 RH max

Service

Do not try to fix the device on your own. Removal of rover may end up with electricity shock.

In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical

Warning: Do not attempt to remove the electronic board from its plastic case. The electronic board is closed for your safety. User should avioid from interference.

Malfunctions that require technical Service

In case of any malfunction or below conditions contact with your authorized service.

  • When Mains cab!e or the plug is harmed.
  • Contact of device with a fluid.
  • Exposure of rain and water,
  • Fell down of device or harmed outer cover,
  • Depending on the instructions  In manual if your device not working properly contact with your authorized service in such terms.
Maintenance on your own

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case any defect or malfuction, contact with your dealer or with your dealer or with authorized service. All the technical interventions have allowed for cleaning

Transportation

Device must be carefully transported avoiding all physical bump. stroke and possible fluid entry. Malfuctions that casued by improper transportation is not under warranty.

Human and Enviroment Health

This device contains no chemical or biological elements that could  harm human condition.

General Features
  • Advance smoke detection algorithm that minimizes false alarms
  • Rejection of transient signals that can to detected as alarms
  • Adaptive intelligent protection by constactly sampling the enviroment
  • Dust algorithm and warning to understand that it is getting polluted and
  • unable to detect
  • Easy to clean smoker chamber
  • Ability to connect an remote indicator
  • Two leds used for statu indicators
  • 15s start time
  • Compatible with DB-0210 Universal Detector Base

Technical Features

Power Input 18V(min) – 30V(max)
Average Current Consumption 30uA (@24V)
Maximum Alarm Current 50mA (@24V) – ( 470ohm resistace limited)
Maximum External Device Current 10mA (@24V)- (2K2 resistance limited)
Operating Temperature Range -10°C ~ +70°C (14°F N 158°F)
Humidity 95°/o RH (max)
Dimensions (mm) Ø110, h42
Housing Material White Color, ABS Plastic
Used Cable Cut 0.4mm 2 rv 1.5mm 2
Weight (incl. Base/ excluding base) 183 gr / 125 gr
Startup Time 15 sec
Indicator leds

| Blue Led| Red Led
---|---|---
When the unit is first energized for 15s, while sampling the environment| Blinks for 5s period| X
Any error condition ( dust or eower failure)| Blinks for ls period| X
In normal Operating condition| Blinks for 20s period| X
In alarm condition| X| It is constantly lit

Terminals
Number 1 Negative (-) power input
Number 2 Negative (-) input of the remote Indicator
Number 3 .Positive supply out and Positive ( +) input of remote indicator
Number 4 Positive ( +) pow input
Number 5 Earth connection

Mounting and Connection

  1. Remove the head of the detector by pulling it upwords (2) by turning it (1) up to the short line in the direction of the counterclockwise direction as seen frim the base.

  2. Mount the base using the 2 mounting location shown.

  3. Make the cable connection according to the following diagram. Make a connection with pole 4 + pole and pole 1 – by taking pole + number 3 from pole 3 of the next detector.

  4. Use the 3 (+)and 2 (-) connections for the remote indicator.

  5. Replace the detector head. Make sure the line on the head matches the long line on the long line on the base

  6. Give the detector power from alarm panel. In the absence of an alarm, the LED on the detector indicates that it is operating with a blue color for 4
    approximately 20 seconds. (the first 15 seconds a blue LED lights up in the detector for 5 seconds).

Test

Smoke Test

For the smoke test, allow the smoke to enter the smoke detection chamber for at least 1 minute with a flammable material or a test aerosol. When enough amount of smoke enters the chamber, the LED illuminates and reports the alarm illuminates and reports the alarm.

  1. Remove the smoke source when the alarm condition is reached.
  2. Check that the red LEDs are lit continuously. Reset the detector on the panel.
  3. If the detector does not give an alarm within 1minute, thr detector should go to service,
  4. The system can be activated after the test has been performed.

EN 54-7:2000; EN 54-7:2000/A 1 :2002; EN 54-7:2000/A2:2006
Point type smoke detector (Ionization) OSD-3230

Honeywell Fire
Emaar Business Park, Sheikh
Zayed Road Building No. 2, 2nd
Floor, 201. PO. Box 232362
Dubai, United Arab Emirates
Tel: +97144541704

**For more information**

www.honeywell.com
© 2020 Honeywell International Inc.

* 2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted  municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see:www.recyclethis.info.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals