EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar User Guide

June 3, 2024
Emerson

EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar

EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG
\(1\)

About this guide

This Quick Start Guide provides basic guidelines for the Rosemount 3408 Level Transmitter. Refer to the 3408 Reference Manual for more instructions.

Safety messages

  • Failure to follow safe installation and servicing guidelines could result in death or serious injury.
  • Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
  • Use the equipment only as specified in this Quick Start Guide and the Reference Manual. Failure to do so may impair the protection provided by the equipment.
  • For installations in hazardous locations, the transmitter must be installed according to the Rosemount 3408 Product Certifications document and System Control Drawing.
  • Repair, e.g. substitution of components, etc. may jeopardize safety and is under no circumstances allowed.

WARNING

  • Explosions could result in death or serious injury.
  • Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
  • Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.
  • In Explosion-proof/Flameproof and Non-Incendive/Type Ex ec installations, do not remove the transmitter cover when power is applied to the unit.
  • The transmitter cover must be fully engaged to meet Explosion-proof/Flameproof requirements.

WARNING

Electrical shock could cause death or serious injury. Ensure the mains power to the transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the transmitter.

WARNING

Process leaks could result in death or serious injury. Ensure that the transmitter is handled carefully. If the process seal is damaged, gas might escape from the tank.

WARNING

Physical access Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.

CAUTION

Hot surfaces The flange and process seal may be hot at high process temperatures. Allow to cool before servicing.

Confirm approval type

For hazardous locations transmitters labeled with multiple approval types:

Procedure

Permanently mark the checkbox of the selected approval type.EMERSON
Rosemount 3408 Level Transmitter Non-Contacting Radar FIG
\(3\)

Mount the process seal antenna

Mount the flanged version

Procedure

  1. Lower the transmitter into the nozzle.
    Note Be careful not to scratch or otherwise damage the PTFE sealing.EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG
\(5\)

  2. Tighten the bolts and nuts (see Table 3-1).
    Note

  3. Re-tighten after 24 hours and again after the first temperature cycle.

  4. Check at regular intervals and re-tighten if necessary.

  5. Torque specifications
    The conditions used for the calculation are:

  6. Standard mating metal flange

  7. A193 B8M Cl.2 / A4-70 bolt material

  8. Friction coefficient of μ=0.16
    Low strength bolt and non-metallic mating flange may require lower tightening torque.
    Table 3-1: Torque Values for Process Seal Antenna, lb-ft (N-m)Process connection size| Process connection rating
    ---|---
    ASME B16.5| EN1092-1| JIS B2220
    Class 150| Class 300| PN16| PN40| 10K| 20K
    2-in./DN50/50A| 29 (40)| 52 (70)| 26 (35)| 29 (40)| 18 (25)| 37 (50)
    3-in./DN80/80A| 33 (45)| 48 (65)| 37 (50)| 41 (55)| 22 (30)| 70 (95)
    4-in./DN100/100A| 59 (80)| 52 (70)| 37 (50)| 74 (100)| 26 (35)| 74 (100)
    6-in./DN150/150A| 66 (90)| 66 (90)| 74 (100)| 136 (185)| 74 (100)| N/A

Mount the lens antenna

Mount on NPT threaded connections

Procedure

  1. Apply anti-seize paste or PTFE tape on threads according to your site procedures.

  2. Mount the transmitter on the tank.
    Example

  3. (A) Threaded fitting

  4. (B) Threaded flange
    Note Be careful not to scratch or otherwise damage the PTFE sealing.

Mount on BSPP (G) threaded connections

Procedure

  1. Place a suitable gasket on the tank nozzle
    Example

  2. (A) Threaded fitting

  3. (B) Threaded flange

  4. Mount the transmitter on the tankEMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG \(11\)
    Note Be careful not to scratch or otherwise damage the PTFE sealing

Mount the ATAP lens antenna

Open air installations

The antenna extension must be fitted to the transmitter to comply with open air requirements.

Figure 5-1: Antenna Extension

Mount the bracket

Prerequisites Mount the bracket so that it is not susceptible to vibration.

Procedure

  1. Mount the bracket to the pipe/wall.
    ExampleEMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG
\(14\)

  2. Mount the adapter.EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG \(15\)

  3. Secure the transmitter to the adapter.

Mount on 1½-in. BSPP (G) threaded connections

Procedure

  1. Place a suitable gasket on the tank nozzle.
    Example

  2. (A) Threaded fitting

  3. (B) Threaded flange

  4. Mount the transmitter on the tank.EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG \(17\)

Rotate the transmitter housing

To improve field access to wiring or to better view the optional LCD display:

Procedure

  1. Loosen the set screw.
  2. Rotate the transmitter housing to the desired location, and then retighten the set screw.

Prepare the electrical connections

Cable selection

Use 24-16 AWG wire (0.20-1.5 mm2). Twisted pairs and shielded wiring are recommended for environments with high EMI (electromagnetic interference).
Fine stranded conductors shall be equipped with a ferrule.

Cable gland/conduit

For explosion-proof/flameproof installations, only use cable glands or conduit entry devices certified explosion-proof or flameproof.

Internal power consumption

< 0.8 W in normal operation

Grounding

Make sure grounding is done according to national and local electrical codes. Failure to do so may impair the protection provided by the equipment.

Transmitter housing

The most effective grounding method is direct connection to earth ground with minimal impedance. There are two grounding screw connections provided (see Figure 7-1).EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar
FIG \(21\)

Cable shield grounding

Make sure the instrument cable shield is:

  • Trimmed close and insulated from touching the transmitter housing.
  • Continuously connected throughout the segment.
  • Connected to a good earth ground at the power supply end

Figure 7-2: Cable ShieldEMERSON Rosemount 3408 Level Transmitter Non-
Contacting Radar FIG \(22\)

  • A. Insulate shield and drain wire
  • B. Minimize distance
  • C. Trim shield and insulate exposed drain wire
  • D. Connect drain wire to the power supply ground

Note
Do not ground the shield and its drain wire at the transmitter. If the cable shield touches the transmitter housing, it can create ground loops and interfere with communications.

Power supply

The transmitter operates on max. 35 Vdc transmitter terminal voltage and max. 22.5 mA (max. 30 Vdc in Intrinsically Safe installations).

Load limitations

For HART® communication, a minimum loop resistance of 250 Ω is required. Maximum loop resistance (R) is determined by the voltage level of the external power supply (UE):

UE (Vdc) R (Ω)
≥ 15.6 R = 44.4 × (UE − 12)
< 15.6 R = 250 × (UE − 15)

EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG
\(23\)

Wiring diagram

Figure 7-4: 4-20 mA/HART® CommunicationEMERSON Rosemount 3408 Level
Transmitter Non-Contacting Radar FIG \(24\)

  • A. Handheld communicator
  • B. Approved IS barrier (for Intrinsically Safe installations only)
  • C. HART modem
  • D. Load resistance (≥250 Ω)
  • E. Current meter
  • F. Power supply

Connect wiring and power up

Procedure

  1. Verify the power supply is disconnected.

  2. Remove the cover.

  3. Remove the LCD display (if fitted).

  4. Remove the plastic plugs

  5. Pull the cable through the cable gland/conduit. Identification of thread size and type

  6. Connect the cable wires.
    Note When connecting a flexible (stranded) conductor, use a small screwdriver to press down and hold the terminal connection open

  7. Ensure proper grounding

  8. Tighten the cable gland. Apply PTFE tape or other sealant to the threads.EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG \(31\)
    Note Make sure to arrange the wiring with a drip loop.

  9. Seal any unused port with the enclosed metal plug. Apply PTFE tape or other sealant to the threadsEMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG \(33\)

  10. Snap the LCD display into place.

  11. Attach and tighten the cover.

  12. Verify the cover jam screw is completely threaded into the housing.EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG \(35\)

  13. Attach and tighten the cover
    Note Make sure the cover is fully engaged. There should be no gap between the cover and the housing.EMERSON Rosemount 3408 Level Transmitter Non-
Contacting Radar FIG \(37\)

  14. Turn the jam screw counterclockwise until it contacts the cover.
    Note Required for explosion-proof/flameproof installations onlyEMERSON
Rosemount 3408 Level Transmitter Non-Contacting Radar FIG
\(38\)

  15. Turn the jam screw an additional ½ turn counterclockwise to secure the cover.

  16. Connect the power supply.

Configuration

Configuration tools

  • Field Device Integration (FDI) compliant systems
  • Device Descriptor (DD) compliant systems
  • Device Type Manager (DTM™) compliant systems
  • Emerson’s configuration tools with Bluetooth® wireless technology capabilities

Rosemount Radar Master Plus

Rosemount Radar Master Plus is the recommended tool for configuration. It is a User Interface Plug-in (UIP) that includes basic configuration options, as well as advanced configuration and service functions. An FDI or DTM compliant host is needed to run Rosemount Radar Master Plus.

Related information

Emerson.com/RosemountRadarMasterPlus

Download AMS Device Configurator

AMS Device Configurator is a software for configuration of Emerson field devices using FDI technology.

Procedure

Download the software at Emerson.com/AMSDeviceConfigurator.

Confirm correct device driver

Procedure

  1. Verify that the correct FDI/DD/DTM Package is loaded on your systems to ensure proper communication.
  2. Download the latest FDI/DD/DTM Package at Emerson.com/DeviceInstallKits or FieldCommGroup.org.

Configure transmitter using guided setup

The options available in the Guided Setup wizard include all items required for basic operation.

Procedure

  1. If using an FDI compliant software, then select Overview →Rosemount Radar Master Plus.EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar FIG \(39\)
  2. Select Configure → Guided Setup and follow the on-screen instructions

Wireless configuration via Bluetooth® technology

Download the AMS Device Configurator Procedure

Download and install the app from your app store.

Related information Emerson.com/AMSDeviceConfigurator

Configure via Bluetooth® wireless technology

Procedure

  1. Launch AMS Device Configurator.
  2. Click on the device you want to connect to.
  3. On first connection, enter the key for this device.
  4. At the top left, click the menu icon.
  5. Select Configure → Guided Setup → Basic Setup and follow the onscreen instructions.

Bluetooth® UID and key

You can find the UID and key on the paper tag attached to the device, and on the display unit.
Figure 9-1: Bluetooth Security InformationEMERSON Rosemount 3408 Level
Transmitter Non-Contacting Radar FIG \(40\)

For more information: Emerson.com
©2022 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners