EMERSON Rosemount 3408 Level Transmitter Non-Contacting Radar
About this guide
This Quick Start Guide provides basic guidelines for the Rosemount 3408 Level Transmitter. Refer to the 3408 Reference Manual for more instructions.
Safety messages
- Failure to follow safe installation and servicing guidelines could result in death or serious injury.
- Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
- Use the equipment only as specified in this Quick Start Guide and the Reference Manual. Failure to do so may impair the protection provided by the equipment.
- For installations in hazardous locations, the transmitter must be installed according to the Rosemount 3408 Product Certifications document and System Control Drawing.
- Repair, e.g. substitution of components, etc. may jeopardize safety and is under no circumstances allowed.
WARNING
- Explosions could result in death or serious injury.
- Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
- Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.
- In Explosion-proof/Flameproof and Non-Incendive/Type Ex ec installations, do not remove the transmitter cover when power is applied to the unit.
- The transmitter cover must be fully engaged to meet Explosion-proof/Flameproof requirements.
WARNING
Electrical shock could cause death or serious injury. Ensure the mains power to the transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the transmitter.
WARNING
Process leaks could result in death or serious injury. Ensure that the transmitter is handled carefully. If the process seal is damaged, gas might escape from the tank.
WARNING
Physical access Unauthorized personnel may potentially cause significant
damage to and/or misconfiguration of end users’ equipment. This could be
intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental
to protecting your system. Restrict physical access by unauthorized personnel
to protect end users’ assets. This is true for all systems used within the
facility.
CAUTION
Hot surfaces The flange and process seal may be hot at high process temperatures. Allow to cool before servicing.
Confirm approval type
For hazardous locations transmitters labeled with multiple approval types:
Procedure
Permanently mark the checkbox of the selected approval type.
Mount the process seal antenna
Mount the flanged version
Procedure
-
Lower the transmitter into the nozzle.
Note Be careful not to scratch or otherwise damage the PTFE sealing. -
Tighten the bolts and nuts (see Table 3-1).
Note -
Re-tighten after 24 hours and again after the first temperature cycle.
-
Check at regular intervals and re-tighten if necessary.
-
Torque specifications
The conditions used for the calculation are: -
Standard mating metal flange
-
A193 B8M Cl.2 / A4-70 bolt material
-
Friction coefficient of μ=0.16
Low strength bolt and non-metallic mating flange may require lower tightening torque.
Table 3-1: Torque Values for Process Seal Antenna, lb-ft (N-m)Process connection size| Process connection rating
---|---
ASME B16.5| EN1092-1| JIS B2220
Class 150| Class 300| PN16| PN40| 10K| 20K
2-in./DN50/50A| 29 (40)| 52 (70)| 26 (35)| 29 (40)| 18 (25)| 37 (50)
3-in./DN80/80A| 33 (45)| 48 (65)| 37 (50)| 41 (55)| 22 (30)| 70 (95)
4-in./DN100/100A| 59 (80)| 52 (70)| 37 (50)| 74 (100)| 26 (35)| 74 (100)
6-in./DN150/150A| 66 (90)| 66 (90)| 74 (100)| 136 (185)| 74 (100)| N/A
Mount the lens antenna
Mount on NPT threaded connections
Procedure
-
Apply anti-seize paste or PTFE tape on threads according to your site procedures.
-
Mount the transmitter on the tank.
Example -
(A) Threaded fitting
-
(B) Threaded flange
Note Be careful not to scratch or otherwise damage the PTFE sealing.
Mount on BSPP (G) threaded connections
Procedure
-
Place a suitable gasket on the tank nozzle
Example -
(A) Threaded fitting
-
(B) Threaded flange
-
Mount the transmitter on the tank
Note Be careful not to scratch or otherwise damage the PTFE sealing
Mount the ATAP lens antenna
Open air installations
The antenna extension must be fitted to the transmitter to comply with open air requirements.
Figure 5-1: Antenna Extension
Mount the bracket
Prerequisites Mount the bracket so that it is not susceptible to vibration.
Procedure
-
Mount the bracket to the pipe/wall.
Example -
Mount the adapter.
-
Secure the transmitter to the adapter.
Mount on 1½-in. BSPP (G) threaded connections
Procedure
-
Place a suitable gasket on the tank nozzle.
Example -
(A) Threaded fitting
-
(B) Threaded flange
-
Mount the transmitter on the tank.
Rotate the transmitter housing
To improve field access to wiring or to better view the optional LCD display:
Procedure
- Loosen the set screw.
- Rotate the transmitter housing to the desired location, and then retighten the set screw.
Prepare the electrical connections
Cable selection
Use 24-16 AWG wire (0.20-1.5 mm2). Twisted pairs and shielded wiring are
recommended for environments with high EMI (electromagnetic interference).
Fine stranded conductors shall be equipped with a ferrule.
Cable gland/conduit
For explosion-proof/flameproof installations, only use cable glands or conduit entry devices certified explosion-proof or flameproof.
Internal power consumption
< 0.8 W in normal operation
Grounding
Make sure grounding is done according to national and local electrical codes. Failure to do so may impair the protection provided by the equipment.
Transmitter housing
The most effective grounding method is direct connection to earth ground with minimal impedance. There are two grounding screw connections provided (see Figure 7-1).
Cable shield grounding
Make sure the instrument cable shield is:
- Trimmed close and insulated from touching the transmitter housing.
- Continuously connected throughout the segment.
- Connected to a good earth ground at the power supply end
Figure 7-2: Cable Shield
- A. Insulate shield and drain wire
- B. Minimize distance
- C. Trim shield and insulate exposed drain wire
- D. Connect drain wire to the power supply ground
Note
Do not ground the shield and its drain wire at the transmitter. If the cable
shield touches the transmitter housing, it can create ground loops and
interfere with communications.
Power supply
The transmitter operates on max. 35 Vdc transmitter terminal voltage and max. 22.5 mA (max. 30 Vdc in Intrinsically Safe installations).
Load limitations
For HART® communication, a minimum loop resistance of 250 Ω is required. Maximum loop resistance (R) is determined by the voltage level of the external power supply (UE):
UE (Vdc) | R (Ω) |
---|---|
≥ 15.6 | R = 44.4 × (UE − 12) |
< 15.6 | R = 250 × (UE − 15) |
Wiring diagram
Figure 7-4: 4-20 mA/HART® Communication
- A. Handheld communicator
- B. Approved IS barrier (for Intrinsically Safe installations only)
- C. HART modem
- D. Load resistance (≥250 Ω)
- E. Current meter
- F. Power supply
Connect wiring and power up
Procedure
-
Verify the power supply is disconnected.
-
Remove the cover.
-
Remove the LCD display (if fitted).
-
Remove the plastic plugs
-
Pull the cable through the cable gland/conduit. Identification of thread size and type
-
Connect the cable wires.
Note When connecting a flexible (stranded) conductor, use a small screwdriver to press down and hold the terminal connection open -
Ensure proper grounding
-
Tighten the cable gland. Apply PTFE tape or other sealant to the threads.
Note Make sure to arrange the wiring with a drip loop. -
Seal any unused port with the enclosed metal plug. Apply PTFE tape or other sealant to the threads
-
Snap the LCD display into place.
-
Attach and tighten the cover.
-
Verify the cover jam screw is completely threaded into the housing.
-
Attach and tighten the cover
Note Make sure the cover is fully engaged. There should be no gap between the cover and the housing. -
Turn the jam screw counterclockwise until it contacts the cover.
Note Required for explosion-proof/flameproof installations only -
Turn the jam screw an additional ½ turn counterclockwise to secure the cover.
-
Connect the power supply.
Configuration
Configuration tools
- Field Device Integration (FDI) compliant systems
- Device Descriptor (DD) compliant systems
- Device Type Manager (DTM™) compliant systems
- Emerson’s configuration tools with Bluetooth® wireless technology capabilities
Rosemount Radar Master Plus
Rosemount Radar Master Plus is the recommended tool for configuration. It is a User Interface Plug-in (UIP) that includes basic configuration options, as well as advanced configuration and service functions. An FDI or DTM compliant host is needed to run Rosemount Radar Master Plus.
Related information
Emerson.com/RosemountRadarMasterPlus
Download AMS Device Configurator
AMS Device Configurator is a software for configuration of Emerson field devices using FDI technology.
Procedure
Download the software at Emerson.com/AMSDeviceConfigurator.
Confirm correct device driver
Procedure
- Verify that the correct FDI/DD/DTM Package is loaded on your systems to ensure proper communication.
- Download the latest FDI/DD/DTM Package at Emerson.com/DeviceInstallKits or FieldCommGroup.org.
Configure transmitter using guided setup
The options available in the Guided Setup wizard include all items required for basic operation.
Procedure
- If using an FDI compliant software, then select Overview →Rosemount Radar Master Plus.
- Select Configure → Guided Setup and follow the on-screen instructions
Wireless configuration via Bluetooth® technology
Download the AMS Device Configurator Procedure
Download and install the app from your app store.
Related information Emerson.com/AMSDeviceConfigurator
Configure via Bluetooth® wireless technology
Procedure
- Launch AMS Device Configurator.
- Click on the device you want to connect to.
- On first connection, enter the key for this device.
- At the top left, click the menu icon.
- Select Configure → Guided Setup → Basic Setup and follow the onscreen instructions.
Bluetooth® UID and key
You can find the UID and key on the paper tag attached to the device, and on
the display unit.
Figure 9-1: Bluetooth Security Information
For more information: Emerson.com
©2022 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark of one of the Emerson family of
companies. All other marks are the property of their respective owners
Quick Start Guide 00825-0100-4418, Rev. AA September 2022
References
- Emerson Global | Emerson
- Software & Drivers Page | Emerson US
- Rosemount | Emerson US
- Rosemount Radar Master Plus - FDI Package | Emerson US
- Homepage | FieldComm Group
- Rosemount 3408 Level Transmitter Non-Contacting Radar | Emerson US
- Rosemount Radar Master Plus - FDI Package | Emerson US
- AMS Device Configurator for Emerson Field Devices | Emerson
- Software & Drivers Page | Emerson US
- Homepage | FieldComm Group
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>