Emerson 4600 Oil & Gas Panel Pressure Transmitter User Manual
- June 4, 2024
- Emerson
Table of Contents
Quick Start Guide
00825-0200-4022, Rev HB
January 2022
Rosemount™ 4600 Oil & Gas Panel Pressure Transmitter
NOTICE
This guide provides basic guidelines for the Rosemount 4600 Oil & Gas Panel
Pressure Transmitter. It does not provide instructions for diagnostics,
maintenance, service, troubleshooting, explosion-proof, flameproof, or
intrinsically safe (I.S.) installations. Refer to the Rosemount 4600 Reference
Manual for more instruction. This manual is also available electronically on
Emerson.com/Rosemount.
WARNING
Explosions can result in death or serious injury.
- Transmitters located in hazardous areas should be installed in accordance with local codes and requirements for that area.
- Connection to transmitter housing uses a ½–14 NPT thread form. For hazardous location installations, the Rosemount 4600 shall be connected using a suitable junction box, e.g. in the type of protection flameproof enclosure “d” or increased safety “e”. Use appropriately rated Ex adapters, blanking elements, and glands during installation.
- Keep process insulation at least 1-in. (25 mm) from the transmitter connection.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
CAUTION
Apply torque only to the hex flat located at the process end of the transmitter. Do not apply torque to the transmitter body or electrical connection – severe damage could result. Do not exceed 100 ft-lb.
Mount the transmitter
1.1 Electrical connection
- Pull the leads through the threaded mounting hole in the panel wall.
- Hand tightens the electrical connection into the mounting hole.
- **** Using a wrench on the hex flat at the process connection, apply sufficient torque to prevent transmitter vibration. Do not exceed 100 ft-lb.
1.2 Process connection
- Hand tightens the appropriately sized impulse piping connector into the process connection.
- **** Using a wrench on the hex flat at the impulse piping connection, apply enough torque to prevent process fluid leakage. Do not exceed 100 ft-lb.
Connect the wiring and power
Use the following steps to wire the transmitter:
- Connect the red lead to the “+” terminal of the power supply.
- Connect the black lead to the “-” terminal of the I/O card on the PLC.
- Connect the green lead to the panel ground.
The figure below shows the wiring connections necessary to power a Rosemount
4600 and enable communications with a hand-held Field Communicator.
Figure 1. Rosemount 4600 Field Wiring
A. Rosemount 4600
B. RL > 250 ohm
C. Power supply| D. I/A card
E. PLC
F. Field Communicator
---|---
2.1 Power supply
The dc power supply should provide power with less than two percent ripple.
The total resistance load is the sum of the resistance of the signal leads and
the load resistance of the controller, indicator, and related pieces.
Note that the resistance of intrinsic safety barriers, if used, must be
included.
Figure 2. Load Limitation
Maximum loop resistance = 43.5 (power supply voltage – 11.25)
The Field Communicator requires a minimum loop resistance of 250Ω for communication.
Configure the transmitter
Note
A check ( ✓ ) indicates the basic configuration parameters. At a minimum,
these parameters should be verified as part of the configuration and startup
procedure.
Table 1. Field Communicator Fast Key Sequence
Function | Fast Key sequence |
---|---|
Alarm Level Config. | 1, 4, 2, 7, 7 |
Alarm and Saturation Levels | 1, 4, 2, 7 |
Analog Output Alarm Direction | 1, 4, 2, 7, 6 |
Analog Output Trim | 1, 2, 3, 2 |
Burst Mode On/Off | 1, 4, 3, 3, 3 |
Burst Options | 1, 4, 3, 3, 4 |
✓ Damping | 1, 3, 6 |
Date | 1, 3, 4, 1 |
Descriptor | 1, 3, 4, 2 |
Digital To Analog Trim (4–20 mA Output) | 1, 2, 3, 2, 1 |
Field Device Information | 1, 4, 4, 1 |
Loop Test | 1, 2, 2 |
Function | Fast Key sequence |
--- | --- |
Lower Sensor Trim | 1, 2, 3, 3, 2 |
Message | 1, 3, 4, 3 |
Number of Requested Preambles | 1, 4, 3, 3, 2 |
Pressure Alert Config. | 1, 4, 3, 5, 3 |
Poll Address | 1, 4, 3, 3, 1 |
Poll a Multidropped Transmitter | Left Arrow, 4, 1, 1 |
Re-mapping | 1, 4, 3, 6, 4 |
Rerange- Keypad Input | 1, 2, 3, 1, 1 |
Saturation Level Config. | 1, 4, 2, 7, 8 |
Scaled D/A Trim (4–20 mA Output) | 1, 2, 3, 2, 2 |
Scaled Variable Config. | 1, 4, 3, 4, 7 |
Self Test (Transmitter) | 1, 2, 1, 1 |
Sensor Information | 1, 4, 4, 2 |
Sensor Temperature | 1, 1, 4 |
Sensor Trim | 1, 2, 3, 3 |
Sensor Trim Points | 1, 2, 3, 3, 5 |
Status | 1, 2, 1, 2 |
✓ Tag | 1, 3, 1 |
Temperature Alert Config. | 1, 4, 3, 5, 4 |
Transmitter Security (Write Protect) | 1, 3, 4, 5 |
✓ Units (Process Variable) | 1, 3, 2 |
Upper Sensor Trim | 1, 2, 3, 3, 3 |
Zero Trim | 1, 2, 3, 3, 1 |
Trim the transmitter
Note
Transmitters are shipped from Emerson™ fully configured per request or by the
factory default of full scale (span = upper range limit).
4.1 Zero trim
A zero trim is a single-point adjustment to compensate for mounting position and sealed gauge pressure effects. When performing a zero trim, ensure the transmitter is vented to atmosphere.
4.2 Using the Field Communicator
Fast Keys | 1, 3, 3, 2 |
---|
- Vent the transmitter to the atmosphere and connect Field Communicator.
- At the main menu, input the Fast Key sequence.
- Follow the commands to perform a zero trim.
4.3 Using the transmitter zero adjustment target
- Vent the transmitter.
- Set the 4 mA point by touching the magnetic end of a small magnetic tool to the zero targets (Z) on the transmitter. You must maintain contact for at least two seconds, but no longer than 10 seconds for the zero function to activate.
- Verify the output is 4 mA.
Figure 3. Local Zero and Span Target Locations
A. Magnetic span target
B. Magnetic zero target
Safety Instrumented Systems (SIS)
The following section applies to Rosemount 4600 Transmitters used in SIS
applications.
Note
Transmitter output is not safety-rated during the following: configuration
changes, multidrop, and loop test. Alternative means should be used to ensure
process safety during
transmitter configuration and maintenance activities.
Installation
No special installation is required in addition to the standard installation
practices outlined in this document. The loop must be designed so the terminal
voltage does not drop below 11.25 Vdc when the transmitter output is 22.5 mA.
Configuration
Use any HART ® compliant master to communicate with and verify the
configuration of the Rosemount 4600.
User-selected damping will affect the transmitter’s ability to respond to
changes in the applied process. The damping value + response time must not
exceed the loop requirements.
Note
DCS or safety logic solver must be configured to match transmitter
configuration. Figure 4 identifies the two-alarm levels available and their
operation values. Change the alarm
directly to the required HI or LO alarm position.
Figure 4. Alarm Levels
- Transmitter Failure, alarm in LO position.
- Transmitter Failure, alarm in HI position.
Reference Table 1 on page 4 for the Fast Keys to change alarm position.
Note
Some detected faults are indicated on the analog output at a level above the
high alarm regardless of the alarm selection.
Operation and maintenance
Proof test and inspection
The following proof tests are recommended. Proof test results and corrective
actions taken must be documented at
Emerson.com/Rosemount/Safety-Measurement in the event that an error is found in the safety
functionality.
Reference Table 1 for the Fast Keys to perform a Loop Test, Analog Output
Trim, or Sensor Trim. See the Rosemount 4600 Reference Manual for additional
information.
Proof test
This proof test will detect 90 percent of DU failures not detected by the
Rosemount 4600 automatic diagnostics.
-
Conduct a loop test. On Field Communicator enter the Fast Key sequence 1,2,2.
a. Enter the milliampere value representing a high alarm state and verify that the analog current reaches that value. (1)
b. Enter the milliampere value representing a low alarm state and verify that the analog current reaches that value. (2) -
Perform a two-point sensor calibration check using the 4–20 mA range points as the calibration points.
a. If necessary, use one of the trim procedures available in the Rosemount 4600 Reference Manual to calibrate. (3)
Note
The user determines the proof-test requirements for impulse piping.
Product repair
All failures detected by the transmitter diagnostics or by the proof-test must
be reported. Feedback can be submitted electronically at
Emerson.com/Rosemount/Safety-Measurement
6.1 Reference
Specifications
The transmitter must be operated in accordance with the functional and
performance specifications provided in the reference manual.
Failure rate data
The FMEDA report includes failure rates. This report is available at
Emerson.com/Rosemount.
Rosemount 4600 safety failure values
Safety accuracy: 2.0 percent (4)
Safety response time- 1.5 seconds
Product life
50 years – based on worst-case component wear-out mechanisms – not based on
wear-out process wetted materials.
- This tests for compliance voltage problems such as a low loop power supply voltage or increased wiring resistance. This also tests for other possible failures.
- This tests for possible quiescent current-related failures.
- If the two-point calibration is performed with electrical instrumentation, this proof test will not detect any failures of the sensor.
- A two percent variation of the transmitter mA output is allowed before a safety trip. Trip values in the DCS or safety logic solver should be derated by two percent.
Product Certifications
Rev 1.7
7.1 European directive information
A copy of the EC Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EC Declaration of
Conformity can be found at
Emerson.com/Rosemount.
7.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
North America
E5 US Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 3012302
Standards: FM Class 3600 – 2011; Class 3615 – 2006; FM Class 3810 – 2005;
NEMA® 250 – 1991; ANSI/ISA-S12.0.01 – 1998; ANSI/ISA-S12.22.01- 1998;
ANSI/ISA-60079-0 – 2009
Markings: Explosionproof for Class I, Division 1, Groups B, C, and D;
Flameproof for Class 1, Zone 1 AEx d IIC T5 (–40 to 85 °C); Dust-ignition
proof for Class II and
Class III, Division 1, Groups E, F, and G; Temperature Code T5 (Tamb= –40 to
85 °C); Enclosure Type 4X; Conduit seal not required.
I5 US Intrinsic Safety (IS), Nonincendive (NI) Certificate: 3012302 Standards:
FM Class 3600 – 2011; Class 3610 – 2010; Class 3611-2004; NEMA 250 -1991;
ANSI/ISA-S12.0.01 – 1998; ANSI/ISA-S12.22.01 – 1998;
ANSI/ISA-60079-0-2009; ANSI/ISA-60079-11- 2009
Markings: Intrinsically Safe for use in Class I, Division 1, Groups A, B, C,
and D; Temperature Code T4 (–50 to 70 °C); Intrinsically Safe for use in Class
I, Zone 0 AEx ia IIC T4 (–50 to 70 °C) in accordance with the control drawing
04620-5007; Nonincendive for Class I, Division 2, Groups A, B, C, and D when
connected in accordance with Rosemount drawing 04620-5007; Enclosure Type 4X
E6 Canada Explosionproof and Division 2
Certificate: 1384913
Standards: CSA Std C22.2 No. 25-1966; CSA Std C22.2 No. 30-M1986;
CAN/CSA-C22.2 No. 94-M91; CSA Std C22.2 No. 142-M1987; CAN/CSA-C22.2 No.
157-92; CSA Std C22.2 No. 213-M1987; CAN/CSA-E79- 0-95; CAN/CSA- E79-1-95;
CAN/CSA- E79-11-95; ANSI/ISA No. 12.27.01-2011
Markings: Explosionproof for Class I, Division 1, Groups B, C, and D; Dust-
Ignitionproof for Class II and Class III, Division 1, Groups E, F, and G;
Temperature Code T5 (–50 to 40 °C); Explosion-proof for Class 1, Zone 1 Ex d
IIC T5 (–20 to 40 °C); Suitable for Class I, Division 2, Groups A, B, C, and D
when installed per Rosemount drawing 04620-5005; Enclosure Type 4X; Conduit
seal not required.
I6 Canada Intrinsic Safety
Certificate: 1384913
Standards: CSA Std C22.2 No. 25-1966; CSA Std C22.2 No. 30-M1986;
CAN/CSA-C22.2 No. 94-M91; CSA Std C22.2 No. 142-M1987; CAN/CSA-C22.2 No.
157-92; CSA Std C22.2 No. 213-M1987; CAN/CSA-E79- 0-95; CAN/CSA- E79-1-95;
CAN/CSA- E79-11-95; ANSI/ISA No. 12.27.01-2011
Markings: Intrinsically Safe for use in Class I, Division 1, Groups A, B, C,
and D; Temperature Code T3C (–50 to 70 °C); Intrinsically Safe for use in
Class I, Zone 0 Ex ia IIC T4 (–50 to 70 °C) when connected in accordance with
Rosemount drawing 04620-5005; Enclosure Type 4X; For entity parameters see
control drawing 04620-5005
Europe
E1 ATEX Flameproof
Certificate: KEMA02ATEX2231X
Standards: EN60079-0:2006; EN60079-1:2014; EN60079-26:2015;
Markings: 1/2 G Ex db IIC T6…T4 Ga/Gb T4/T5(–60 °C ≤ Ta ≤ +80 °C), T6 (–60 °C
≤ Ta ≤ +70 °C)
Process connection temperature range (°C)| Ambient temperature
range| Temperature class/maximum surface temperature
---|---|---
–60 to +70 °C| –60 to +70 °C| T6/ T135 °C
–60 to +80 °C|
–60 to +80 °C
| T5/ T135 °C
–60 to +120 °C| T4/ T135 °C
Special Conditions for Safe Use (X):
-
The device contains a thin wall diaphragm less than 1 mm thick that forms a boundary between Category 1 (process connection) and Category 2 (all other parts of the equipment). The model code and data sheet are to be consulted for details of the diaphragm material. During installation, maintenance, and use the environmental conditions to which the diaphragm will be subjected shall be taken into account. The manufacturer’s instructions for installation and maintenance shall be followed in detail
to assure safety during its expected lifetime. -
Flameproof joints are not intended for repair.
I1 ATEX Intrinsic Safety
Certificate: Baseefa03ATEX0114X
Standards: EN60079-0: 2012+A11:3013, EN60079-11:2012
Markings: 1 G Ex ia IIC T4 Ga (–40 °C ≤ T ≤ +70 °C)
Parameters | HART |
---|---|
Voltage U i | 30 V |
Current I i | 200 mA |
Power P i | 1.0 W |
Capacitance C i | 35 nF |
Inductance L i | 390 μH |
Special Condition for Safe Use (X):
- The equipment with the Transient Protection (T1) option is not capable of withstanding the 500 V insulation test required by Clause 6.3.13 of EN60079-11:2012. This must be taken into account when installing the equipment.
This must be taken into account when installing the equipment.
N1 ATEX Type n
Certificate: Baseefa03ATEX0115X
Standards: EN60079-0:2012+A11:2013, EN60079-15:2010
Markings: 3G Ex nA IIC T5 Gc (–40 °C ≤ Ta ≤ +70 °C) Ui = 42.4 V
Special Condition for Safe Use (X):
- The equipment with the Transient Protection (T1) option is not capable of withstanding the 500 V insulation test required by Clause 6.5.1 of EN60079-15:2010. This must be taken into account when installing the equipment.
ND ATEX Dust Ignition-proof
Certificate: KEMA02ATEX2231X
Standards: EN60079-0:2012+A11:2013, EN 60079-31:2014
Markings: 2 D Ex tb IIIC T135 °C Db (–60 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
-
The device contains a thin wall diaphragm less than 1 mm thick that forms a boundary between Category 1 (process connection) and Category 2 (all other parts of the equipment). The model code and data sheet are to be consulted for details of the diaphragm material. During installation, maintenance, and use of the environmental conditions to which the diaphragm will be subjected shall be taken into account. The manufacturer’s instructions for installation and maintenance shall be followed in detail
to assure safety during its expected lifetime. -
Flameproof joints are not intended for repair.
International
E7 IECEX Flameproof and Dust
Certificate: IECEx DEK 13.0017X
Standards: IEC 60079-0:2011; IEC 60079-1:2014; IEC 60079-26:2014; IEC
60079-31:2013
Markings: Ex db IIC T6…T4 Ga/Gb T4/T5(–60 °C ≤ Ta ≤ +80 °C), T6 (–60 °C ≤ Ta ≤
+70 °C) Ex tb IIIC T135 °C Db (–60 °C ≤ Ta ≤ +80 °C)
Process connection temperature range (°C)| Ambient temperature
range| Temperature class/maximum surface temperature
---|---|---
–60 to +70 °C| –60 to +70 °C| T6/ T135 °C
–60 to +80 °C|
–60 to +80 °C
| T5/ T135 °C
–60 to +120 °C| T4/ T135 °C
Special Conditions for Safe Use (X):
-
The device contains a thin wall diaphragm less than 1 mm thick that forms a boundary between Category 1 (process connection) and Category 2 (all other parts of the
equipment). The model code and data sheet are to be consulted for details of the diaphragm material. During installation, maintenance, and use the environmental conditions to which the diaphragm will be subjected shall be taken into account. The manufacturer’s instructions for installation and maintenance shall be followed in detail
to assure safety during its expected lifetime. -
Flameproof joints are not intended for repair.
Brazil
E2 INMETRO Flameproof
Certificate: UL-BR 15.0509X
Standards: ABNT NBR IEC 60079-0: ABNT NBR IEC 60079-1:
ABNT NBR IEC 60079-26.
Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤
+80 °C)
Special Condition for Safe Use (X):
- This device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail in order to assure safety during its expected lifetime.
Technical Regulations Customs Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.GB05.B.00401
Markings: Ga/Gb Ex d IIC T6…T4 X, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5(–60 °C ≤ Ta
≤ +80 °C)
Special Condition for Safe Use (X):
- See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate: RU C-US.GB05.B.00401
Markings: 0Ex ia IIC T4 Ga X (–40 °C ≤ Ta ≤ +70 °C)
Special Condition for Safe Use (X):
- See certificate for special conditions.
Combinations
K1 Combination of E1, I1, and N1
K5 Combination of E5 and I5
K6 Combination of E6 and I6
KA Combination of E1, I1, E6, and I6
KB Combination of E5, E6, I5, and I6
KC Combination of E1, E5, I1, and I5
KM Combination of EM and IM
Figure 5. Rosemount 4600 Declaration of Conformity
EU Declaration of Conformity
No: RMD 1048 Rev. J
We,
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
declare under our sole responsibility that the product,
Rosemount™ 4600 Pressure Transmitters
manufactured by,
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
to which this declaration relates, is in conformity with the provisions of the
European Union
Directives, including the latest amendments, as shown in the attached
schedule.
Assumption of conformity is based on the application of the harmonized
standards and, when applicable or required, a European Union notified body
certification, as shown in the attached schedule.
(signature)
Chris LaPoint
(name – printed)
Vice President of Global Quality (function name – printed)
1-Feb-19; Shakopee, MN USA
(date of issue)
EMC Directive (2014/30/EU)
All Models 4600 Pressure Transmitters
EN 61326-1:2013, EN 61326-2-3:2013
ATEX Directive (2014/34/EU)
Model 4600 Pressure Transmitter
Baseefa03ATEX0114X – Intrinsic Safety Certificate
Equipment Group II Category 1 G
Ex ia IIC T4 Ga
Harmonized Standards Used:
EN60079-0:2012+A11:2013, EN60079-11:2012,
Baseefa03ATEX0115X – Type n Certificate
Equipment Group II Category 3 G
Ex nA IIC T5 Gc
Harmonized Standards Used:
EN60079-0:2012+A11:2013, EN60079-15:2010
KEMA02ATEX2231X – Flameproof and Dust Certificate
Equipment Group II Category 1/2 G
Ex db IIC T6…T4 Ga/Gb
Equipment Group II Category 2 D
Ex tb IIIC T135°C Db
Harmonized Standards Used:
EN60079-0:2012+A11:2013, EN60079-1:2014, EN60079-26:2015, EN6007931:2014
ATEX Notified Bodies for EC Type Examination Certificate
DEKRA
[Notified Body Number: 0344] Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Postbank 6794687
SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
ATEX Notified Body for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
China RoHS Rosemount 4600
List of Rosemount 4600 Parts with China RoHS Concentration above MCVs
__**__**
Part Name
| **Hazardous Substances
---|---
Lead (Pb)| Mercury (Hg)| Cadmium (Cd)| Hexavalent Chromium
(Cr +6)| Polybrominated biphenyls (PBB)| Polybrominated diphenyl
ethers (PBDE)
Sensor Assembly| X| O| O| O| O|
** O
SJ/T11364
This table is proposed in accordance with the provision of SJ/T11364.
O: GB/T 26572
O: Indicate that said hazardous substance in all of the homogeneous materials
for this part is below the limit requirement of GB/T 26572.
X: GB/T 26572
X: Indicate that said hazardous substance contained in at least one of the
homogeneous materials used for this part is above the limit requirement of
GB/T 26572.
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RMT-NA.RCCRFQ@Emerson.com
| Linkedin.com/company/Emerson-Automation-Solutions
---|---
| Twitter.com/Rosemount_News
| Facebook.com/Rosemount
|
Youtube.corniuser/RosemountMeasurement
| Google.comf+RosemountMeasurement
Emerson Terms and Conditions of Sale are available upon request. The Emerson
logo is a trademark and service mark of Emerson Electric Co.
Rosemount is a mark of one of the Emerson family of companies.
All other marks are the property of their respective owners.
© 2022 Emerson. All rights reserved.
Quick Start Guide
00825-0200-4022, Rev HB
January 2022
ROSEMOUNT™
References
- Emerson Global | Emerson
- Rosemount | Emerson US
- Rosemount | Emerson US
- Safety Measurement | Emerson US
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>