IBD Global SensoIRIS CSST IS Intelligent Analogue Addressable Sounder Installation Guide

June 1, 2024
IBD Global

IBD-Global-logo

IBD Global SensoIRIS CSST IS Intelligent Analogue Addressable Sounder

IBD-Global-SensoIRIS-CSST-IS-Intelligent-Analogue-Addressable-Sounder-
product-image

Specifications:

  • Operating Voltage Range: 16 – 32VDC
  • Maximal consumption at communication: 470mA @ 27VDC
  • Maximal consumption: [not specified]
  • Sound Level at 1m: 88dB – 89dB
  • Isolator Module Technical Specifications:
    • Vmax (Max. line voltage): 32V
    • Vnom (Nom. line voltage): 28V
    • Vmin (Min. line voltage): 16V
    • Vso max (Max. voltage at which the device isolates): 7.5V
    • Vso min (Min. voltage at which the device isolates): 5.9V
    • Vsc max (Max. voltage at which the device reconnects): 6.7V
    • Vsc min (Min. voltage at which the device reconnects): 5V
    • Ic max (Max. rated continuous current with the switch closed): 0.7A
    • Is max (Max. rated switching current under short circuit): 1.8A

Product Usage Instructions

  • Installation:
    For indoor use, ensure the product is installed with the IP21C* rating intact. Use SensoIRIS B124 low profile base or B124-HP high profile base for addressable detectors and sounders.

  • Warranty Information:
    All devices come with a warranty valid from the date of manufacture. The date of manufacture is indicated on the device with the first two numbers representing the year and the last two representing the month.

  • A-weighted Sound Level Diagram:
    The sound levels measured at a distance of 1m range from 85dB to 89dB.

  • Isolator Module Information:
    The isolator module has specific voltage parameters for isolation and reconnection. Ensure the voltages are within the specified range for optimal functionality.

FAQ:

  • Q: What should I do if my device is consuming more power than specified?
    A: If you notice excessive power consumption, check for any communication issues or potential short circuits that may be causing the higher consumption. Contact your distributor for further assistance.

  • Q: Can I use the product outdoors?
    A: The product is suitable for outdoor use, but ensure proper protection against environmental elements to maintain its functionality.

SensoIRIS CSST IS

Intelligent analogue address able sounder with strobe base and with built-in isolator module

DoP No: 197
Tested by EVPU

Teletek Electronics JSC

  • Address: 2 Iliyansko shose Str,
  • 1220 Sofia, Bulgaria
  • EN 54-3:2001
  • EN 54-3:2001/A1:2002
  • EN 54-3:2001/A2:2006
  • EN 54-17:2005
  • EN 54-17:2005/AC:2007
  • Sounder Type: A

Dimensions

Installation

Installation Instruction

ATTENTION: Read carefully this installation Instructions before installing the device!

  • This manual is subject to change without notice!
  • SensoIRIS CSST IS is аn addressable sounder with strobe base and with built-in isolator module, compatible for mounting on all models standard bases for SensoIRIS devices. The sounder is designed for installing in addressable fire alarm systems which support operation via TTE communication protocol. The device is powered on from the panel and can be controlled via the communication protocol.
  • SensoIRIS CSST IS supports 32 different tone types at two sound levels. The tone type and sound level are programmed from the control panel.
  • The SensoIRIS CSST IS is compatible for operation with SensoIRIS addressable detectors series: T110 (IS), S130 (IS) and M140 (IS).

The sounder is compatible for mounting on the following bases:

  1. SensoIRIS B124 – Standard low profile base for addressable detectors and sounders.
  2. SensoIRIS B124-HP – Standard high profile base for addressable detectors and sounders

Installation Instructions

Attention: Power off the loop circuit before installing the SensoRIS CSST IS addressable sounder!

  1. Choose the proper place for installation of the device.
  2. Set the device address using SensoIRIS Programmer or directly from addressable fire panel. The address must be in the range from 1 to 250.
  3. Mount the standard base (SensoRIS B124/B124-HP), choosing the type according the requirement of the installation. If you want to “lock” the sounder to the standard base, remove the little “tooth” on the top of the locking mechanism of the base.
  4. Connect the standard base to the fire panel using the wiring diagrams.
  5. Insert the SensoIRIS CSST IS sounder into the standard base and rotate it clockwise until it drops into place – the short mark on the standard base fits with the long mark on the sounder body. Continue to rotate the sounder until the short and the long marks coincides with those on the base – a click is heard.
  6. Insert a detector – SensolRIS T110 (IS)/ S130 (IS)/ M140 (IS) – into the sounder base and rotate clockwise until it drops into place – the short mark on the sounder fits with that on the detector. Continue to rotate the detector until its mark coincides with the long mark on the sounder – a click is heard. If you want to “lock” the detector to the sounder before installation, remove the little “tooth” on the top of the locking mechanism of the sounder. Note: The mounted detector on the Senso RIS CSST IS sounder is assigned at different address to the control panel!
  7. Program the sounder parameters. Refer to the Programming manual of the control panel for more details. The programming manuals for IRIS and SIMPO fire alarm panels are accessible for download from the site of the manufacturer: http://www.teletek-electronics.com
  8. Test the sounder for proper operation.
  9. If the sounder has been locked to the base, to remove it for a service schedule maintenance and cleaning, you have to use the special tool available in all SensoRIS standard bases. Light press with the tool into the base opening and at the same time rotate the sounder body counter-clockwise. The same way is used for unlocking a detector from the SensoRIS CSST IS addressable sounder.

Warranty

  • All devices carry on a warranty valid from the date of manufacture. The date of manufacture can be checked on the device. The first two numbers represent the year and the last two – the month.
  • For example: The date code “21 07”, means the sounder is manufactured in July, 2021.
  • To return goods for warranty service, please contact with your local distributer for details.

Technical Specifications

  • Operating Voltage Range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 – 32VDC

  • Maximal consumption at communication . . . . . . . . . . . . . . . . .  . . . . . . . . . . . 470 μА @ 27VDC

  • Maximal consumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    • main tone type 27, low volume level . . . . . . . . . . . . . . . . . – . . . . . . . . . . . . . . . . 3 mА @ 27VDC
    • main tone type 27, high volume level . . . . . . . . . . . . . . . . – . . . . . . . . . . . . . . . . 10 mА @ 27VDC
  • Power volume (main tone type 27): . . . . . . . . . . . . . . . . . . . . .

    • low volume (up to 100 pcs sounders* to the loop) . . . . . . – . . . . . . . ~ 81dB (A) ± 3dB @ 1m
    • high volume (up to 30 pcs sounders* to the loop) . . . . . . – . . . . . . ~ 88dB (A) ± 3dB @ 1m
  • Power volume (other tone types): . . . . . . . . . . . . . . . . . . . . . .

    • low volume (up to 100 pcs sounders* to the loop) . . . . . . . . . . . ~ 81dB (A) ± 3dB @ 1m
    • high volume (up to 30 pcs sounders* to the loop) . . . . . . . . . . . ~ 87dB (A) ± 3dB @ 1m
  • Frequency of the strobe flash. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Hz

  • Number of tone types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

  • Supported communication protocol . . . . . . . . . . . . . . . . . .  . . . . . . . . . . . . . . . ТТЕ

  • Relative humidity resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (93 ± 3)% @ +40°C

  • Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PC, transparent

  • SensoIRIS CSST IS

Isolator Module Technical Specifications

  • Vmax . . . Max. line voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32V
  • Vnom . . . Nom. line voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28V
  • Vmin . . . . Min. line voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . 16V
  • Vso max . Max. voltage at which the device isolates* . . . . . . . . . . . . . . . .. . . . . . . . 7.5V
  • Vso min. . Min. voltage at which the device isolates* . . . . . . . . . . . . . . . . . . . . . . . . . . 5.9V
  • Vsc max . Max. voltage at which the device reconnects** . . . . . . . . . . . . . . 6.7V
  • Vsc min. . Min. voltage at which the device reconnects** . . . . . . . . . . . . . . . . . . 5V
  • Ic max . . . Max. rated continuous current with the switch closed. . . . . . . . . . . . 0.7A
  • Is max. . . Max. rated switching current (e.g. under short circuit) . . . . . . . . . . . . . . . . 1.8A
  • II max . . . Max. leakage current with the switch open (isolated state). . . . . . . . . . . . . . . . . . . 16mA
  • Zc max . . Max. series impedance with the switch closed . . . . . . . . . . . . 0.12Ω@28VDC; 0.15Ω@15VDC

* Vso max/min
Note: Switches from closed to open
** Vsc max/min
Note: Switches from open to closed

Assembly

IBD-Global-SensoIRIS-CSST-IS-Intelligent-Analogue-Addressable-Sounder-fig-
\(4\)

IBD-Global-SensoIRIS-CSST-IS-Intelligent-Analogue-Addressable-Sounder-fig-
\(5\)

IBD-Global-SensoIRIS-CSST-IS-Intelligent-Analogue-Addressable-Sounder-fig-
\(6\)

Legend

  • RI – Remote Indicator
  • +Loop – Positive loop wire
  • -Loop – Negative loop wire
  • Mounting of T110 IS, S130 IS and M140 IS to the CSST IS and using the built-in isolators in the detector and in the sounder
  • Mounting of T110, S130 and M140 to the CSST IS and not using the built-in isolator in the sounder; Mounting of T110 IS, S130 IS and M140 IS to the CSST IS and not using the built-in isolators in the detector and in the sounder

At the end of installation, the long marks of the standard base and CSST IS sounder must coincide with the single mark of the mounted detector

Tone types and description

IBD-Global-SensoIRIS-CSST-IS-Intelligent-Analogue-Addressable-Sounder-fig-
\(11\) IBD-Global-
SensoIRIS-CSST-IS-Intelligent-Analogue-Addressable-Sounder-fig-
\(12\) IBD-Global-
SensoIRIS-CSST-IS-Intelligent-Analogue-Addressable-Sounder-fig-
\(13\)

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals