Description
The 2010-2A-PAK-HPL Panel Activation Key (PAK) increases the maximum loop output from 500 mA to 800 mA (high-powered loop) on compatible Aritech 2X-A addressable control panels. A new PAK is required for each control panel that requires high-powered loops. Please note that the PAK is only compatible with 2X-A control panels.

Product Usage Instructions

Registration
Follow these steps to register or unregister the PAK. Installer-level access is required.

To Register the PAK

  1. Insert the PAK into either of the USB type A slots on the control panel main board.
  2. Select Panel Setup on the control panel LCD, then choose Panel Activ. Key.
  3. Select Register New PAK, confirm details on the LCD, and press Continue.
  4. Press Register, then confirm the registration by pressing Yes.
  5. Apply the registration details to the panel by pressing Apply or register more PAKs by pressing Continue.
  6. Remove the PAK from the USB slot.
  7. Enable High-Power Loop in the control panel (Main Menu > Field Setup > High-Power Loop).

To Unregister the PAK

  1. Insert the PAK into either of the USB type A slots on the control panel main board.
  2. Select Panel Setup on the control panel LCD, then choose Panel Activ. Key.
  3. Select Unregister PAK and follow the on-screen instructions.
  4. Remove the PAK from the USB slot.

Specifications

KIDDWE-2X-A-Addressable-Control-Panels-fig-1

Regulatory information

Manufacturer Carrier Manufacturing Poland Spółka Z o.o., Ul. Kolejowa 24, 39-100 Ropczyce, Poland. Authorized EU manufacturing representative: Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Netherlands.
2012/19/EU (WEEE Directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: recyclethis.info

Contact information and product documentation
For contact information or to download the latest product documentation, visit firesecurityproducts.com

Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED PROFESSIONALS. CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR“AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND SECURITY RELATED PRODUCTS.

For more information on warranty disclaimers  and product safety information, please check https://firesecurityproducts.com/policy/productwarning/ or scan the QR code:

KIDDWE-2X-A-Addressable-Control-Panels-fig-2

FAQ

Q: Can I use the 2010-2A-PAK-HPL Panel Activation Key with any control panel?
A: No, the PAK is only compatible with 2X-A control panels.

Q: How do I enable a High-Power Loop after registering the PAK?

A: You can enable High-Power Loop in the control panel by navigating to Main Menu > Field Setup > High-Power Loop.