Altronix NetWaySP4PX 4-port Ethernet to Fiber Media Converter with Integral Power Supply Installation Guide
- June 3, 2024
- Altronix
Table of Contents
Altronix NetWaySP4PX 4-port Ethernet to Fiber Media Converter with
Integral Power Supply
Overview
Altronix NetWaySP4PX Media Converter with Integral Power, provides four (4) 1Gb SFP ports and four (4) ports for up to 120W per port (480W total) to be transmitted over single/multi-mode fiber or composite cable (powered) cable (fiber + copper combined) to NetWay Spectrum PoE Hardened Switches.
Features
Agency Listings
- CE : European Conformity.
Input
- 115VAC, 60Hz, 5.5A or 230VAC, 50/60Hz, 3A (auto-ranging).
Power
-
Four (4) 56VDC non power-limited outputs up to 120W max. full power per port. Total power: 480W.
-
IEEE 802.3af, IEEE 802.3at and
IEEE 802.3bt compliant. -
Short circuit protection.
SFP Ports
- Four (4) Gigabit SFP/Fiber ports.
- Use with SFP module 1000Base-X (1Gb), compliant to Class 1 laser product (not included).
Ethernet/Data
- • Four (4) ports to switch.
• Wire type: 4-pair CAT5e and higher.
• Connectivity: RJ45, auto-crossover.
• Speed: 10/100/1000Mbps.
• Distance: up to 100m.
Environmental
- Refer to Environmental Conditions on page 6.
Battery Backup
-
Built-in battery charger
(optional rack mount battery enclosure – RE2). -
Automatic switchover to stand-by battery when AC fails.
Compatible PoE Hardened Switches and Accessories
- NetWaySP1BTWPN: 3-port (802.3bt) PoE Hardened Switch with (1) SFP port.
- NetWaySP3WPN: 3-port PoE Hardened Switch with (1) SFP port.
- NetWay4EWPN: 4-port PoE Hardened Switch with (1) SFP port.
- NetWaySP4WPN: 4-port PoE Hardened Switch with (2) SFP ports.
- NetWaySP4BTWPN: 4-port (802.3bt) PoE Hardened Switch with (2) SFP ports.
- NetWaySP8WPN: 8- port PoE Hardened Switch with (2) SFP ports.
- Rack Mount Battery with (2) SFP ports.
- RE2: Rack Mount Battery Enclosure accommodates up to four (4) 12VDC/7AH batteries
Installation Instructions
Wiring methods shall be in accordance with the National Electrical Fig. 1a
Fig. 1b
Code (ANSI/NFPA70), local codes, and the authorities having jurisdiction.
NetWaySP4PX is not intended to be connected to outside plant leads. These
products are for indoor use only and must be installed within the protected
premises.
NetWaySP4PX must be installed in a restricted access area. If battery bracket
is removed, must be installed in a restricted access area (Fig. 1b, pg. 3).
The outputs are of a non-limited power source. For non-limited power sources,
additional protective circuitry and/or an appropriate fire enclosure for the
products supplied by this device are required.
-
Attach mounting brackets to the unit for rack or wall mount installation (Fig. 4 or 5, pg. 8).
Affix rubber pads to the unit for shelf installation (Fig. 6, pg. 8). -
Secure the unit in a rack or on a wall, or place unit on a shelf as desired.
Note: The following factors should be taken into consideration when installing these rack mount units:- The unit is to be installed in a space where the maximum ambient temperature does not exceed 104ºF (40ºC).
- Take care to ensure that there is sufficient air flow around the unit and that obstructions do not impede it.
- When mounting units in a rack, take care to avoid uneven loading which can cause a hazardous condition.
-
Plug the grounded AC line cord (included) into the IEC 320 connector of the unit (Fig. 2f, pg. 4). Plug unit into a reliable earth grounded socket. When using multiple units, the sum of the individual name plate ratings should not exceed the supply circuit rating. Do not connect to a receptacle controlled by a switch.
-
Connect structured cable from ethernet switch/NVR (network video server) to RJ45 jack marked
[Ethernet 1-4] (Fig. 2e, pg. 4).
Note: All cabling and wire must be UL Listed and/or Recognized wire suitable for their application. -
Connect Composite (Powered) Fiber cable: fiber portion to port marked [SFP 1-4], copper portion connects to output marked [OUT 56VDC, 1-4] (Fig. 2b & 2d, pg. 4).
-
Connect opposite end of Composite (Powered) Fiber cable: fiber portion to SFP port on NetWay Spectrum Hardened Switch, copper portion connects to power input of NetWay Spectrum Hardened Switch, carefully observing correct polarity (Refer to respective NetWay Spectrum Switch Installation Guide).
-
When the use of stand-by batteries is required, they must be sealed lead acid or gel type. Use 14 AWG or larger for all power connections. Connect four (4) 12VDC batteries in series to terminals marked [+ BAT –](Fig. 2h, pg. 4). Note: When batteries are not used, a loss of AC will result in a loss of output voltage.
Recommended Altronix SFP Modules
Altronix P1MM, P1SM10, P1AB2K and P1GCE are hot-pluggable SFP fiber
transceiver modules and are readily usable with all Altronix Spectrum fiber
optic equipment for 1Gb transmission rates.
P1MM – For use with Multi-Mode Fiber for distances up to 550m.
P1SM10 – For use with Single-Mode Fiber for distances up to 10km.
P1AB2K – For use with Single Strand Single-Mode Fiber for distances up to 2km.
P1GCE – For use with CAT5e or better for distances up to 100m.
Fig. 2
- 2a LED indicates AC Power is present.
- 2b 1Gb SFP port.
- 2c LED indicates fiber link.
- 2d 120W max output (480W total power)
- 2e RJ45 connects to switch
- 2f IEC 320 Connector: 115/230VAC (grounded line cord included).
- 2g Built-in battery charger: Charges stand-by batteries for applications requiring back-up.
(Optional rack mount battery enclosure available – RE2)
Typing Application
Technical Specifications
The lightning flash with arrowhead symbol within an equilateral triangle is
intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE
within the product’s enclosure that may be of sufficient magnitude to
constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the
user to the presence of important operating and maintenance (servicing)
instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure.
There are no user serviceable parts inside.
Refer servicing to qualified service personnel.
Parameter | Description |
---|---|
Number of Ports | Four (4) Gigabit SFP Ports. Four (4) ports 10/100/1000Mbps. |
Power Outputs | Four (4) 56VDC non power-limited outputs 120W max (480W total). |
Input power requirements | 115VAC, 60Hz, 5.5A or 230VAC, 50/60Hz, 3A. |
Environmental Conditions
| Operating Ambient Temperature (120W): – 40ºC to 50ºC (– 40ºF to 122ºF) Relative Humidity: 85%, +/– 5%
Storage Temperature: – 40ºC to 85ºC (– 40ºF to 185ºF). Operating Altitude: – 304.8 to 2,000m.
Regulatory Compliance| CE European Conformity.
Weights (approx.)| Product: 3.8 lbs. (1.7kg) | Shipping: 6.0 lbs. (2.7kg)
Mounting Options
Rack Mount Installation
- Remove and discard factory installed screws from both sides of rack chassis (Fig. 4a).
- Install mounting brackets (A) on the left and right side of rack chassis using the four (4) flat head screws (B)(included) (Fig. 4b).
- Place unit into desired EIA 19” rack position and secure with mounting screws (not included) (Fig. 4c).
Wall Mount Installation
-
Install mounting brackets (A) on the left and right side of rack chassis using
four (4) flat head screws (B) (included) (Fig. 5a). -
Place unit at desired location and secure with #6 size screws or larger (not included) (Fig. 5b). Caution: It is necessary to make sure mounting screws are securely fastened to a beam when installing the unit vertically.
Shelf Installation
- Position and affix rubber pads (C) (included) at each corner on the bottom of the unit (Fig. 6)
- Place unit in desired location. Fig. 6
Altronix is not responsible for any typographical errors.