victron energy 12-500-20-120V Multi Plus Charger User Manual

June 1, 2024
victron energy

victron-energy-LOGO

victron energy 12-500-20-120V Multi Plus Charger

victron-energy-12-500-20-120V-Multi-Plus-Charger-
PRODUCT

Product Information

  • Specifications
    • Model: MultiPlus
    • Voltage Options: 12/500/20-120V and 12/1200/50-120V
    • Revision: 00 – 10/2023
  • Description
    • General
    • The MultiPlus is a versatile power management device designed and tested to meet international standards. It serves as both an inverter and a battery charger for efficient energy usage.
    • Battery Charger
    • The MultiPlus features a built-in battery charger that ensures optimal charging of connected batteries, maintaining their performance and longevity.
  • Safety Instructions
    • General
    • Prioritize safety by thoroughly reading the documentation provided with the product before usage.
    • The equipment should only be used for its intended purpose and in compliance with international standards.
    • Installation
    • Follow the installation instructions carefully, adhering to local and national wiring standards.
    • Electrical work should comply with the Canadian Electrical Code, Part 1, and wiring methods per the National Electrical Code, ANSI/NFPA 70.
    • Troubleshooting
    • If you encounter any issues with the MultiPlus, refer to the troubleshooting section in the manual for guidance on resolving common problems.

Product Usage Instructions

  • Safety Precautions
    • Read all safety instructions before using the product.
    • Only qualified personnel should perform servicing.
    • Always switch off AC power and disconnect the battery before maintenance.
    • Do not open the enclosure or operate the product without all panels in place.
    • Ensure the batteries used are compatible with the product.
    • Do not charge non-rechargeable or frozen batteries.
    • Keep the product away from areas prone to gas or dust explosions.
    • Supervise children using the appliance.
  • Installation
    • Before installation, carefully read and follow the provided installation instructions. Ensure compliance with relevant electrical codes for a safe and proper setup.
  • Operation
    • Connect the MultiPlus to a compatible battery following the manufacturer’s guidelines.
    • Turn on the AC power after ensuring proper connections.
    • Use the device as an inverter or battery charger as needed.
    • Monitor the device for any unusual behaviour or indicators of malfunction.

FAQs

  • Q: Can I use the MultiPlus with non-rechargeable batteries?
    • A: No, it is not recommended to charge non-rechargeable batteries with the MultiPlus as it may cause damage to both the product and the battery.
  • Q: What should I do if I suspect blown fuses in the unit?
    • A: If you suspect blown fuses, do not attempt to replace them yourself. Take the unit to an authorized service centre for evaluation and replacement if necessary.

Safety instructions

Please familiarise yourself with the safety features and instructions by first reading the documentation supplied with this product before using the equipment. This product has been designed and tested by international standards. The equipment must be used exclusively for the purpose for which it was designed.

General

  • Please read the documentation supplied with this product first so that you are familiar with the safety signs and directions before using the product.
  • This product is designed and tested per international standards. The equipment should be used for the designated application only.
  • WARNING – These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions unless you are qualified to do so.
  • WARNING – The product is used in combination with a permanent energy source (battery). Even if the equipment is switched off, a dangerous electrical voltage can occur at the input and/or output terminals. Always switch the AC power off and disconnect the battery before performing maintenance.
  • The product contains no internal user-serviceable parts. Do not open the enclosure, and do not put the product into operation unless all panels are fitted. All maintenance should be performed by qualified personnel. Internal fuses are not user-replaceable.
  • A unit with suspected blown fuses should be taken to an authorised service centre for evaluation.
  • Never use the product at sites where gas or dust explosions could occur. Refer to the specifications provided by the manufacturer of the battery to ensure that the battery is suitable for use with this product.
  • The battery manufacturer’s safety instructions should always be observed.
  • Never try to charge non-rechargeable – or frozen batteries.
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

Installation

  • Read the installation instructions before commencing installation activities. For electrical work, follow the local national wiring standards, regulations, and installation instructions. The installation shall be per the Canadian Electrical Code, Part 1. The wiring methods shall be per the National Electrical Code, ANSI/NFPA 70.
  • This product is a safety class I device (supplied with a ground terminal for safety purposes). Its AC input and/or output terminals must be provided with uninterruptible grounding for safety purposes. An additional grounding point is located on the outside of the product. The ground conductor should be at least 4mm². If it can be assumed that the grounding protection is damaged, the product should be taken out of operation and prevented from accidentally being put into operation again; contact qualified maintenance personnel Ensure that the connection cables are provided with fuses and circuit breakers. Never replace a protective device with a component of a different type. Refer to the manual for the correct part.
  • Do not invert neutral and phase when connecting the AC.
  • Check before switching the device whether the available voltage source conforms to the configuration settings of the product as described in the manual.
  • Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet or dusty environment. Ensure that there is always sufficient free space around the product for ventilation, and those ventilation openings are not blocked. Install the product in a heatproof environment. Ensure, therefore, that there are no chemicals, plastic parts, curtains or other textiles, etc. near the equipment.
  • This inverter is provided with an internal isolation transformer providing reinforced insulation.

Transport and storage

  • On storage or transport of the product, ensure that the main supply and battery leads are disconnected.
  • No liability can be accepted for damage in transit if the equipment is not transported in its original packaging.
  • Store the product in a dry environment; the storage temperature should range from -40 °C and 70 °C.

Symbols on enclosure

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(1\)

Description

General

  • Multifunctional
    • The Multi gets its name from the multiple functions it can perform.
    • It is a powerful true sine wave inverter, a sophisticated battery charger that features adaptive charge technology and a high-speed AC transfer switch in a single enclosure.
    • Besides these primary functions, however, the Multi has several advanced features that provide a range of new applications, as outlined below.
  • Uninterrupted AC power
    • In the event of a grid failure or shore or generator power being disconnected, the inverter within the Multi is automatically activated and takes over the supply to the connected loads.
    • This happens so fast (less than 20 milliseconds) that computers and other electronic equipment will continue to operate without disruption.
  • Parallel and 3-phase operation capability
    • Up to 6 inverters can operate in parallel to achieve higher power output. Operation in a 3-phase configuration is also possible.
  • PowerControl – Dealing with a limited generator or shoreside power
    • With a Digital Multi Control panel a maximum generator or shore current can be set.
    • The Multi will then take account of other AC loads and use whatever is extra for charging, thus preventing the generator or shore supply from being overloaded.
  • Programmable relay
    • The Multi is equipped with a programmable relay that, by default, is set as an alarm relay.
    • The relay can be programmed for all kinds of other applications, however, for example, as a starter relay for a generator.

Battery charger

  • Adaptive 4-stage charging characteristics: bulk – absorption – float – storage

    • The microprocessor-driven adaptive battery management system can be adjusted for various types of batteries. The adaptive function automatically adapts the charging process to battery use.
  • The right amount of charge: variable absorption time

    • In the event of slight battery discharge, absorption is kept short to prevent overcharging and excessive gas formation. After deep discharging, the absorption time is automatically extended in order to fully charge the battery.
  • Preventing damage due to excessive gassing: The BatterySafe mode

    • If, to quickly charge a battery, a high charge current in combination with a high absorption voltage has been chosen, damage due to excessive gassing will be prevented by automatically limiting the rate of voltage increase once the gassing voltage has been reached.
  • Less maintenance and aging when the battery is not in use: The storage mode

    • The Storage mode kicks in whenever the battery has not been subjected to discharge for 24 hours. In the Storage mode, float voltage is reduced to 2.2V/cell (13.2V for 12V battery) to minimise gassing and corrosion of the positive plates. Once a week, the voltage is raised back to the absorption level to “equalise’ the battery. This feature prevents stratification of the electrolyte and sulphation, a major cause of early battery failure.
  • Two DC outputs for charging two batteries

    • The main DC terminal can supply the full output current. The second output, intended for charging a starter battery, is limited to 1 A and has a slightly lower output voltage.
  • Increasing service life of the battery: temperature compensation

    • The temperature sensor (supplied with the product) serves to reduce charging voltage when the battery temperature rises. This is particularly important for maintenance-free batteries, which could otherwise dry out by overcharging.
  • More on batteries and charging

  • Self-consumption – solar energy storage systems

    • When the Multi is used in a configuration in which it will feed back energy to the grid, it is required to enable grid code compliance by selecting the grid code country setting with the VEConfigure tool.
    • Once set, a password will be required to disable the grid code compliance or change grid code-related parameters. If the local grid code is not supported by the Multi, an external certified interface device should be used to connect the Multi to the grid.

Operation

On/Off/Charger-only switch

  • When switched to “on”, the product is fully functional. The inverter will come into operation and the LED “inverter on” will light up.
  • An AC voltage connected to the “AC in” terminal will be switched through to the “AC out” terminal, if within specifications. The inverter will switch off, the “Charger” LED will light up and the charger commences charging. If the voltage at the “AC-in” terminal is not within specifications, the inverter will switch on.
  • When the switch is switched to “charger only”, only the battery charger of the Multi will operate (if mains voltage is present). In this mode input also is switched through to the “AC out” terminal.
  • NOTE: When only the charger function is required, ensure that the switch is switched to “charger only”. This prevents the inverter from being switched on if the mains voltage is lost, thus preventing the batteries from running flat.

LED indications

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(2\)

Note: The inverter/charger will shut down if four abnormal events occur within 30 seconds. It can be reset by switching to Off and then to On again.

For the latest and most up-to-date information about the blink codes, please refer to the Victron Toolkit app. Scan the QR code or click on the below link to go to the Victron software downloads webpage. https://www.victronenergy.com/support-and-downloads/software.

Remote control

  • Remote control is possible with a 3-position switch or with a Digital Multi Control panel.
  • The control panel has a simple rotary knob with which the maximum current of the AC input can be set: see Power Control in the General [4] chapter.
  • For the appropriate DIP switch settings, refer to the Configuration by DIP switches [16] chapter.

Maintenance

The Multi does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture and oil/soot/ vapours and keep the device clean.

Installation

  • This product may only be installed by a qualified engineer.
  • Each system requires a method of disconnecting the AC and DC circuits. If the overcurrent protection device is a circuit breaker, it will also serve as the disconnect. If fuses are used, separate disconnect switches will be needed between the source and the fuses.
  • To reduce the risk of fire, do not connect to an AC load centre (circuit breaker panel) having multiwire branch circuits connected.
  • To reduce the risk of injury, charge only Lead Acid or LIFEPO4-type rechargeable batteries. Other types of batteries may burst causing personal injury and damage. Do not try to recharge non-rechargeable batteries.
  • Use of an attachment not recommended or sold by the marine unit manufacturer may result in a risk of fire, electric shock, or injury to persons.
  • DC CONNECTION PRECAUTIONS – Connect and disconnect DC output connections only after setting any marine unit switches to the off position and removing the AC cord from the electric outlet or opening the AC disconnect.
  • EXTERNAL CONNECTIONS TO CHARGER SHALL COMPLY WITH THE UNITED STATES COAST GUARD ELECTRICAL REGULATIONS (33CFR183, SUBPART I). GROUNDING INSTRUCTIONS – This marine unit should be connected to a grounded, metal, permanent wiring system; or an equipment-grounding conductor should be run with circuit conductors and connected to an equipment-grounding terminal or lead-on unit. Connections to units should comply with all local codes and ordinances
  • This product is not suitable for direct connection to a vehicle’s electrical system. It should be connected to a dedicated DC system that includes a dedicated service or house battery, appropriate fusing, and the appropriate gauge of DC wiring. For recommendations on battery capacity, fuse rating, and cable gauge, refer to the Battery Connection [9] chapter in this manual.
  • WARNING – RISK OF EXPLOSIVE GASES) WORKING IN THE VICINITY OF A LEAD-ACID BATTERY IS DANGEROUS. BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION. FOR THIS REASON, IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING THE UNIT IN THE VICINITY OF THEBATTERY, YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY.

PERSONAL PRECAUTIONS:

  • Someone should be within range of your voice or close enough to come to your aid when you work near a lead-acid battery
  • Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes.
  • Wear complete eye protection and clothing protection. Avoid touching your eyes while working near the battery.
  • If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters the eye, immediately flood the eye with running cold water for at least 10 min and get medical attention immediately.
  • NEVER smoke or allow a spark or flame in the vicinity of the battery or engine.
  • Be extra cautious to reduce the risk of dropping a metal tool onto the battery. It might spark or short-circuit the battery or other electrical parts which may cause an explosion.
  • Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a lead-acid battery. A lead-acid battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn.
  • NEVER charge a frozen battery.
  • If necessary to remove the battery from the vessel, always remove the grounded terminal from the battery first. Make sure all accessories in the vessels are off, so as not to cause an arc.
  • Be sure the area around the battery is well-ventilated. Clean battery terminals. Be careful to keep corrosion from coming in contact with eyes. Study all battery manufacturer’s specific precautions such as removing or not removing cell caps while charging and recommended rates of charge.
  • Clean battery terminals. Be careful to keep corrosion from coming in contact with eyes.
  • Study all battery manufacturer’s specific precautions such as removing or not removing cell caps while charging and recommended rates of charge.

location
The product must be installed in a dry, well-ventilated and heatproof area.

  • For safety purposes, this product should be installed in a heat-resistant environment. You should prevent the presence of e.g. chemicals, synthetic components, curtains or other textiles, etc., in the immediate vicinity.
  • There should be a clear space of at least 10cm around the appliance for cooling.
  • Excessively high ambient temperature will result in the following:
    • Reduced service life.
    • Reduced charging current.
    • Reduced peak capacity, or shutdown of the inverter.
  • Try to keep the distance between the product and the battery to a minimum to minimise cable voltage losses.
  • Never position the appliance directly above the batteries.
  • For the location of the mounting holes, see the Dimension drawings [26] chapter.

MARINE UNIT LOCATION

  • Locate marine unit away from the battery in a separate, well-ventilated compartment
  • Never place the marine unit directly above the battery; gases from the battery will corrode and damage the marine unit.
  • Never allow battery acid to drip on the marine unit when reading gravity or filling the battery.
  • Do not operate the marine unit in a closed-in area or restrict ventilation in any way.

Battery connection

For optimal performance, use batteries with a suitable capacity and cables with sufficient cross-section, as indicated in the below table:

Inverter/charger| Recommended battery capacity (Ah)| Recommended cable cross-section (mm²) For cables between 1.5 and 5m
---|---|---
12/500/20| 60 – 300| 16
12/1200/50| 150 – 700| 35

Battery connection procedure

  • Use an insulated box spanner to avoid shorting the battery terminals.
  • Avoid shorting the battery cables.
  1. Confirm battery cable polarity before connection. A reverse polarity connection will cause damage to the product (the safety fuse inside the Multi can be damaged).
  2. Connect battery cables to the Multi and the battery, see the Connection overview [22] chapter. Use a PZ 2 screwdriver for the 500VA unit and a flat screwdriver 6.5mm for the 1200VA unit.

Internal DC fuses
All servicing must be undertaken by qualified personnel.

Inverter/charger Fuse type Fuse value (A)
12/500/20 MIDI or BF1 fuse 32V 125 – 60
12/1200/50 MIDI or BF1 fuse 32V 200 – 100

AC connection

This product is a safety class I product (supplied with a ground terminal for safety purposes). Its AC input and/or output terminals and/or grounding point on the outside of the product must be provided with an uninterruptible grounding point for safety purposes. The Multi is provided with a ground relay, see the Internal wiring diagram [23] chapter, that automatically connects the Neutral output to the chassis if no external AC supply is available. If an external AC supply is provided, the ground relay H will open before the input safety relay closes. This ensures the correct operation of an earth leakage circuit breaker that is connected to the output.

  • In a fixed installation, uninterruptable grounding can be secured by means of the grounding wire of the AC input. Otherwise, the casing must be grounded.
  • In a mobile installation, interrupting the shore connection will simultaneously disconnect the grounding connection. In that case, the casing must be connected to the chassis (of the vehicle) or to the hull or grounding plate (of the boat).
  • In the case of a boat, direct connection to the shore ground is not recommended because of potential galvanic corrosion. The solution to this is using an isolation transformer.
  • The AC input and output terminal connectors can be found at the bottom of the Multi, see the Connection overview [22] chapter.
  • The shore or mains cable must be connected to the connector with a three-wire cable. Use a three-wire cable with a flexible core and a cross-section of at least 1.5 mm²
  • The inverter does incorporate a mains frequency isolating transformer. This precludes the possibility of DC current at any AC port.
  • Therefore, type A RCDs can be used.

AC connection procedure
Proceed as follows to connect the AC cables:

  1. The AC output cable can be connected directly to the male connector (the connector pulls out).
  2. The terminal points are indicated clearly. From left to right: neutral (N), earth (PE), and phase (L1).
  3. The AC input cable can be connected directly to the female connector (the connector pulls out).
  4. The terminal points are indicated clearly. From left to right: neutral (N), earth (PE), and phase (L1).
  5. Push the “input” connector into the AC-in connector.
  6. Push the “output” connector into the AC-out connector.

Optional connections

  • Several optional connections are possible:

Second battery

  • The Multi has a connection (+) for charging a starter battery. For connection see the Connection overview [22]chapter.
  • The trickle charge output is protected by automatic overcurrent and overload protection (trip current=1A Imax= 5.5 A).

Temperature sensor

  • The temperature sensor supplied with the product may be used for temperature-compensated charging. The sensor is insulated and must be mounted on the battery minus pole.
  • Default output voltages for Float and Absorption are at 25 °C. In adjust mode temperature compensation is disabled.

Remote control

  • The product can be remotely controlled in two ways:
    • With an external 3-position switch
    • With a Multi Control Panel
  • Please see the Configuration by DIP switches [16] chapter for appropriate DIP switch settings

Programmable relay

  • The Multi is equipped with a multi-functional relay that by default is programmed as an alarm relay.
  • The relay can be programmed for all kinds of other applications, for example, to start a generator (VEConfigure software or VictronConenct app needed).

Parallel connection

The MultiPlus can be connected in parallel with several identical devices. To this end, a connection is established between the devices using standard RJ45 UTP cables. The system (one or more MultiPlus units plus an optional control panel) will require subsequent configuration, see the Configuration [13] chapter.
In the event of connecting MultiPlus units in parallel, the following requirements must be met:

  • A maximum of six units can be connected in parallel.
  • Only identical devices may be connected in parallel.
  • The DC connection cables to the devices must be of equal length and cross-section.
  • If a positive and a negative DC distribution point is used, the cross-section of the connection between the batteries and the DC distribution point must at least equal the sum of the required cross-sections of the connections between the distribution point and the MultiPlus units.
  • Place the MultiPlus units close to each other, but allow at least 10 cm for ventilation purposes under, above and beside the units.
  • UTP cables must be connected with an RJ45-splitter from one unit to the other (and to the remote panel).
  • A battery-temperature sensor need only be connected to one unit in the system. If the temperature of several batteries is to be measured, you can also connect the sensors of other MultiPlus units in the system (with a maximum of one sensor per MultiPlus). Temperature compensation during battery charging responds to the sensor indicating the highest temperature.
  • Only one means of remote control (panel or switch) can be connected to the system. victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1 \(4\)

Three-phase connection
The MultiPlus can also be used in a 3-phase wye (Y) configuration. To this end, a connection between the devices is made using standard RJ45 UTP cables and RJ45-splitter splitter (the same as for parallel operation). The system (MultiPlus units plus an optional control panel) will require subsequent configuration, see the Configuration [13] chapter. For the prerequisites see the previous Parallel connection [11] chapter.
Note: The MultiPlus is not suitable for a 3-phase delta (Δ) configuration.

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(5\)

Configuration

  • Settings may only be changed by a qualified engineer.
  • Carefully read the instructions before changes are made.
  • Batteries should be placed in a dry and well-ventilated area during charging.

Standard settings: ready for use
On delivery, the Multi is set to standard factory values. In general, these settings are suitable for single-unit operation.
Warning: The standard charging voltage might not be appropriate for your batteries. Consult the manufacturer’s documentation or your battery supplier for guidance.

Setting Default value
Inverter frequency 60 Hz
Input frequency range 45 – 65 Hz
Input voltage range 94 – 143 VAC
Inverter voltage 120 VAC
Stand-alone/parallel / 3-phase stand-alone
Search mode off
Ground relay on
Charger on/off on
Battery charge algorithm four-stage adaptive withBatterySafe mode
Charge current 100 % of the maximum charge current
Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep

Discharge)
Automatic equalisation charging| off
Absorption voltage| 14.4V
Absorption time| up to 8 hours (depending on bulk time)
Float voltage| 13.8V
Storage voltage| 13.2V (not adjustable)
Repeated absorption time| 1 hour
Absorption repeat interval| 7 days
Bulk protection| off
AC input current limit| 12A (= adjustable current limit for PowerControl andPowerAssist functions)
UPS feature on| on
Dynamic current limiter off| off
Weak AC| off
Boost factor| 2
Programmable relay| alarm function

Explanations of settings

  • Settings that are not self-explanatory are described briefly below.
  • For further information on these settings, refer to the help files in the software configuration programs as indicated in the next Configuration by Computer [15] chapter.

Inverter frequency

  • Output frequency if no AC is present at the input.
  • Adjustability: 50 Hz; 60 Hz

Input frequency range

Input frequency range accepted by the Multi. The Multi synchronises within this range with the AC input frequency. The output frequency is then equal to the input frequency.

  • Adjustability: 45 – 65 Hz.

Inverter voltage

  • Output voltage of the Multi in battery operation.
  • Adjustability: 95-128V.

Input voltage range
Voltage range accepted by the Multi. The Multi synchronises within this range with the AC input voltage. The output voltage is then equal to the input voltage.
Adjustability:

  • Lower limit: 94 – 120V
  • Upper limit: 120 – 143 V

Stand-alone/parallel operation / 2-3 phase setting Using several devices, it is possible to:

  • Increase total inverter power (several devices in parallel).
  • Create a split-phase system.
  • create a 3-phase system.

The standard product settings are for standalone operation. For parallel, or three phase operation see the Parallel connection [11] and Three-phase connection [11] chapters.

Search mode
If search mode is “on”, the power consumption in no-load operation is decreased by approx. 70 %. In this mode the Multi, when operating in inverter mode, is switched off in case of no load or very low load, and switches on every two seconds for a short period. If the output current exceeds a set level, the inverter will continue to operate. If not, the inverter will shut down again.

  • Search Mode can be set with a DIP switch.
  • Search Mode “shut down” and “remain on” load levels can be set with VEConfigure. The standard settings are:
  • Shut down: 30 Watt (linear load)
  • Turn on: 60 Watt (linear load)

AES (Automatic Economy Switch)

  • Instead of the search mode, the AES mode can also be chosen (with the help of VEConfigure only).
  • If this setting is turned “on”, the power consumption in no-load operation and with low loads is decreased by approx. 20 %, by slightly “narrowing” the sinusoidal voltage

Ground relay

  • With this relay the neutral conductor of the AC output is grounded to the chassis when the back-feed safety relay is open (See chapter Internal wiring diagram [23], item H).
  • This ensures the correct operation of earth leakage circuit breakers in the output.
  • If a non-grounded output is required during inverter operation, this function must be turned off (use VE-Configure or the VictronConnect app).

Charge curve

  • The standard setting is “Four-stage adaptive with BatterySafe mode”. See chapter Battery Charger [4] for a description.
  • This is the recommended charge curve. See the help files in the software configuration programs for other features.

Battery type

  • The standard setting is the most suitable for Victron Gel Deep Discharge, Gel Exide A200, and tubular plate stationary batteries (OPzS). This setting can also be used for many other batteries: e.g.
  • Victron AGM Deep Discharge and other AGM batteries, and many types of flat-plate flooded batteries. Four charging voltages can be set with DIP switches.

Automatic equalisation charging

  • This setting is intended for tubular plate traction batteries.
  • During absorption, the voltage limit increases to 2.83 V/cell.
  • Once the charge current has tapered down to less than 10 % of the set maximum current.

Absorption time

  • The absorption time depends on the bulk time (adaptive charge curve) so that the battery is optimally charged.
  • If the “fixed” charging characteristic is selected, the absorption time is fixed.
  • For most batteries, a maximum absorption time of eight hours is suitable.
  • If an extra high absorption voltage is selected for rapid charging (only possible for open, flooded batteries!), four hours is preferable.
  • With DIP switches, a time of eight or four hours can be set. For the adaptive charge curve, this determines the maximum absorption time.
  • Storage voltage, Repeated Absorption Time, Absorption Repeat Interval See the Battery charger [4] chapter.

Bulk Protection

  • Default setting: off. When this setting is “on”, the bulk charging time is limited to 10 hours. A longer charging time could indicate a system error (e.g. a battery cell short-circuit).

AC input current limit

  • These are the current limit settings at which PowerControl and PowerAssist come into operation. The factory setting is 12A.

UPS feature

  • If this setting is “on” and AC on the input fails, the Multi switches to inverter operation practically without interruption. The Multi can therefore be used as an Uninterruptible Power Supply (UPS) for sensitive equipment such as computers or communication systems.
  • The output voltage of some small generator sets is too unstable and distorted for using this setting* – the Multi would continually switch to inverter operation. For this reason, the setting can be turned off.
  • The Multi will then respond less quickly to AC input voltage deviations. The switchover time to inverter operation is consequently slightly longer, but most equipment (most computers, clocks or household equipment) is not adversely impacted.
  • Recommendation: Turn the UPS feature off if the Multi fails to synchronise, or continually switches back to inverter operation.
  • In general, the UPS setting can be left “on” if the Multi is connected to a generator with a “synchronous AVR regulated alternator”.
  • The UPS mode may have to be set to “off” if the Multi is connected to a generator with a “synchronous capacitor regulated alternator” or an asynchronous alternator.

Dynamic current limiter

  • Intended for generators, the AC voltage is generated using a static inverter (so-called “inverter” generator). In these generators, rpm is down-controlled if the load is low: this reduces noise, fuel consumption and pollution. A disadvantage is that the output voltage will drop severely or even completely fail in the event of a sudden load increase. More load can only be supplied after the engine is up to speed.
  • If this setting is “on”, the Multi will reduce the charge current until the set current limit is reached. This allows the generator engine to get up to speed. This setting is also often used for “classic” generators that respond slowly to sudden load variation.

Weak AC

  • Strong distortion of the input voltage can result in the charger hardly operating or not operating at all. If Weak AC is set, the charger will also accept a strongly distorted voltage, at the cost of greater distortion of the input current.
  • Recommendation: Turn the Weak AC on if the charger is hardly charging or not charging at all (which is quite rare!). Also, turn on the dynamic current limiter simultaneously and reduce the maximum charging current to prevent overloading the generator if necessary.

BoostFactor

  • Change this setting only after consulting with Victron Energy or with an engineer trained by Victron Energy!

Programmable relay

  • By default, the programmable relay is set as an alarm relay, i.e. the relay will de-energise in the event of an alarm or a pre-alarm (inverter almost too hot, ripple on the input almost too high, battery voltage almost too low).
  • With VEConfigure software or the VictronConenct app, the relay can also be programmed for other purposes, for example, to provide a generator starting signal.

Configuration by computer
All settings can be changed using a phone, tablet or computer.

The following is required:

  • The VictronConnect app or the VEConfigure3 software package. Both can be downloaded free of charge from the downloads section on www.victronenergy.com.
  • An Interface MK3-USB and a RJ45 UTP cable.
  • Refer to the VictronConnect configuration guide for VE. Bus products document for further instructions and further explanation of the various settings.
  • Note that some settings can also be changed with DIP switches (see the next Configuration by DIP switches [16] chapter).

Configuration by DIP switches
Some settings can be changed with DIP switches.
Procedure:

  1. Turn the Multi on, preferably without load and without AC voltage on the input. The Multi will then operate in inverter mode.
  2. Set the DIP switches as required.
  3. Store the settings by moving DIP switch 6 to “on” and back to “off”.

DIP switch 1

  • Default setting: to operate the product with the “On/Off/Charger Only” switch ds 1: “off” When combined with the Digital Multi Control panel, a VE.
    Bus Smart dongle, CCGX, Venus GX or alike, DIP switch 1 should also be in the “off” position. Setting for operation with a 3-position remote switch: ds 1: “on” The 3-position switch must be wired to terminal H, see appendix A.

  • Use only one type of remote control: either a switch or a Digital Multi Control panel.

DIP switch 2 and 3 These DIP switches can be used to set:

  • Battery charge voltage and Absorption time
  • Inverter frequency
  • Search mode

(For more system settings, use VEConfigure or the VictronConnect app)

DS 2 – DS 3| Absorption voltage (V)| Float voltage (V)| Storage Voltage (V)| Absorption Time (hours)| Suitable battery types
---|---|---|---|---|---
DS 2=off DS 3=off

(default)

| 14.4| 13.8| 13.2| 8| Gel Victron deep discharge Gel Exide A200

AGM Victron deep discharge

 |  |  |  |  | Gel Victron Long Life (OPzV)
DS 2=on DS 3=off| 14.1| 13.8| 13.2| 8| Long Life (OPzV)

Gel Exide A600 (OPzV) Gel MK battery

 |  |  |  |  | Li-ion (LiFePO4)
 |  |  |  |  | AGM Victron deep discharge
DS 2=off

DS =on

| 14.7| 13.8| 13.2| 5| Tubular plate or OPzS batteries in semi-float mode
 |  |  |  |  | AGM spiral cell

Dip switch 4

  • Inverter frequency off = 50 Hz on = 60 Hz

Dip switch 5

  • Search Mode off = off on = on
  • Store the settings by moving DIP switch 6 to “on” and back to “off”.

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(13\)

Example 1 is the factory setting (since factory settings are entered by the computer, all DIP switches of a new product are set to “off”). Store the settings by changing switch DS-6 from off to on, and then back to off. The LEDs “charger” and “alarm” will flash to indicate acceptance of the settings.

Troubleshooting

Proceed as follows for quick detection of common faults. DC loads must be disconnected from the batteries and the AC loads must be disconnected from the inverter before the inverter and/or battery charger is tested. Consult your Victron Energy dealer if the fault cannot be resolved.

Problem Cause Solution
The inverter fails to operate when switched on The battery voltage is too
high or too low Ensure that the battery voltage is within the correct value.
The inverter fails to operate Processor in no function-mode Disconnect mains

voltage. Switch the front switch off, and wait 4 seconds. Switch the front switch on.
The alarm LED flashes| Pre-alarm alternative 1:

The DC input voltage is low

| Charge the battery or check the battery connections.
The alarm LED flashes| Pre-alarm alternative 2:

The ambient temperature is too high

| Place the inverter in a cool and well-ventilated room or reduce the load.
The alarm LED flashes| Pre-alarm alternative 3:

The load on the inverter is higher than the nominal load

| Reduce the load.
The alarm LED flashes| Pre-alarm alternative 4:

Voltage ripple on the DC input exceeds 1.25Vrms

| Check the battery cables and terminals. Check the battery capacity; increase if necessary.
The alarm LED flashes intermittently| Pre-alarm alternative 5:

Low battery voltage and excessive load

| Charge the batteries, reduce the load or install batteries with a higher capacity. Use shorter and/or thicker battery cables.
The alarm LED is on| The inverter did cut out following a pre-alarm| Check the table for the appropriate course of action.
The charger is not functioning| The AC input voltage or frequency is out of range| Ensure that the input voltage is between 185 VAC and 265 VAC and that the frequency matches the setting.
The battery is not being charged fully| Incorrect charging current| Set the charging current at between 0.1 and 0.2x battery capacity.
A defective battery connection| Check the battery terminals.
The absorption voltage has been set to an incorrect value| Adjust the absorption voltage to the correct value.
The float voltage has been set to an incorrect value| Adjust the float voltage to the correct value.
The internal DC fuse is defective| Inverter is damaged
The battery is overcharged| The absorption voltage has been set to an incorrect value| Adjust the absorption voltage to the correct value
The float voltage has been set to an incorrect value| Adjust the float voltage to the correct value.
A defective battery| Replace the battery.
The battery is too small| Reduce the charging current or use a battery with a higher capacity.
The battery is too hot| Connect a temperature sensor.
Battery charge current drops to 0 when the absorption voltage is reached| Alternative 1: Battery overtemperature (>50 °C)| Allow battery to cool down – Place battery in a cool environment – Check for shorted cells
Problem| Cause| Solution
---|---|---
 | Alternative 2: The battery temperature sensor is faulty| Unplug the battery temperature sensor from the Multi. Reset the Multi by switching it off, then wait for 4 seconds and switch it on again. If the Multi now charges normally, the battery temperature sensor is faulty and needs to be replaced.

Technical data

Technical specifications

  MultiPlus 12/500/20 – 120Vac Multiplus 12/1200/50 – 120Vac
PowerControl / PowerAssist Yes / No Yes / Yes
Transfer switch 16A

INVERTER
Input voltage range| 9.5 – 17Vdc
Output voltage| 120Vac ± 2%
Output frequency(1)| 60Hz ± 0,1%
Cont. output power at 25°C (77°F) (3)| 500VA| 1200VA
Cont. output power at 25°C (77°F)| 430W| 1000W
Cont. output power at 40°C (104°F)| 400W| 900W
Cont. output power at 65°C (149°F)| 300W| 600W
Peak power| 900W| 2400W
Maximum efficiency| 90%| 93%
Zero-load power| 6W| 10W
Zero-load power search mode| 2W| 3W
CHARGER
AC Input voltage range| 95 – 140Vac
AC input frequency range| 45 – 65Hz
Charge voltage ‘absorption’| 14.4V
Charge voltage ‘float’| 13.8V
Storage mode| 13.2V
Charge current house battery (4)| 20A| 50A
Charge current starter battery| 1A
Battery temperature sensor| Yes
GENERAL
Programmable relay (5)| Yes
Protection (2)| a – g
Operating temperature| -40 to +65°C (-40 to + 140°F), fan assisted cooling
Humidity| Maximum 95%, non-condensing
ENCLOSURE
Material & colour| Steel/ABS, blue RAL 5012
Protection category| IP 21
Battery-connection| 16 mm²| 35 mm²
230V AC-connection| G-ST18i connector
Weight| 4.4kg| 8.2kg
Dimensions (h x w x d)| 311 x 182 x 100 mm| 406 x 250 x 100 mm
STANDARDS
Safety| EN-IEC 60335-1, EN-IEC 60335-2-29, EN 62109-1


Emission / Immunity

| EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3

IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3

  MultiPlus 12/500/20 – 120Vac Multiplus 12/1200/50 – 120Vac
Road vehicles ECE R10-4
  1. Can be adjusted to 50Hz                  3) Non-linear load, crest factor 3:1

  2. Protection                                        4) Up to 25°C (77°F) ambient

a. Output short circuit                           5) Programmable relay which can be set for:

b. Overload                                          • general alarm, DC under voltage or generator start/stop signal function

c. Battery voltage too high                   • AC rating: 230V/4A

d. Battery voltage too low

•  DC rating: 4A up to 35Vdc, 1A up to 60Vdc

e. Temperature too high

f. 120Vac on inverter output

g. Input voltage ripple too high

Connection overview

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(7\)

ID Description
A DIP switches (remove plastic cover)
B On/off/charger only switch
C VE.Bus communication port
D Temperature sensor terminal
E Programmable relay terminal
F Battery negative connection
G Starter battery positive connection
H Remote control terminal
I AC input terminal (N, PE, L1)
J AC output terminal (N, PE, L1)
K Battery positive
L Earth connection

Internal wiring diagram

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(8\)

ID Description
D AC input (L, N, PE).
E AC output (L, N, PE).
F Ground AC input and AC output are connected to the chassis.
G Back feed safety relay.
H Ground relay (closed when the back feed relay is open).
I DC fuse.
J Bidirectional converter.
K The chassis on input/output ground terminals should be permanently

connected to the ground.

Four-stage charge algorithm

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(9\)

charge stage Description
Bulk Entered when charger is started. Constant current is applied until the

gassing voltage is reached (14,4 V resp. 28.8V, temperature compensated).
Battery safe| If, in order to quickly charge a battery, a high charge current in combination with a high absorption voltage has been chosen, the Multi will prevent damage due to excessive gassing by automatically limiting the rate of voltage increase once the gassing voltage has been reached. The Battery Safe period is part of the calculated absorption time.
Absorption| A constant voltage period to fully charge the battery. The absorption time is equal to 20x bulk time or the set maximum absorption time, whichever comes first.
Float| Float voltage is applied to keep the battery fully charged and to protect it against self-discharge.
Storage| After one day of Float charge the charger switches to storage. This is 13,2 V resp. 26,4 V (for 12 V and 24 V charger). This will limit water loss to a minimum. After an adjustable time (default = 7 days) the charger will enter Repeated Absorption for an adjustable time (default = 1 hour).

Temperature compensation charge chart

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1
\(10\)

  • Default output voltages for Float and Absorption are at 25 °C.
  • Reduced Float voltage follows Float voltage and Raised Absorption voltage follows Absorption voltage.
  • In adjust mode temperature compensation does not apply.

Dimension drawings

Multiplus 12/500/20 – 120V

victron-energy-12-500-20-120V-Multi-Plus-Charger-FIG-1