Danfoss Optyma G & D HBP Condensing Inverter Owner’s Manual
- June 1, 2024
- Danfoss
Table of Contents
- Danfoss Optyma G & D HBP Condensing Inverter
- Designation system
- Introduction
- Handling and storage
- Installation precautions
- Installation
- Leak detection
- Vacuum dehydration
- Electrical connections
- Filling the system
- Verification before commissioning
- Start-up
- Check with running unit
- Maintenance
- Warranty
- Disposal
- Instructions
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Danfoss Optyma G & D HBP Condensing Inverter
Specifications
- Model: OptymaTM G & D HBP
- Design: Air cooled condenser, Twin fan, Scroll compressor
- Refrigerant: R410A/R454B/R452B
- Unit Sizes: 1/3 HP to 10 HP
- Voltage Options:
- N = Compressor 230V/1ph/60Hz, Fan(s) 230V/1ph/60Hz
- Q = Compressor 230V/3ph/60Hz, Fan(s) 230V/1ph/60Hz
- R = Compressor 460V/3ph/60Hz, Fan(s) 460V/3ph/60Hz
Warnings
- Use the condensing unit only for its designed purpose and within its scope of application.
- Ensure compliance with safety regulations like ASHRAE15 or UL60335.
- Installation and servicing should be done by qualified personnel following sound refrigeration engineering practices.
- Do not place the unit in a flammable atmosphere.
Installation
- Ensure proper oil return for the compressor and prevent liquid slug over in the compressor.
- Connect the condensing unit to an appliance suitable for the same refrigerant.
- Check for leaks and ensure all connections are secure before opening valves.
Maintenance
- Switch off the unit at the main switch before removing fan panel.
- Perform periodic service inspections to ensure system reliability as per local regulations.
- Clean the condenser annually to prevent clogging, especially microchannel coils.
- If refrigerant system is opened, flush with dry air or nitrogen and install a new filter drier.
FAQ
Q: How often should the condenser be checked for clogging?
A: The condenser must be checked at least once a year forclogging and cleaned
if necessary.
Instructions
Optyma™ G & D HBP
HLH061 OP-HRSM0500N C0217N / C0218Q / C0219R DSH105 OP-HRSM0750N C0213Q /
C0214R
DSH140 OP-HRSM1000N C0215Q / C0216R
Designation system
1| Application
H = HBP/Universal
---|---
2| Design
R = Air cooled condenser, Twin fan, Scroll compressor
3| Refrigerant
S = R410A/R454B/R452B
4| Condenser
M = Microchannel condenser size 100°F Max Ambient
5| Unit SIze (Nominal HP)
HP rating in hundredths of HP, i.e.: 0033=1/3 HP, 1000 = 10HP
6| Version
NCXXXX = Customer specific unit with unique identification Number
7| Voltage code
N = Compressor 230V/1ph/60Hz, Fan(s) 230V/1ph/60Hz Q = Compressor 230V/3ph/60Hz, Fan(s) 230V/1ph/60Hz R = Compressor 460V/3ph/60Hz, Fan(s) 460V/3ph/60Hz
Warnings
The condensing unit must only be used for its designed purpose(s) and within its scope of application.
Under all circumstances, the ASHRAE15 or UL60335 (or other applicable local
safety regulation) requirements must be fulfilled.
The condensing unit is delivered under nitrogen gas pressure (1 bar) and hence
it cannot be connected as it is; refer to the «installation» section for
further details. It does not contain refrigerant on delivery.
The condensing unit must be handled with cau- tion in the vertical posi- tion
(maximum offset from the vertical: 15°)
Installation and servicing of the condensing units by qualified personnel
only. Follow these instructions and sound refrigeration engineering prac- tice
relating to installation, commissioning, maintenance and service.
This product is intended use inside of Outdoor End-Product as
Air-Cooled Chillers. Any different Application shall be according with
UL Standard or Compliance with National Regulations. The installation of the condensing unit in a refrigeration system is the responsibility of the system designer
Introduction
These instructions pertain to Optyma G&D HBP HLH061, DSH105 & DSH140
condensing units (R410A/R452B/R454B) used for refrigeration systems. They
provide necessary information regarding safety and proper usage of this
product.
Note: These HRSM0500N models are only qualified to use R410A and R454B
refrigerant. The condensing unit includes following:
- Scroll compressor
- Microchannel heat exchanger
- Fix low Pressure cartridge
- Fix high Pressures cartridge
- EC Fan Motor
- Stop Valves Suction/ Liquid
- Heater for Compressor
- Receiver Vessel
- Accumulator Vessel
- Check Valve in Discharger Pipe
Handling and storage
- It is recommended not to open the packaging before the unit is at the final place for installation.
- Handle the unit with care. The packaging allows for the use of a forklift or pallet jack. Use appropriate and safe lifting equipment.
- Store and transport the unit in an upright position.
- Don’t expose the packaging to rain orcorrosive atmosphere.
- Store the unit between -31°F to 122°F (-35°C to 50°C).
- After unpacking, check that the unit is complete and undamaged.
Installation precautions
- Do not braze as long the condensing unit is under pressure.
- A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts.
- Never place the unit in a flammable atmosphere.
- Place the unit in such a way that it is not blocking or hindering walking areas, doors, windows or similar.
- The installation instructions shall be installed in accordance with the Safety Standard for Refrigeration Systems, ANSI/ASHRAE 15 or Compliance with National Regulations.
- The Installation shall include protection from physical damage in operation and service and be in compliance with national and local codes and standards, such as ANSI/ASHRAE 15, IAPMO Uniform Mechanical Code, ICC International Mechanical Code, or CSA B52.
- All field joints shall be accessible for inspection prior to being covered or enclosed.
- Ensure adequate space around the unit for air circulation and to open doors. Refer to picture 1 for minimal values of distance to walls, for End-Products.
- Avoid installing the unit in locations which are daily exposed to direct sunshine for longer periods.
- Avoid installing the unit in aggressive and dusty environments.
- Ensure a foundation with horizontal surface (less than 3° slope), strong and stable enough to carry the entire unit weight and to eliminate vibrations and interference.
- The unit ambient temperature may not exceed 122°F (50°C) during off cycle.
- Ensure that the power supply corresponds to the unit characteristics (see nameplate).
- When installing units for HFO refrigerants, use equipment specifically reserved for HFO refrigerants which was never used for CFC or HCFC refrigerants.
- Use clean and dehydrated refrigeration grade copper tubes and silver alloy brazing material.
- Use clean and dehydrated system components.
- The suction piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations. Furthermore, piping has to be done in such a way that oil return for the compressor is ensured and the risk of liquid slug over in compressor is eliminated.
| Unit| W| X| Y| Z
---|---|---|---|---|---
Housing
| In| 10| 30| 23| 23
mm| 250| 760| 581| 581
Installation
- This product is to be installed in accordance with the requirements in ANSI/ASHRAE 15 or Compliance with National Regulations. The condensing unit itself is not a “unit” in the scope this directive.
- The unit must be securely installed on a stable and rigid support and fixed from the beginning.
- It is recommended to install the unit on rubber grommets or vibration dampers (Not supplied).
- Slowly release the nitrogen holding charge through the Schrader port.
- Connect the unit to the system as soon as possible to avoid oil contamination from ambient moisture.
- Avoid material entering the system while cutting tubes. Never drill holes where burrs cannot be removed.
- Braze with great care using state-of-the-art technique and vent piping with nitrogen gas flow.
- Connect the required safety and control devices. When the Schrader port is used for this, remove the internal valve.
- It is recommended to insulate the suction pipe up to the compressor inlet with 0.75 in (19 mm) thick insulation.
- Copper piping material should comply with ASHRAE 15. And all pipe joints should comply with SAE J513f.
- Connecting pipes shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts.
Leak detection
Never pressurize the circuit with oxygen or dry air. This could cause fire or explosion.
- Do not use dye for leak detection.
- Perform a leak detection test on the complete system.
- The maximum test pressure is 464 psi (32 bar).
- When a leak is discovered, repair the leak, and repeat the leak detection.
Vacuum dehydration
- Never use the compressor to evacuate the system.
- Connect a vacuum pump to both the LP & HP sides.
- Pull down the system under a vacuum of 500 μm Hg (0.67 mbar) absolute.
- Do not use a megohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.
Electrical connections
- Switch off and isolate the main power supply.
- Ensure that power supply cannot be switched on during installation.
- All electrical components must be selected as per local standards and unit requirements.
- Refer to wiring diagram for electrical connections details.
- Ensure that the power supply corresponds to the unit characteristics and that the power supply is stable (nominal voltage ± 10% and nominal frequency ±2,5 Hz).
- Dimension the power supply cables according to unit data for voltage and current.
- Protect the power supply and ensure correct earthing.
- Make the power supply according to local standards and legal requirements.
- The supply cable must be sized for the electrical characteristics mentioned on nameplate.
- The power supply must be connected with electrical connectors or cable glands, with a degree of protection equal to or greater than IP54, in the electrical box in such a way that no external force is exerted on the terminals.
- The unit is equipped with high- and low-pressure switches, which directly cut the power supply to the compressor in case of activation.
- For units with a 3-phase scroll compressor, correct phase sequence for compressor. rotation direction shall be observed.
- Determine the phase sequence by using a phase meter in order to establish the phase orders of line phases L1, L2 and L3.
- Connect line phases L1, L2 and L3 to main switch terminals T1, T2 and T3 respectively.
Filling the system
Assure that Condensing Unit (partial unit) shall only be connected to an
appliance suitable for the same refrigerant.
NOTE: A2L Refrigerants are filled in cylinders with left-hand thread. To
connect to a standard flexible hose, you need to use an inter-connector on
cylinders.
Wear protective stuff like goggles and protective gloves.
- Never start the compressor under vacuum. Keep the compressor switched off.
- Vacuum system shall be approved for A2L.
- Before charging the refrigerant, verify that the oil level is between ¼ and ¾ on the compressor oil sight glass. If additional oil is required, please refer to the compressors label for type of oil.
- Use only the refrigerant for which the unit is designed for.
- Only fill the refrigerant in liquid phase into the condenser or liquid receiver. Ensure a slow charging of the system 58 to 72 psi (4 – 5 bar).
- Do not put liquid refrigerant through suction line.
- It is not allowed to mix additives with the oil and/or refrigerant.
- The remaining charge is done until the installation has reached a level of stable nominal condition during operation.
- Never leave the filling cylinder connected to the circuit.
- Stop Valve as Schrader port for service operation like Gas Charging, pressure measurement.
- In the case of 1-Valve cylinder (without dip tube). To place carefully and safely cylinder upside down. (see the picture 2).
- In the case of 2-Valve cylinder (with dip tube). To charge from liquid (red) Valve.
Verification before commissioning
Use safety devices such as safety pressure switch and mechanical relief valve
in compliance with both generally and locally applicable regulations and
safety standards. Ensure that they are operational and properly set.
Check that the settings of high-pressure switches and relief valves don’t
exceed the maximum service pressure of any system component.
- Verify that all electrical connections are properly fastened and in compliance with local regulations.
- When a crankcase heater is required, it must be energized at least 12 hours before initial start- up and start-up after prolonged shut-down period.
Start-up
- Never start the unit when no refrigerant is charged.
- All service valves must be in the open position.
- Check compliance between unit and power supply.
- Check that the crankcase heater is working.
- Check that the fan can rotate freely.
- Check that the protection sheet has been removed from the backside of condenser.
- Balance the HP/LP pressure.
- Energize the unit. It must start promptly. If the compressor does not start, check wiring conformity, voltage on terminals and sequence phase.
- Eventual reverse rotation of a 3-phase compressor can be detected by following phenomena; unit doesn’t start, the compressor doesn’t build up pressure, it has abnormally high sound level and abnormally low power consumption. In such case, shut down the unit immediately and connect the phases to their proper terminals.
- If the rotation direction is correct the low-pressure indication on the low-pressure gauge shall show a declining pressure and the high-pressure indication on the high pressure gauge shall show an increasing pressure.
Check with running unit
-
Check the fan rotation direction. Air must flow from the condenser towards the fan.
-
Check current draw and voltage.
-
Check suction superheat to reduce risk of slugging.
-
The optimum compressor suction superheat is around 41°F (6K). The maximum allowed superheat is 86°F (30K).
-
When a sight glass is provided observe the oil level at start and during operation to confirm that the oil level remains visible.
-
Respect the operating limits.
-
Check all tubes for abnormal vibration. Movements in excess of 0.06 in (1.5 mm) require corrective measures such as tube brackets.
-
When needed, additional refrigerant in liquid phase may be added in the low-pressure side as far away as possible from the compressor. The compressor must be operating during this process.
-
Do not overcharge the system.
-
Never release refrigerant to atmosphere.
-
Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise, and leak detection.
-
Record type and amount of refrigerant charge as well as operating conditions as a reference for future inspections.
Compressor failure to build up pressure: Check all bypass valves in the system to ensure that none of these has been opened. Also check that all solenoid valves are in their proper position. -
Abnormal running noise: Ensure the absence of any liquid flood-back to the compressor by means of measuring the return gas superheat and compressor sump temperature. The sump should be at least 41°F (6K) above the saturated suction temperature under steady-state operating conditions.
-
The high-pressure switch trips out: Check condenser operations (condenser cleanliness, fan operation, water flow and water pressure valve, water filter, etc.). If all these are OK, the problem may be due to either refrigerant overcharging or the presence of a non-condensable (e.g., air, moisture) in the circuit.
-
The low-pressure switch trips out: Check evaporator operations (coil cleanliness, fan operations, water flow, water filter, etc.), liquid refrigerant flow and pressure drops (solenoid valve, filter dryer, expansion valve, etc.), refrigerant charge.
-
Low refrigerant charge: The correct refrigerant charge is given by the liquid sight glass indication, the condenser delta T in relation to the refrigerant pressure tables (pressure temperature), the superheat and the subcooling, etc. (if additional charge is deemed necessary, refer to section 8).
Maintenance
Always switch off the unit at main switch before remove fan panel.
Internal pressure and surface temperature are dangerous and may cause
permanent injury. Maintenance operators and installers require appropriate
skills and tools. Tubing temperature may exceed 212°F (100°C) and can cause
severe burns.
Ensure that periodic service inspections to ensure system reliability and as
required by local regulations are performed.
Risk Of Fire Or Explosion. flammable Refrigerant Used. To Be Repaired Only By
Trained Service Personnel. Do Not Puncture Refrigerant Tubing.
To prevent system related problems, following Periodic maintenance is recommended:
- Verify that safety devices are operational and properly set.
- Ensure that the system is leak tight.
- Check the compressor current draw.
- Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
- Check that all electrical connections are still adequately fastened.
- Keep the unit clean and verify the absence of rust and oxidation on the unit components, tubes and electrical connections.
The condenser must be checked at least once a year for clogging and be cleaned if deemed necessary. Access to the internal side of the condenser takes place through the fan panel. Microchannel coils tend to accumulate dirt on the surface rather than inside, which makes them easier to clean than fin-&-tube coils.
- Switch off the unit at main switch before remove any panel from the condensing unit.
- Remove surface dirt, leaves, fibers, etc. with a vacuum cleaner, equipped with a brush or other soft attachment. Alternatively, blow compressed air through the coil from the inside out, and brush with a soft bristle. Do not use a wire brush. Do not impact or scrape the coil with the vacuum tube or air nozzle.
If the refrigerant system has been opened, the system has to be flushed with dry air or nitrogen to remove moisture and a new lter drier has to be installed. If evacuation of refrigerant has to be done, it shall be done in such a way that no refrigerant can escape to the environment.
Warranty
Always transmit the model number and serial number with any claim filed
regarding this product.
The product warranty may be void in following cases:
- Absence of nameplate.
- External modifications; in particular, drilling, welding, broken feet and shock marks.
- Compressor opened or returned unsealed.
- Rust, water or leak detection dye inside the compressor.
- Use of a refrigerant or lubricant not approved by Danfoss.
- Any deviation from recommended instructions pertaining to installation, application or maintenance.
- Use in mobile applications.
- Use in explosive atmospheric environment.
- No model number or serial number transmitted with the warranty claim.
Disposal
Danfoss recommends that condensing units and oil should be recycled by a suitable company at its site.
Instructions
OP-HRSM0500NC0217N / OP-HRSM0500NC0218Q / OP-HRSM0500NC0219R
| H| L| D| a1| a2| b1
---|---|---|---|---|---|---
in| 28.1| 49.4| 31.5| 48.4| 47.2| 26.1
mm| 715| 1254| 800| 1230| 1200| 664
OP-HRSM0750NC211Q / OP-HRSM0750NC211R
| H| L| D| a1| a2| b1
---|---|---|---|---|---|---
in| 38.5| 61.2| 31.5| 60.2| 58.6| 27.4
mm| 977| 1554| 800| 1530| 1488| 696
OP-HRSM1000NC211Q / OP-HRSM1000NC211R
| H| L| D| a1| a2| b1
---|---|---|---|---|---|---
in| 52.5| 65.2| 35.8| 64.2| 62.8| 23.1
mm| 1333| 1655| 910| 1631| 1595| 588
Code: OP- HRSM0500NC0217N
Code: OP-HRSM0500NC0218Q / OP-HRSM0750NC0213Q / OP-HRSM1000NC0215Q
Code: OP-HRSM0500NC0219R / OP-HRSM0750NC0214R / OP-HRSM1000NC0216R
Danfoss A/S
Climate Solutions • danfoss.us • +1 888 326 3677 •
baltimore@danfoss.com
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.