EKC 361 Media Temperature Controller User Guide
- June 1, 2024
- EKC
Table of Contents
- EKC 361 Media Temperature Controller
- Features
- Introduction
- Application examples
- Extra options
- Function
- Survey of functions
- Operation
- Menu survey
- Data
- Ordering
- Connections
- Data communication
- Start of controller
- If the temperature fluctuates
- Trouble shooting – ICS/PM with CVQ
- Fine adjustments
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
EKC 361 Media Temperature Controller
The controller and valve can be used where there are stringent requirements to accurate temperature control in connection with refrig- eration.
E.g.:
- Cold room for fruits and food products
- Refrigerating systems
- Work premises in the food industry
- Process cooling of liquids
Features
- The temperature is kept within an accuracy of ±0.25°C or better after a transient phenomenon.
- The evaporator’s temperature is kept as high as possible, so that the air humidity is kept high and waste is limited.
- A transient phenomenon can be controlled with the adaptive function. Select either:
- Fast build-up where underswings are allowed
- Not quite so fast build-up where under swings are less pronounced
- Build-up without underswings
- PID regulation
- p0 limitation
Introduction
Functions
- Modulating temperature control
- Digital ON/OFF input for start/stop of regulation ICS/PM or forced closing of ICM
- Alarm if the set alarm limits are exceeded
- Relay output for fan
- Relay output for solenoid valves
- Analog input signal that can displace the temperature reference
- Analog Output signal corresponding to selecting temperature as running display value. Please observe : Not possible if ICM is selected as valve
Application examples
ICS/PM
- ISC/PM with CVQ is a pilot-operated and pressure-dependent valve for controlling media temperature.
- The ICS or PM must be equipped with a CVQ pilot valve in order to position ICS or PM. The CVQ valve is operated by the EKC 361 controller.
- Please notice that a power failure will cause the CVQ pilot valve to fully open ICS/PM. If it is required that ICS/PM must close at power failure, the pilot valve type EVM-NC can be installed.
- If the Digital Input is ON, it releases the ICS/PM for controlling temperature. If the Digital Input is OFF, if stops controlling PM/ICS, but EKC 361 will maintain a CVQ minimum temperature. (Param-eter n02)
- Please see separate literature for ICS/PM
- ICS : DKRCI.PD.HS0.A-
- PM : DKRCI.PD.HL0.A-
ICM
- ICM is a direct activating and pressure independent valve for con-trolling media temperature.
- When ICM is selected, the ICM is positioned directly via the analog output 0/4-20mA output from the EKC 361.
- If the Digital Input is ON, it releases the ICM for controlling tem-perature. If the Digital Input is OFF, the ICM is forced to close.
- The opening degree OD 0-100 % can be limited by parameter n32 and n33.
- Please see separate literature for ICM
- ICM : DKRCI.PD.HT0.A-
General for ICS/PM and ICM
- The EKC 361 can also operate a solenoid valve in the liquid line (Digital output on terminal 9 and 10). It will follow the status of Digital Input, however if a low temperature alarm is detected (A2 alarm) the solenoid valve in the liquid line will be closed.
- The EKC 361 can also operate a fan (Digital output on terminal 8 and 10). It will follow the status of Digital Input.
- The Parameter (r12) must be ON in order to ensure general opera-tion. If Parameter (r12) is OFF, EKC 361 will operate corresponding to if Digital Input is OFF
- As media temperature sensor is Sair is used. Please observe that Sair can also be used to control liquid.
- As option an auxiliary temperature sensor Saux can be installed but only for monitoring.
- Sair/Saux can both be shown as running display value selected by parameter o17. The selected sensor (Sair or Saux) will be sent out on the Analog Output as 0/4-20 mA.
- Temperature scaling with parameter o27 and o28. Please observe by ICM the Analog Output is not available for sending temperature signals (Sair or Saux).
- It is normally recommended, on a aircooler, to install Sair, at the evaporator air outlet side.
Extra options
PC operation
The controller can be provided with data communication, so that it may be
hooked up with other products in the ADAP-KOOL® range of refrigeration
controls. Operation, moni toring and data collection can then be performed
from a PC – either in situ or at a service company.
Function
Very accurate temperature control
With this system where controller, pilot valve and main valve have been
adapted for optimum use in the refrigerating plant, the re-frigerated products
may be stored with temperature fluctuations of less than ±0.25°C.
High air humidity
As the evaporating temperature is constantly adapted to the refrigeration
needs and will always be as high as possible with a very small temperature
fluctuation, the relative air humidity in the room will be kept at a maximum.
Drying-out of the products will in this way be reduced to a mini-mum.
Temperature is quickly attained
With the built-in PID control and the possibility of choosing be-tween three
transient phenomena, the controller can be adapted to a kind of temperature
performance that is optimum for this particular refrigerating plant. See
parameter (n07).
- Fastest possible cooling
- Cooling with less underswing
- Cooling where underswing is unwanted.
Regulation ICS/PM with CVQ
The controller receives signals from room sensor Sair. This room sensor must
be placed at the air outlet from the evaporator to obtain the best possible
regulation. The controller sees to it that the required room temperature is
maintained.
Built-in between the controller and the actuator is a so-called inner control
loop which constantly checks the temperature (pres-sure) in the actuator’s
pressure vessel. In this way a very stable control system is obtained.
If there is a deviation between the required and the registered temperature
the controller will immediately send more or fewer pulses to the actuator to
counteract the error. A change of the number of pulses will act on the
temperature and hence the pressure in the pressure vessel. As the charging
pressure and the evaporating pressure p0 follow each other, a changed charging
pressure will produce the effect that the valve’s opening degree is also
changed. The ICS/PM with CVQ system maintains the pressure in the evaporator
whatever pressure changes there may be on the suction side (on the ICS/PM
valve’s outlet).
Evaporating pressure limitation (p0 limitation)
The inner control loop mentioned above also causes the evapora-ting pressure
to stay within a fixed limit. In this way the system is safeguarded against a
too low supply air temperature.
It offers the following advantages:
- High-temperature systems can be connected to low-tempera ture compressor units
- Protection against icing on evaporator
- Frost protection of liquid coolers
Regulation with ICM
When using ICM as selected valve the system will still control ICM in order to
maintain Sair according to entered setpoint.
This system does not include any inner control loop.
It is a direct operating and pressure independent valve for control-ling media
temperature. (Sair).
Survey of functions
Function| Para- meter| Parameter by operation via data com-
munication
---|---|---
Normal display| |
Normally Sair (017=Air) will be shown as running display value. If lower
button is activated Saux will be displayed for 5 sec, and then return to Sair
If (017=Au) Saux will be shown as running display value. If lower button is activated Sair will be displayed for 5 sec, and then return to Saux
If ICM has been selected (n03=6)
If (017=Air) Sair (017=Air) will be shown as running display value. If lower button is activated OD (u24) will be displayed for 5 sec, and then return to Sair.
If (017=Au) OD (u24) will be shown as running display value. If lower button is activated Sair will
be displayed for 5 sec, and then return to OD (u24)
| | Air temp.
Reference| |
Setpoint
Regulation is performed based on the set value provided that there is no external contribution (o10).
(Push both buttons simultaneously to set the setpoint).
| –| SP Temp.
Temperature unit
Here you select whether the controller is to indicate the temperature values in °C or in °F. If indi- cation in °F is selected, other temperature settings will also change over to Fahrenheit, either as absolute values or as delta values.
| r05| Temp unit
°C=0,
°F=1
(In AKM only °C is displayed whatever the setting)
External contribution to the setpoint
This setting determines how large a contribution (in °C/°F) is to be added to the set setpoint when the input signal is max. (20 mA).
| r06| Ext. Ref.off set (°C/°F)
Correction of signal from S air
(Compensation possibility through long sensor cable).
| r09| Adjust SAir (°C/°F)
Correction of signal from S aux
(Compensation possibility through long sensor cable).
| r10| Adjust SAux (°C/°F)
Start/stop of refrigeration
With this setting refrigeration can be started and stopped. Start/stop of refrigeration can also be accomplished with the external switch function. See also appendix 1.
| r12| Main Switch
Alarm| |
The controller can give alarm in different situations. When there is an alarm
all the light-emitting diodes (LED) will flash on the controller front panel,
and the alarm relay will cut in.| |
Alarm for upper deviation
The alarm for too high Sair temperature is set here. The value is set in Kelvin. The alarm becomes active when the Sair temperature exceeds the actual reference plus A01. (The actual reference (SP
+ r06) can be seen in u02).
| A01| Upper deviation
Alarm for lower deviation
The alarm for too low Sair temperature is set here. The value is set in Kelvin. The alarm becomes active when the Sair temperature drops below the actual reference minus A02. If a low tempera- ture alarm is detected (A2 alarm) the solenoid valve in the liquid line (Digital output on terminal 9 and 10) will be closed
| A02| Lower deviation
Alarm delay
If one of the two limit values is exceeded, a timer function will commence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes.
| A03| Temp alarm delay
| | With data communication the importance of the individual alarms can be
defined. Setting is carried out in the “Alarm destina- tions” menu. See also
page 10.
Control parameters| |
Actuator’s max. temperature
Set the temperature (°C) the actuator is to have at the limit of the regulating range. The setting ensures that the actuator will not become superheated and work itself away from the regulating range. Due to tolerances in the actuator the value must be set 10K higher than indicated in the curves on page 11.
| n01| Q-max. temp.
Actuator’s min. temperature
Set the temperature (°C) the actuator will have at the limit of the regulating range. The setting ensures that the actuator will not become too cold and work itself away from the regulating range. Due to tolerances in the actuator the value must be set 10K lower than indicated in the curves on page 11.
| n02| Q-min. temp.
Actuator type
Here you define the actuator mounted in the system: 1: CVQ -1-5 bar
2: CVQ 0-6 bar
3: CVQ 1.7-8 bar
4: CVMQ
5: KVQ
6: ICM
| n03| Valve type
---|---|---
P: Amplification factor Kp
If the Kp value is reduced the regulation becomes slower.
| n04| Kp factor
I: Integration time Tn
The I-setting can be cancelled by setting the value to max. (600s). If it is set to 600s, parameter n07 must be set to “0”. (If the Tn value is increased the regulation becomes slower).
| n05| Tn sec.
D: Differentiation time Td
The D-setting can be cancelled by setting the value to min. (0).
| n06| Td sec.
Transient phenomenon
If the refrigeration requires a very fast transient phenomenon or must not have an underswing or temperature shift, this function can be used. (see page 4)
0: Ordinary regulating technique
1: Fast building-up where a minor underswing is allowed 2: Not quite so fast building-up, but without underswing
| n07| Q-ctrl. mode
OD – Opening degree Max. Limitation – ICM only
When ICM has been selected (n03=6) the Maximum OD can be entered. ICM will never go above this value. (If n32=n33, ICM is forced to this value)
| n32| ICM OD Max.
OD – Opening degree Min. Limitation – ICM only
When ICM has been selected (n03=6) the Minimum OD can be entered. ICM will never go below this value. (If n32=n33, ICM is forced to this value)
| n33| ICM OD Min.
Miscellaneous| |
Output signal
The controller can transmit a current signal via the analog output (terminal 2 and 5). Range of current signal can be selected below:
If (017=Air) Sair will send out to the analog output. If (017=Au) Saux will send out to the analog output
Sair/Saux min. value (0 or 4 mA) will correspond to the setting in “o27” Sair/Saux max. value (20 mA) will correspond to the setting in “o28”
If ICM has been selected (n03=6)
OD (u24) to control ICM, is send out to the analog output (o27) and (o28) is not active
Range for current signal: 0: No output signal
1: 4-20 mA
2: 0-20 mA
| o09| AO type
Input signal
If you wish to connect a signal that is to displace the controller’s control reference, the signal must be defined in this menu.
0: No signal
1: 4-20 mA
2: 0-20 mA
(4 or 0 mA will not give a displacement. 20 mA will displace the reference by the value set in menu r06).
| o10| AI type
Data communication
If the controller is built into a network with data communication, it must have an address, and the master gateway of the data communication must then know this address.
These settings can only be made when a data communication module has been mounted in the controller and the installation of the data communication cable has been completed.
This installation is mentioned in a separate document “RC8AC”.
| | ****
Following installation of a data communica- tion module, the controller can be operated on a par with the other controllers in ADAP- KOOL® refrigeration controls.
The address is set between 1 and 60| o03| –
The address is sent to the gateway when the menu is set in pos. ON (The
setting will automatically change back to Off after a few seconds.)| o04| –
Language
This setting is only required if data communication is connected to the controller. Settings: 0=English, 1=German, 2=French, 3=Danish, 4=Spanish and 6=Swedish
When the controller is operated via data communication, the texts in the right-hand column will be shown in the selected language.
When you change the setting to an other language you must activate o04 before “the new language” can be visible from the AKM program.
| o11| Language
Frequency
Set the net frequency.
| o12| 50 / 60 Hz
(50=0, 60=1)
Selection of running display value
If Sair (017=Air) will be shown as running display value. If lower button is activated Saux will be displayed for 5 sec, and then return to Sair
Sair will send out to the analog output. See also (o09),(o27),(o28)
If (017=Au) Saux will be shown as running display value. If lower button is activated Sair will be displayed for 5 sec, and then return to Saux
Saux will send out to the analog output. See also (o09),(o27),(o28)
If ICM has been selected (n03=6)
If (017=Air) Sair (017=Air) will be shown as running display value. If lower button is activated OD (u24) will be displayed for 5 sec, and then return to Sair
If (017=Au) OD (u24) will be shown as running display value. If lower button is activated Sair will be displayed for 5 sec, and then return to OD (u24)
| o17| Display Aux/Air Aux =0
Air = 1
---|---|---
(Setting for the function o09)
Set the temperature value where the output signal must be minimum (0 or 4 mA)
| o27| Temp. at AO min.
(Setting for the function o09)
Set the temperature value where the output signal must be maximum (20 mA). (With a tem- perature range of 50°C (differential between the settings in o27 and o28) the dissolution will be better than 0.1 °C. With 100°C the dissolution wil be better than 0.2°C.)
| o28| Temp. at AO max.
Service
A number of controller values can be printed for use in a service situation
Read the temperature at the Sair sensor (calibrated value)| u01| Air temp.
Read the control reference
(Setpoint + any contribution from external signal)
| u02| Air reference
Read temperature at the Saux sensor (calibrated value)
(This showing can also be uploaded from the normal display, if you push the lowermost button
for almost a second)
| u03| Aux. temp.
Read valve’s actuator temperature| u04| Actuator temp.
Read reference for valve’s actuator temperature| u05| Actuator Ref.
Read value of external current signal| u06| AI mA
Read value of transmitted current signal| u08| AO mA
Read status of input DI (start/stop input)| u10| DI
ICM opening degree. Only active if (n03)=6| u24| OD%
| —| DO1 Alarm
Read status of alarm relay
| —| DO2 Cooling
Read status of relay for solenoid valve
| —| DO3 Fan
Read status of relay for fan
Operating status
Operating status of the controller can be called forth in the display. Push
briefly (1s) the upper button. If there is a status code, it will be shown on
the display. (Status codes have lower priority than alarm codes. In other
words, you cannot see a status code, if there is an active alarm).
The individual status codes have the following meanings:
| | EKC State
(0 = regulation)
S10: Refrigeration stopped by the internal or external start/ stop| | 10
S12: Refrigeration stopped due to low Sair| | 12
Operation
Display
The values will be shown with three digits, and with a setting you can
determine whether the temperature is to be shown in °C or in °F.
Light-emitting diodes (LED) on front panel
There are LED’s on the front panel which will light up when the corresponding
relay is activated.
The three lowest LED’s will flash, if there is an error in the regula-tion.
In this situation you can upload the error code on the display and cancel the
alarm by giving the uppermost button a brief push.
The controller can give the following messages:
E1|
Error message
| Errors in the controller
E7| Cut-out Sair
E8| Short circuited Sair
E11| Valve’s actuator temperature outside its range
E12| Analog input signal is outside the range
A1|
Alarm message
| High-temperature alarm
A2| Low-temperature alarm
The buttons
When you want to change a setting, the two buttons will give you a higher or
lower value depending on the button you are push-ing. But before you change
the value, you must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds – you will then enter the column with
parameter codes. Find the parameter code you want to change and push the two
buttons simultaneously. When you have changed the value, save the new value by
once more pushing the two buttons simultane-ously.
Examples of operations
Set set-point
- Push the two buttons simultaneously
- Push one of the buttons and select the new value
- Push both buttons again to conclude the setting
Set one of the other menus
- Push the upper button until a parameter is shown
- Push one of the buttons and find the parameter you want to change
- Push both buttons simultaneously until the parameter value is shown
- Push one of the buttons and select the new value
- Push both buttons again to conclude the setting
Menu survey
Function| Para-
meter
| Min.| Max.| Fac.
setting
---|---|---|---|---
Normal display
Shows the temperature at the selected sensor
At ICM valve OD also can be selected
| –| °C|
Reference
Set the required room temperature| –| -70°C| 160°C| 10°C
Temperature unit| r05| °C| °F| °C
Input signal’s temperature influence| r06| -50°C| 50°C| 0.0
Correction of the signal from Sair| r09| -10,0°C| 10,0°C| 0.0
Correction of the signal from Saux| r10| -10,0°C| 10,0°C| 0.0
Start/stop of refrigeration| r12| OFF/0| On/1| On/1
Alarm
Upper deviation (above the temperature setting)| A01| 0| 50 K| 5.0
Lower deviation (below the temperature setting)| A02| 0| 50 K| 5.0
Alarm’s time delay| A03| 0| 180
min
| 30
Regulating parameters
Actuator max. temperature| n01| 41°C| 140°C| 140
Actuator min. temperature| n02| 40°C| 139°C| 40
Actuator type (1=CVQ-1 to 5 bar, 2=CVQ 0 to 6 bar, 3=CVQ 1.7 to 8 bar, 4=
CVMQ, 5=KVQ, 6= ICM)| n03| 1| 6| 2
P: Amplification factor Kp| n04| 0,5| 50| 3
I: Integration time Tn (600 = off)| n05| 60 s| 600 s| 240
D: Differentiation time Td (0 = off)| n06| 0 s| 60 s| 10
Transient phenomenon 0: Ordinary control
1: Underswing minimised
2: No underswing
|
n07
|
0
|
2
|
2
OD – Opening degree – max. limit – ICM only| n32| 0%| 100%| 100
OD – Opening degree min limit – ICM only| n33| 0%| 100%| 0
Miscellaneous
Controller’s address (0-120)| o03| 0| 990| 0
ON/OFF switch (service-pin message)| o04| –| –|
Define output signal of analog output: 0: no signal, 1: 4 – 20 mA, 2: 0 – 20
mA| o09| 0| 2| 0
Define input signal of analog input 0: no signal, 1: 4 – 20 mA, 2: 0 – 20 mA|
o10| 0| 2| 0
Language (0=english, 1=German, 2=French, 3=Danish, 4=Spanish and
6=Swedish.)When you change the setting to an other language you must activate
o04 before “the new language” can be visible from the AKM program.|
011*
|
0
|
6
|
0
Set supply voltage frequency| o12| 50
Hz/0
| 60
Hz/1
| 0
Select of running display value| o17| Au/0| Air/1| Air/1
(Setting for the function o09)
Set the temperature value where the output signal must be minimum (0 or 4 mA)
|
o27
|
-70°C
|
160°C
|
-35
(Setting for the function o09)
Set the temperature value where the output signal must be maximum (20 mA)
|
o28
|
-70°C
|
160°C
|
15
Service
Read temperature at the Sair sensor| u01| °C|
Read regulation reference| u02| °C|
Read temperature at the Saux sensor| u03| °C|
Read valve’s actuator temperature| u04| °C|
Read reference of the valve’s actuator temperature| u05| °C|
Read value of external current signal| u06| mA|
Read value of transmitted current signal| u08| mA|
Read status of input DI| u10| on/off|
ICM opening degree. (only at ICM)| u24| %|
*) This setting will only be possible if a data communication module has been installed in the controller.
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage
Data
Supply voltage
| 24 V a.c. +/-15% 50/60 Hz, 80 VA
(the supply voltage is galvanically separated from the input and output signals)
---|---
Power consumption| Controller Actuator| 5 VA
75 VA
Input signal
| Current signal| 4-20 mA or 0-20 mA
Digital input from external contact function
Sensor input| 2 pcs. Pt 1000 ohm
Output signal| Current signal| 4-20 mA or 0-20 mA
Max. load: 200 ohm
Relay output| 2 pcs. SPST| AC-1: 4 A (ohmic)
AC-15: 3 A (inductive)
Alarm relay| 1 pcs. SPST
Actuator
| ****
Input
| Temperature signal from sensor in the actuator
Output| Pulsating 24 V a.c. to actuator
Data communication| Possible to connect a data communication module
Ambient temperature| During operation During transport| -10 – 55°C
-40 – 70°C
Enclosure| IP 20
Weight| 300 g
Mounting| DIN rail
Display| LED, 3 digits
Terminals| max. 2.5 mm2 multicore
Approvals
| EU Low Voltage Directive and EMC demands re CE-marking complied with.
LVD-tested acc. to EN 60730-1 and EN 60730- 2-9
EMC-tested acc. to EN50081-1 and EN 50082-2
Capacitive load
The relays cannot be used for the direct connection of capacitive loads such
as LEDs and on/off control of EC motors.
All loads with a switch mode power supply must be connected with a suit-able
contactor or similar.
Ordering
Type | Function | Code No. |
---|---|---|
EKC 361 | Evaporating pressure controller | 084B7060 |
EKA 174
| Data communication module (accessories), (RS 485 module) with galvanic separation| ****
084B7124
- Temperature sensor Pt 1000 ohm: ……….Kindly refer to catalogue RK0YG…
- Valves: …………………………………………………….DKRCI.PD.HT0.A
Connections
Necessary connections
Terminals:
25-26 Supply voltage 24 V a.c.
17-18 Signal from actuator (from NTC) 23-24 Supply to actuator (to PTC)
20-21 Pt 1000 sensor at evaporator outlet
1-2 Switch function for start/stop of regulation. If a switch is not
connected, terminals 1 and 2 must be short circuited.
Application dependent connections
Terminal:
-
12-13 Alarm relay
There is connection between 12 and 13 in alarm situa tions and when the controller is dead -
8-10 Relay switch for start/stop of fan
-
9-10 Relay switch for start/stop of solenoid valves
-
18-19 Current signal from other regulation (Ext.Ref.)
-
21-22 Pt 1000 sensor for monitoring
-
2-5 Current output for Sair/Saux temperature or ICAD actuator for ICM valve
-
3-4 Data communication
Mount only, if a data communication module has been mounted.
It is important that the installation of the data communication cable be done correctly. Cf. separate literature No.
RC8AC..
Data communication
This page contains a description of a few of the possibilities you will have when the controller is provided with data communication.
If you want to know more about operation of controllers via PC, you may order additional literature.
Examples
Example of menu display
- Measurements are shown at one side and settings at the other.
- You will also be able to see the parameter names of the functions on page 5-7.
- With a simple change-over the values can also be shown in a trend diagram.
- If you wish to check earlier temperature measurements, you can see them in the log collection.
Alarms
-
If the controller is extended with data communication, it will be possible to define the importance of the transmitted alarms.
-
The importance is defined with the setting: 1, 2, 3 or 0. When the alarm then arises at some time, it will result in one of the following activities:
-
1 = Alarm
The alarm message is sent off with alarm status 1. This means that the gateway that is the master in the system will have its alarm relay output activated for two minutes. Later, when the alarm ceases, the alarm text will be retransmitted, but now with status value 0. -
2 = Message
The alarm text is transmitted with status value 2. Later, when the “message” lapses, the alarm text is retransmitted, but now with status value 0. -
3 = Alarm
As “1”, but the master gateway’s relay output is not activated. -
0 = Suppressed information The alarm text is stopped at the controller. It is transmitted nowhere.
Appendix 1
Interaction between internal and external start/stop functions and active
functions.
Internal Start/stop | Off | Off | On | On |
---|---|---|---|---|
External Start/stop | Off | On | Off | On |
Refrigeration | Off | On | ||
Actuator | Stand-by | Regulating | ||
Actuator temperature | “n02” | “n02” to “n01” | ||
Fan relay | Off | On | ||
Expansion valve relay | Off | On | ||
Temperature monitoring | No | Yes | ||
Sensor monitoring | Yes | Yes |
Appendix 2
Cable length for the CVQ actuator
The actuator must be supplied with 24 V a.c. ± 10%.
To avoid excessive voltage loss in the cable to the actuator, use a thicker
cable for large distances.
Appendix 3
Connection between the evaporating temperature and the actuator’s temperature
(the values are approximate).
n01: The highest regulated room temperature will have a be longing to value
which in turn indicates the value of the n01 setting. Due to tolerances in the
actuator, the setting value must be 10 K higher than shown in the curve.
n02: The lowest occurring suction pressure will have a belonging to value
which in turn indicates the value of the n02 setting. Due to tolerances in the
actuator, the setting value must be 10 K lower than shown in the curve.
Start of controller
When the electric wires have been connected to the controller, the following points have to be attended to before the regulation starts:
- Switch off the external ON/OFF switch that starts and stops the regulation.
- Follow the menu survey on page 7, and set the various para- meters to the required values.
- Switch on the external ON/OFF switch, and regulation will start.
- If the system has been fitted with a thermostatic expansion valve, it must be set to minimum stable superheating. (If a specific T0 is required for the adjustment of the ex pansion valve, the two setting values for the actuator temperature (n01 and n02) can be set to the belonging value while the adjustment of the expansion valve is carried out. Remember to reset the values).
- Follow the actual room temperature on the display. (On terminals 2 and 5 a current signal can be transmitted which represents the room temperature. Connect a data collection unit, if applicable, so that the temperature performance can be followed).
If the temperature fluctuates
When the refrigerating system has been made to work steadily, the controller’s
factory-set control parameters should in most cases provide a stable and
relatively fast regulating system.
If the system on the other hand oscillates, you must register the periods of
oscillation and compare them with the set integration time Tn, and then make a
couple of adjustments in the indicated parameters.
If the time of oscillation is longer than the integration time:(Tp > Tn , (Tn is, say, 4 minutes))
- Increase Tn to 1.2 times Tp
- Wait until the system is in balance again
- If there is still oscillation, reduce Kp by, say, 20%
- Wait until the system is in balance
- If it continues to oscillate, repeat 3 and 4
If the time of oscillation is shorter than the integration time:(Tp < Tn , (Tn is, say, 4 minutes))
- Reduce Kp by, say, 20% of the scale reading
- Wait until the system is in balance
- If it continues to oscillate, repeat 1 and 2
Trouble shooting – ICS/PM with CVQ
In addition to the error messages transmitted by the controller, the table below may help identifying errors and defects.
Symptom | Defect | Confirmation of defect |
---|---|---|
Media temperature too low. Actuator feels cold. | Short-circuited NTC resistor | |
in actuator. | If less than 100 ohm is measured across terminals 17 and 18 |
(disassemble the lead), the NTC or the leads are short-circuited. Check the
leads.
Defective PTC resistor (heating element) in actuator.| If more than 30 ohm or
0 ohm is measured across terminal 23 and 24 (disassemble the lead), either the
PTC or the leads are defective.
Check the leads.
Media temperature too low. Actuator fells warm.| Undersized cable to CVQ.|
Measure voltage across terminals 77 and 78 (min. 18 V a.c.). Measure
resistance in power cables to CVQ (max. 2 ohm)
Undersized 24 V transformer.| Measure voltage across transformer output
terminals (24 V a.c. +10/ -15%) under all working conditions.
If voltage drops under some working conditions the transformer is undersized.
Loss of charge in actuator.| Replace actuator.
Media temperature too high. Actuator feels cold.| Fault in refrigerant plant.|
Examine plant for ther defects.
Media temperature too high. Actuator feels warm.| Cut out NTC resistor in
actuator.| If more than 200 kohm is measured across terminals 17 and 18
(disassemble the lead), either the NTC or leads are disconnected.
Check the leads.
Fine adjustments
When the system has been operating for a while, it may be required for some systems to optimise some of the adjustments. Below we have a look at settings having an influence on the speed and accuracy of the regulation.
Adjustment of the actuator’s min. and max. temperatures
At the first setting these values were set to 10 K outside of the expected
temperature in order to eliminate the tolerances in the actuator. By adjusting
the two values to the values where the valve is exactly in mesh, the valve
will all the time remain active in its regulation. If the actuator is replaced
at a later date, this procedure must be repeated for the new actuator.
Min.
By adjusting the actuator’s min. temperature you obtain a limit for how low a
pressure can occur in the evaporator (the point is where the valve starts a
limitation of the refrigerant flow).
The system must be put in an operating situation where max. capacity is called
for (large refrigeration need).
The min. temperature must now be changed upwards step by step, at the same
time as the evaporating pressure is read on the system’s manometer.
When a change of the evaporating pressure is registered, this is the point
where the valve is exactly in mesh. (If frost protec tion is required for the
system, the value can be raised to the belonging value).
Max.
By adjusting the actuator’s max. temperature you obtain a limit for how high a
pressure can occur in the evaporator (the refrigerant ow is blocked
completely).
The system is put in an operating situation where there is no call for
refrigeration capacity (no refrigerant flow).
The max. temperature is now changed downwards step by step, at the same time
as the evaporating pressure is read on the system’s manometer.
When a change of the evaporating pressure is registered, this is the point
where the valve opens. Adjust the setting a little upwards, so that the valve
will again close completely for the refrigerant flow. (If the actual
application has a requirement re-garding max. evaporating pressure, a lower
setting may of course be selected, so that the pressure is limited).
Method for fixing Kp, Tn and Td
Described below is a method (Ziegler-Nichols) for fixing Kp, Tn and Td.
-
The system is made to regulate the temperature at the required reference with a typical load. It is important that the valve regu-lates, and that it is not fully open.
-
Parameter u05 is read. The actuator’s min. and max. setting is adjusted, so that the average of the min. and max. values is equal to the read u05.
-
The controller is set, so that it will regulate as a P-controller. (Td is set to 0, Tn in pos. OFF (600), and Q-Ctrl.mode is set at 0).
-
The stability of the system is examined by stopping the system for, say, one minute (using the start/stop setting or the switch). Now check how the building-up of the temperature proceeds. If the building-up peters out, raise Kp a little and repeat the start/stop operation. Continue with this until you obtain a build-ing-up which does not peter out.
-
Kp is in this case the critical amplification (Kpcritical) and the build-ing-up time for the continued oscillation is the critical building-up time (Tcritical).
-
Based on these values, the regulating parameters can now be calculated and subsequently set:
-
If PID regulation is required:
Kp < 0.6x Kpcritical
Tn > 0.5x Tcritical
Td < 0.12x Tcritical -
If PI regulation is required:
Kp < 0.45x Kpcritical
Tn > 0.85x Tcritical -
Reset the values for the controller’s min. and max. tem peratures and Q-Ctrl.mode.
Danfoss can accept no responsibility for possible errors in catalogues,
brochures and other printed material. Danfoss reserves the right to alter its
products without notice. This also applies to products already on order
provided that such alternations can be made without subsequential changes
being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies.
Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights
reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>