AET DW-6195 3 Phase Power Analyzer Instruction Manual
- June 1, 2024
- AET
Table of Contents
AET DW-6195 3 Phase Power Analyzer
Product Information
Specifications
- Model: DW-6195
- 3 Phase Power Analyzer
- SD Card Real-Time Data Recorder with Harmonic Measurement
- Features True RMS value for Voltage and Current
- ACV Input Impedance: 10 Mega ohms
- Safety Standard: IEC 1010, CAT III 600V
- Display: TFT for easy reading of measurement results
- Supports analysis for 3 phase multi-power systems
- Includes 3 current probes (CP-1201)
- Built-in clock and calendar for real-time data recording with SD card
Product Usage Instructions
1. Setup and Installation
Before use, ensure the device is placed in an indoor environment with a relative humidity of up to 80% and altitude below 2000 meters. Connect the necessary probes securely to the input terminals.
2. Powering On and Measurement
Turn on the power analyzer using the designated button. Select the appropriate power system (1P/2W, 1P/3W, 3P/3W, 3P/4W) for analysis. Monitor the measurements on the TFT display.
3. Data Recording and Retrieval
To record real-time data, insert an SD card into the device. The built-in clock will timestamp the measurements for accurate logging. To retrieve the saved data, follow the instructions to download it to a computer using Excel software.
4. Maintenance
Regularly clean the device using a dry cloth to ensure proper functioning. Replace batteries as needed following the guidelines provided in the manual.
FAQs
- Q: Can I use this power analyzer outdoors?
- A: No, this device is recommended for indoor use only.
- Q: What is the input impedance for AC voltage?
- A: The ACV input impedance is 10 Mega ohms.
- Q: How many current probes are included with the analyzer?
- A: The analyzer comes with 3 current probes (CP-1201).
“`
Sd card real time data recorder with harmonic measurement
3 PHASE
POWER ANALYZER
Model : DW-6195
Your purchase of this 3 phase POWER ANALYZER marks a step forward for you into the field of precision measurement. Although this METER is a complex and delicate instrument, its durable structure will allow many years of use if proper operating techniques are developed. Please read the following instructions carefully and always keep this manual within easy reach.
OPERATION MANUAL
Caution Symbol
Caution : Risk of electric shock ! During the measurement,
do not open the cabinet.
Caution : Do not apply the overload
voltage, current to the input terminal ! Remove test leads before open the
battery cover ! * Cleaning – Only use the dry cloth to clean the plastic case
!
Environment Conditions
- Installation Categories III 600V.
- Pollution Degree 2.
- Altitude up to 2000 meters.
- Indoor use.
- Relative humidity 80% max.
FEATURES
-
TFT Display to easy reading measument result. Analysis for 3 phase multi-power system, 1P/2W, 1P/3W,
3P/3W, 3P/4W. Voltage and the Current are the True RMS value. 3 current probes ( CP-1201 ) are included, if change the
current probes, the calibration procedures are not necessary. Current probe input signal/ranges with selection : Input signal (ACV) : 200 mV/300 mV/500 mV/1 V/2 V/3 V. Ranges (ACA) : 20 A/200 A/2000 A ( 1200 A )/30 A/300A /3000 A 60 A/600 A/6000 A. Meter can cooperate the universal current probes. Complete set with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp Probe ( CP 1201 ), AC to DC 9V adapter, 4 G SD memory card and Carrying bag. Measurement : V (phase-to-phase), V (phase-to-ground) A (phase-to-ground) KW ( True Power )/ KVA / KVAR / PF (phase) KW ( True Power )/ KVA / KVAR / PF (system) KWH / KVAH / KVARH / PFH (system) Phase angle Harmonics display (1-50th order). Simultaneous display of Harmonics and Waveform. Display of Waveform with Peak Values. Analysis of Total Harmonic Distortion ( THD ). Graphic Phase diagram with 3-Phase system parameters. 3 phase Voltage or Current Unbalanced Ratio ( VUR, AUR ) and Unbalanced Factor. Calculated Unbalanced Current through Neutral Line ( An ) Capture Transient events (including Dip, Swell and Outage ) with programmable threshold ( % ). Programmable CT ratio ( 1 to 600 ) and PT ratio ( 1 to 1000 )
1 -
ACV input impedance is 10 Mega ohms. Safety Standard : IEC 1010, CAT III 600V. Built-in clock and Calendar, real time data record with SD
memory card , sampling time set from 2 to 7200 seconds. Just slot in the SD card into the computer, it can down load the all the measured value with the time information ( year, month, date, hour, minute, second ) to the Excel directly, then user can make the further data analysis by themselves. Powered by AA ( UM-3 ) DC 1.5 V X 8 batteries ( Alkaline type ) or DC 9V adapter. Computer data output, can cooperate with optional USB Cable/USB-01, RS232 cable/UPCB-02 and Data Acquisition software, SW-U811. Optional current probes : CP-1201, CP-2000, CP-200, CP-3000, detail specification. User can order the meter only ( without the current probes ) with the special request as intend to cooperate their own current probes. Patented.
2. SPECIFICATIONS
2-1 General Specifications: Circuit Custom one-chip of microprocessor LSI
circuit Display LCD Size :
81.4 X 54 mm ( 3.2 X 2.1 inch ) * TFT LCD (320 X 240 pixels )
with backlight.
2
Measurement
Wire connections Voltage ranges Current probe input signal and range
Safety standard ACV input impedance Range select
Clamp frequency response Spec. tested frequency Over load protection
Over Indicator
- V (phase-to-phase) V (phase-to-ground) A (phase-to-ground) KW / KVA / KVAR / PF (phase)
KW / KVA / KVAR / PF (system) KWH / KVAH / KVARH / PFH (system) Power factor - Phase angle Frequency Harmonics display. 1P/2W, 1P/3W, 3P/3W, 3P/4W.
10 ACV to 600 ACV, auto range. - Current probe input signal volage ( ACV ) : 200mV/300mV/500mV/1V/2V/3V.
- Current probe input current range ( ACA ) : 20 A/200A/2000A (1200 A)/30A/300A/3000A 60 A/600 A/6000 A.
- Meter can cooperate the universal current probe.
IEC1010 CAT III 600 V.
10 Mega ohms.
ACV Auto range. ACA Manual range. 40 Hz to 1 KHz.
45 to 65 Hz.
ACV 720 ACV rms
ACA
1300 ACA with clamp probe * For the Clamp ,CP-1201
-
LCD display show ” OL “.
-
The data save into the SD card will show
” 9999 ” or ” 999 ” ( overleap the decimal point ).
3
Under Indicator Data Hold Data Record Sampling Time Power ON/OFF Real time
data logger
Data Output USB/RS232 * Computer
interface
Operating Temperature Operating Humidity Power Supply
Power Consumption Clamp max. conductor Size
- The data save into the SD card will show ” 9999 ” or ” 999 ” (overleap the decimal point ).
Freeze the display reading. SD Card Record. Approx. 1 second. Manual OFF by push button. Real time data logger, saved the data
into SD memory card and down load the all the measured value with the time information ( year/month/date/ hour/minute/second ) down load to the Excel. Sampling time for data logger : 2 seconds to 7200 seconds, the during of setting step are 2 seconds. Data error no. : 0.1% no. of total saved data typically. RS232 computer serial interface : Connect the optional USB cable USB-01 will get the USB plug. * Connect the optional RS232 cable UPCB-02 will get the RS232 plug. 0 to 50 ( 32 to 122 ).
Less than 80% R.H.. - DC 1.5V, AA ( UM-3 ) Battery X 8 PCs (Alkaline or heavy-duty battery).
- AC to DC 9V power adapter. Meter : 362 DCmA. Clamp : 22 DCmA.
50 mm ( 2.0 inch ) Dia. * For the Clamp ,CP-1201
4
Weight Dimension
Accessories Included
Optional Accessories
-
Meter : 840g ( meter only )
-
Clamp ( included cable ) : 500g
Meter :
225 X 125 X 64 mm
Clamp :
( 8.86 X 4.92 X 2.52 inch ) 210 X 64 X 33mm
( 8.3 X 2.5 X 1.3 inch )
Clamp Jaw : 86 mm (3.4 inch)- outside
- Instruction manual……………
1 PC
- Test Leads (TL88-4AT)………..
1 Set (4 PCs)
- Alligator clips (TL88-4AC)
1 Set (4 PCs)
-
Clamp Probe ( CP-1201 )……… 3 PCs
-
AC to DC 9V adapter…………….. 1 PC
-
SD card ( 4 G )………………..
1 PC
- Carrying bag…………………….
1 PC
-
200 Amp current probe, CP-200
-
2000 Amp current probe, CP-2000
-
Flexible 3000 Amp current probe, CP-3000
-
Flexible 3000 Amp current probe, CP-3001
-
Flexible 3000 Amp current probe, CP-3002
-
Flexible 6000 Amp current probe, CP-6001
-
USB Cable , USB-01
-
RS232 cable, UPCB-02
-
Data Acquisition software, SW-U811
-
EXCEL Data Acquisition software, SW-E802
2-2 Electrical Specifications ( 23±5 )
ACV
Range 10.0V to 600.0V Phase to neutral line
10.0V to 600.0V Phase to phase
Resolution 0.1V
Accuracy ±(0.5%+0.5V)
5
ACA
Range Resolution
20A 0.001A, < 10 A
0.01A,
10 A
200A 0.01A,
< 100 A
0.1A,
100 A
1200A 0.1A,
< 1000 A
1A,
1000 A
Accuracy Meter + CP-1201 Meter only Meter + CP-1201 Meter only Meter + CP-1201 Meter only
±(1 %+0.1A) ±(0.5 %+0.02A) ±(1 %+0.5A) ±(0.5 %+0.2A) ±(1 %+5A) ±(0.5 %+2A)
Remark : * When the Active power value ( P1 to P3 ) and Apparent
power value ( S1 to S3 ) show ” – ” indicator, it means the current probe is
under the reverse direction that compare with the real measuring current.
Power factor
Range
Resolution
0.00 to 1.00 0.01
Accuracy ±0.04
Remark : PFH : Long term power factor PF:
For 34W, 33W, 13W : PF = P/S
For 12W : PF1 = P1/S1
( Phase angle )
Range
Resolution
-180° to 180° 0.1°
Accuracy
±1°
- COS ( PF )
Frequency
Range 45 to 65 Hz
Resolution 0.1 Hz
Accuracy ±0.1 Hz
6
Active (Real) Power
DW-6195 + CP1201
Range
Resolution
System
Accuracy
0.000 to 9.999 KW
*0.001/0.01/0.1 KW
±(1.2%+0.008KW)
10.00 to 99.99 KW
*0.01/0.1 KW
±(1.2%+0.08KW)
100.0 to 999.9 KW
0.1 KW
±(1.2%+0.8KW)
1.000 to 9.999 MW
0.001 MW
±(1.2%+0.008MW)
- The resolution is changed according the different ACA range.
Apparent Power
DW-6195 + CP1201
Range
Resolution
System
Accuracy
0.000 to 9.999 KVA
*0.001/0.01/0.1KVA
±(1.2%+0.008KVA)
10.00 to 99.99 KVA
*0.01/0.1 KVA
±(1.2%+0.08KVA)
100.0 to 999.9 KVA
0.1 KVA
±(1.2%+0.8KVA)
1.000 to 9.999 MVA
0.001 MVA
±(1.2%+0.008MVA)
- The resolution is changed according the different ACA range.
Reactive Power
DW-6195 + CP1201
Range
Resolution
System
Accuracy
0.000 to 9.999 KVAR
*0.001/0.01/0.1KVAR ±(1.2%+0.008 KVAR)
10.00 to 99.99 KVAR
*0.01/0.1 KVAR
±(1.2%+0.08 KVAR)
100.0 to 999.9 KVAR
0.1 KVAR
±(1.2%+0.8 KVAR)
1.000 to 9.999 MVAR
0.001 MVAR
±(1.2%+0.008 MVAR)
- The resolution is changed according the different ACA range.
Remark : When the Reactive power value ( Q1 to Q3 ) show ” – ”
indicator, it means the ” current phase ” lag than the ” voltage phase “, the
load character is induction. When the Reactive power value ( Q1 to Q3 ) do
not show ” – ” indicator, it means the ” current phase ” lead than the ”
voltage phase “, the load character is capacitance.
7
Watt Hour ( Active Power Hour) : WH
DW-6195 + CP1201 Range
0.000 to 9.999 KWH 10.00 to 99.99 KWH 100.0 to 999.9 KWH 1.000 to 9.999 MWH
Resolution
0.001 KWH 0.01 KWH 0.1 KWH 0.001 MWH
System Accuracy ±(2%+0.008 KWH)
±(2%+0.08 KWH)
±(2%+0.8 KWH)
±(2%+0.008 MWH)
VA Hour ( Apparent Power Hour ) : SH
DW-6195 + CP1201 Range
0.000 to 9.999 KVAH 10.00 to 99.99 KVAH 100.0 to 999.9 KVAH 1.000 to 9.999
MVAH
Resolution
0.001 KVAH 0.01 KVAH 0.1 KVAH 0.001 MVAH
System Accuracy ±(2%+0.008 KVAH)
±(2%+0.08 KVAH)
±(2%+0.8 KVAH)
±(2%+0.008 MVAH)
VAR Hour ( Reactive Power Hour ) : QH
DW-6195 + CP1201 Range
Resolution
0.000 to 9.999 KVARH 10.00 to 99.99 KVARH 100.0 to 999.9 KVARH 1.000 to 9.999 MVARH
0.001 KVARH 0.01 KVARH 0.1 KVARH 0.001 MVARH
System Accuracy
±(2%+0.008 KVARH)
±(2%+0.08 KVARH)
±(2%+0.8 KVARH)
±(2%+0.008 MVARH)
Harmonics of AC voltage in Magnitude * Fundamental frequency 50 Hz, 60 Hz
DW-6195 + CP1201
Range
Resolution
1 to 20th 21 to 30th 31 to 50th
0.1 V
System Accuracy
± ( 2 % + 0.5 V )
± ( 4 % + 0.5 V )
reference
8
Harmonics of AC voltage in Percentage * Fundamental frequency 50 Hz, 60 Hz
DW-6195 + CP1201
Range
Resolution
1 to 20th 21 to 30th 31 to 50th
0.1 %
System Accuracy
± ( 2 % + 10 d )
± ( 4 % + 20 d )
reference
Harmonics of AC current in Magnitude * Fundamental frequency 50 Hz, 60 Hz
DW-6195 + CP1201
Range
Resolution
1 to 20th 21 to 30th 31 to 50th
0.001 A to 1 A
System Accuracy
± ( 2 % + 0.5 A )
± ( 4 % + 0.5 A )
reference
Harmonics of AC current in Percentage * Fundamental frequency 50 Hz, 60 Hz
DW-6195 + CP1201
Range
Resolution
1 to 20th 21 to 30th 31 to 50th
0.1 %
System Accuracy
± ( 2 % + 10 d )
± ( 4 % + 20 d )
reference
Peak value of ACV or ACA
DW-6195 + CP1201
Range
Resolution
ACV ( Peak to Peak ) 0.1 V to 1 V ACA ( Peak to Peak ) 0.001 A to 1 A
System Accuracy
± ( 5 % + 30 d )
9
Crest Factor of ACV or ACA
DW-6195 + CP1201
Range
Resolution
1.000 – 9.999
0.001
System Accuracy
± ( 5 % + 0.3 )
Total Harmonic Distortion
DW-6195 + CP1201
Range
Resolution
0 to 20 % 20.1 to 100 %
0.1 %
System Accuracy
± ( 2 % + 5 d )
± ( 6 % + 10 d )
FRONT PANEL DESCRIPTION
Fig. 1 10
3-1 Display
Fig. 2
3-2 1 3 ( Phase/wire ) key button
3-3 key button
3-4 key button
3-5 Hold key button
3-6 Backlight key button
3-7 Power key button
3-8 Exit key button
3-9 REC key button
3-10 A ( current ) range key button
3-11 Shift key button
3-12 Setup key button
3-13 Voltage input terminals
3-14A Current probe signal input sockets
3-14B Current probe power sockets
3-15 SD card socket
3-16 RS232 socket
11
3-17 Reset button 3-18 DC 9V power adapter socket 3-19 Battery Cover/Battery
compartment 3-20 Stand 3-21 Current Sense Jaw 3-22 Trigger 3-23A Current probe
signal plugs 3-23B Current probe power plug 3-24 Harmonic Analysis Left Key
3-25 Harmonic Key 3-26 Harmonic Analysis Right Key 3-27 Harmonic Analysis
V1,V2,V3, A1,A2,A3
Select Key 3-28 Harmonic Function Voltage or Current
Input Range 3-29 Power Measurement Key 3-30 Phase Diagram Key 3-31 Waveform of
Voltage and Current Key 3-32 Transient Key
12
MEASURING PREPARATION
4-1 The original screen
4-2 Entry the measurement Screen 1) The bottom right display of screen 1 will
show as ” SD
Check ” along with blinking while inserting SD CARD then disappears after
several seconds that indicates the data from SD CARD has been read completed.
2) The bottom right display of screen 2 will show as ” NO DISK ” along with
blinking when SD CARD is not inserted.
13
screen 1 ( 4-2 )
V12: 0.0 V
V1:
V23: 0.0 V
V2:
V31: 0.0 V
V3:
0.0 V
A1:
0.0 V
A2:
0.0 V
A3:
0.00 A 0.00 A 0.00 A
P1: -0.000 KW S1: 0.000KVA P2: -0.000 KW S2: 0.000KVA P3: -0.000 KW S3: 0.000KVA
Q1: -0.000 KVAR Q2: -0.000 KVAR Q3: -0.000 KVAR
P: PF1: PF: 1:
-0.000 KW S:
-0.00
PF 2:
0.00
PF H:
– 0.0°
2:
0.000KVA -0.00 0.00
– 0.0°
Q: -0.000 KVAR PF 3: -0.00
3:
– 0.0°
WH: 0.000 KWH QH: 0.000 KVARH
SH: FREQ:
0.000KVAH 0.0 Hz
CP1201 20A
34W SEC: 2
CT: 1 PT: 1
SD Check
screen 2 ( 4-2 )
V12: 0.0 V
V1:
V23: 0.0 V
V2:
V31: 0.0 V
V3:
0.0 V
A1:
0.0 V
A2:
0.0 V
A3:
0.00 A 0.00 A 0.00 A
P1: -0.000 KW S1: 0.000KVA P2: -0.000 KW S2: 0.000KVA P3: -0.000 KW S3: 0.000KVA
Q1: -0.000 KVAR Q2: -0.000 KVAR Q3: -0.000 KVAR
P: PF1: PF: 1:
-0.000 KW S:
-0.00
PF 2:
0.00
PF H:
– 0.0°
2:
0.000KVA -0.00 0.00
– 0.0°
Q: -0.000 KVAR PF 3: -0.00
3:
– 0.0°
WH: 0.000 KWH QH: 0.000 KVARH
SH: FREQ:
0.000KVAH 0.0 Hz
CP1201 20A
34W SEC: 2
CT: 1 PT: 1
NO DISK
14
4-3 The summary description of keyboard 1) POWER KEY ( 3-7, Fig. 1 ) :
Press the key to turn the instrument ON/OFF. 2) 1 3 ( phase/wire ) KEY ( 3-2,
Fig. 1 ) :
Press the key to select (1P/2W1P/3W3P/3W3P/4W) measurement function mode. 3) A
( current ) RANGE KEY ( 3-10, Fig. 1 ) : Press the key to change the current
range quickly. 4) REC KEY ( 3-9, Fig. 1 ) : The data record key for SD CARD.
5) HOLD KEY ( 3-5, Fig. 1 ) : Press the key to freeze the display reading. 6)
BACKLIGHT KEY ( 3-6, Fig. 1 ) : Press the key to switch Third-order brightness
selection. 7) SETUP KEY ( 3-12, Fig. 1 ) : Press the key to setup the function
before measuring. 8) EXIT KEY ( 3-8, Fig. 1 ) : Press the key to exit setting
screen. 9) SHIFT KEY ( 3-11, Fig. 1 ) Press the key to set the different
functions in setting screen. 10)UP () KEY ( 3-3, Fig. 1 ) : Press the key to
move the cursor up in setting screen. 11)DOWN () KEY ( 3-4, Fig. 1 ) : Press
the key to move the cursor down in setting screen. 12)Harmonic Analysis Left
Key ( 3-24, Fig. 1 ) 13)Harmonic Key ( 3-25, Fig. 1) 14)Harmonic Analysis
Right Key ( 3-26 , Fig. 1 ) 15)Harmonic Analysis V1,V2,V3, A1,A2,A3 Select Key
( 3-27, Fig. 1 ) 16)Harmonic Function Voltage or Current Input Range Select
Key ( 3-28, Fig. 1 ) 17)Power Measurement Key ( 3-29, Fig. 1 ) 18)Phase
Diagram Key ( 3-30, Fig. 1 ) 19)Waveform of Voltage and Current Key ( 3-31,
Fig. 1) 20)Transient Key ( 3-32, Fig. 1)
15
4-4 SETUP KEY description:
4-4-1 SHIFT KEY
- SHIFT 1 : When the symbols ” SETUP ” and ” SHIFT 1 ”
are appeared on up right display of screen 1 in the
meantime, and then use the or to select the
expect item.
- SHIFT 2 : When the symbols ” SETUP ” and ” SHIFT 2 ”
are appeared on up right display of screen 2 in the meantime, and then use the or to select ( 1P/2W 1P/3W3P/3W3P/4W ) in File Name function.
screen 1 ( 4-4 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delet File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range: 200A
Total Size:
1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year 2010
Month 11
Date 13
Minute 37
Second 25
screen 2 ( 4-4 )
Folder Name:
WTA01
File Name:
3P401001.XLS
REC Date: 2008-11-28 00:03:17
Sampling Time:
2
Trans Ref :
Delet File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
Free Size:
1946 MB
A
Range:
Total Size:
1946 MB
V
Range:
RS232 Out Sel:
PT:
1 : 1
V1
I1
CT:
1 : 1
S1
Q1
Beep:
ON
1
FREQ
SETUP SHIFT 2
220.0 V
CP1201 200A 200mV
P1 PF1
Year Month 2010 11
Date 13
Hour Minute
14
37
Second 25
16
4-4-2 The Setting Function menu
- Folder Name : Set the expect folder name for SD CARD, the range is between WTA01 and WTA10.
- File Name: Set the file name for SD CARD, It allows setting 50 filenames in this function.
- REC Date: Show the recorded time of existing files ( Year/Month/Date, Hour/Min./Sec. )
- Sampling Time : Set the sampling time from 2 to 7200 seconds. Delete File : To delete the existing data from SD CARD. SD Format : to Format SD CARD fast. PT : Set the potential transformer from 1 to 1000. CT : Set the current transformer from 1 to 600. Beep : Set to ON/OFF for buzzer. Clamp Type : Select the Clamp Type to CP-200, CP-1201,
CP-2000, CP-2011, CP-3000, CP-3001, CP-6001 or Other Type. RS232 out Sel. : Set RS232 output function, maximum up
to nine items can be selected to output. screen 1 screen 2. Year : Set the year. Month : Set the month. Date : Set the date. Hour : Set the hour. Minute : Set the minute. * Second : Set the second.
4-5 Setting function description before measuring
Press SETUP KEY to enter setting function screen, the selected item will be displayed in highlight.
17
4-5-1 Folder Name: Set the folder name for SD
screen 1 ( 4-5-1 )
Folder Name:
WTA01
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
Delet File:
0 % SDVP :
SD Format:
0 % Decimal:
Use Size:
388 KB Clamp Type:
Free Size:
1946 MB A
Range:
Total Size:
1946 MB V
Range:
RS232 Out Sel:
PT:
1 : 1
V1
I1
CT:
1 : 1
S1
Q1
Beep:
ON
1
FREQ
SETUP
220.0 V 10% Basic
CP1201 200A
200mV
P1 PF1
Year 2010
Month 12
Date 05
Hour 11
Minute 14
Second 49
screen 2 ( 4-5-1 )
Folder Name:
WTA01
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
Delet File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
Free Size:
1946 MB A
Range:
Total Size:
1946 MB V
Range:
RS232 Out Sel:
PT:
1 : 1
V1
I1
CT:
1 : 1
S1
Q1
Beep:
ON
1
FREQ
SETUP SHIFT 1
220.0 V
CP1201 200A
200mV
P1 PF1
Year 2010
Month 12
Date 05
Hour 11
Minute 14
Second 34
18
A : Folder Name range: WTA01 to WTA10. B : Press or to select the expect
folder number, the
number consists of ” 01 to 10 ” (as screen 1). C : Press or continuously at
least two seconds can
skip the numbers faster. D : Press SHIFT KEY once, the symbol ” SHIFT1″ will
appear on up right display, and then press to entry next setting function as
screen 2 (Folder Name File Name).
4-5-2 File Name: Set the file name for SD
A : The screen will show ” NO File ” indicator in REC Date option when the
selected file is new ( as screen 1 ).
B : The screen will show recording date and time in REC Date option when the
selected file has been recorded as screen 2.
screen 1 ( 4-5-2 )
Folder Name:
WTA03
File Name:
3P401001.XLS
REC Date: NO File
Sampling Time:
2
Trans Ref :
Delet File:
0 % SDVP :
SD Format:
0 % Decimal:
Use Size:
388 KB Clamp Type:
Free Size:
1946 MB A
Range:
Total Size:
1946 MB V
Range:
RS232 Out Sel:
PT:
1 : 1
V1
I1
CT:
1 : 1
S1
Q1
Beep:
ON
11
FREQ
SETUP
220.0 V 10% Basic CP1201
200A 200mV
P1 PF1
Year 2010
Month 11
Date 13
Hour 14
Minute 37
Second 25
19
screen 2 ( 4-5-2 )
Folder Name:
WTA03
File Name:
3P401001.XLS
REC Date: NO File
Sampling Time:
2
Trans Ref :
Delet File:
0 % SDVP :
SD Format:
0 % Decimal:
Use Size:
388 KB Clamp Type:
Free Size:
1946 MB A
Range:
Total Size:
1946 MB V
Range:
RS232 Out Sel:
PT:
1 : 1
V1
I1
CT:
1 : 1
S1
Q1
Beep:
ON
11
FREQ
SETUP
220.0 V 10% Basic CP1201
200A 200mV
P1 PF1
Year 2010
Month 11
Date 13
Hour 14
Minute 37
Second 25
C : File Name description : press or in screen 2 to select expect file number
from 001 to 050. Remark : When press or > 2 sec, the setting no. will change
fast. 1P201001 : 1P2 means one phase by two wires. 1P301001: 1P3 means one
phase by three wires, 3P301001 : 3P3 means three phases by three wires.
3P401001 : 3P4 means three phases by four wires. HAR01001 : HAR means
harmonic measurement. PHA01001 : PHA means phasor measurement. * TRA01001 :
TRA means transient measurement. Remark : Above file description, 01 means
folder number, 001 means file number.
D : The up right display will show ” SHIFT1 ” symbol while pressing SHIFT KEY
once in screen 2, and then press to enter next setting function as screen 3 (
File Name Sampling Time ).
20
E : The up right display will show ” SHIFT2 ” symbol
while pressing SHIFT KEY again in screen 4, at this time press or to select 1P/2W(1P2)1P/3W(1P3)
3P/3W(3P3) and 3P/4W(3P4) as screen 4.
F: One by one to press SHIFT KEY to select different
functions circularly.
screen 3 (4-5-2)
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delet File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year
Month
Date
Hour
Minute
Second
2010
11
13
14
37
25
screen 4 ( 4-5-2 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 2
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delet File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year 2010
Month 11
Date 13
Hour 14
Minute 37
Second 25
21
4-5-3 Sampling time: Set the data logger sampling time
for SD
A : When press SHIFT KEY once, the symbol ” SHIFT1 ”
will disappear on up right display, at this time press
or to adjust expect sampling time as screen 2,
adjusting numbers are from 2 to 7200 seconds.
Remark : When press or > 2 sec, the setting no. will change fast.
B : The up right display will show ” SHIFT1 ” symbol
while pressing SHIFT KEY again, and then press to
enter next setting function (Sampling Time Delete File)
screen 1 ( 4-5-3 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delet File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size:
1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year 2010
Month Date
11
13
Hour 14
Minute 37
Second 25
screen 2 ( 4-5-3 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2008-11-28 00:03:17
Sampling Time: Delet File:
2 0%
Trans Ref : SDVP :
220.0 V 10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size:
1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year 2010
Month Date
11
13
Hour 14
Minute 37
Second 25
22
4-5-4 Delete File: Delete the files for SD
A : The indicator ” Y or N ” will appear on right side display of the option
while pressing SHIFT KEY continuously at least two seconds, and now press the
display will show ” Y ” in highlight as screen 2, press SETUP KEY again to
confirm, the selected file (ex: 3P401001.XLS) will be erased then return to
screen 1, or else press SETUP KEY in ” N ” option to return to screen 1.
B : Press in screen 1 to enter next setting function (Delete File SD Format)
screen 1 ( 4-5-4 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size:
1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
23
screen 2 ( 4-5-4 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File: Y OR N
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1 1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
4-5-5 SD Format : Formatting function for SD CARD
A : The indicator ” Y or N ” will appear on right side display of the option
while pressing SHIFT KEY continuously at least two seconds, and press the
display will show ” Y ” in highlight as screen 2, press SETUP KEY again to
confirm to format SD CARD then return to screen 1, or else press SETUP KEY in
” N ” option return to screen 1.
B : Press in screen 1 to enter next setting function ( SD Format PT ).
24
screen 1 ( 4-5-5 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size:
1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
screen 2 ( 4-5-5 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format: Y OR N
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size:
1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
11
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
25
4-5-6 PT: Set the Potential Transformer
A : When press SHIFT KEY once, the symbol ” SHIFT1 ” will disappear as screen
2 at this time press or can adjust to expect PT values, the adjusting numbers
are from 1 to 1000. Remark : When press or > 2 sec, the setting no. will
change fast.
B : Press SHIFT KEY once again will return to screen 1 then press to enter
next setting function ( PT CT ).
screen 1 ( 4-5-6 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref : 220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
26
screen 2 ( 4-5-6 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
4-5-7 CT: Set the Current Transformer
A : When press SHIFT KEY once, the symbol ” SHIFT1 ” will disappear as screen
2 at this time press or can adjust to expect CT values, the adjusting numbers
are from 1 to 600. Remark : When press or > 2 sec, the setting no. will change
fast.
B : Press SHIFT KEY once again will return to screen 1 then press to enter
next setting function ( CT BEEP ).
27
screen 1 ( 4-5-7 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
screen 2 ( 4-5-7 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
28
4-5-8 Beep: Control the buzzer to ON/OFF
A : When press SHIFT KEY once the symbol ” SHIFT1 ” will disappear as screen
2, at this time press or to control the buzzer to ON/OFF.
B : Press SHIFT KEY once again will return to screen 1 then press to enter
next setting function ( BEEP Trans Ref type )
screen 1 ( 4-5-8 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
29
screen 2 ( 4-5-8 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2 Trans Ref : 220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range:
200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
4-5-9 Trans Ref: Nominal voltage for transient detection reference
A : When press SHIFT KEY once will disappear as screen 2, at this time press
or to adjust the voltage level to 50.0 V to 850.0 V.
B : Press SHIFT KEY once again will return to screen 1 then press to enter
next setting function ( Trans Ref SDVP ).
30
screen 1 ( 4-5-9 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: NO File
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
23 MB
Clamp Type:
CP1201
Free Size:
1904 MB
A
Range:
200A
Total Size:
1927 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 12
Date 14
Hour 09
Minute 22
Second 41
screen 2 ( 4-5-9 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: NO File
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
23 MB
Clamp Type:
CP1201
Free Size:
1904 MB
A
Range:
200A
Total Size:
1927 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 12
Date 14
Hour 09
Minute 22
Second 41
31
4-5-10 SDVP: Set up upper and low limits % of transient voltage detection
A : When press SHIFT KEY once will disappear as screen 2, at this time press or to adjust the voltage % value to 1% to 100%.
B : Press SHIFT KEY once again will return to screen 1 then press to enter next setting function ( SDVP Decimal ).
screen 1 ( 4-5-10 )
Folder Name:
WTA01
SETUP
File Name:
3P401026.XLS
SHIFT 1
REC Date: NO File
Sampling Time:
2
Trans Ref : 220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
23 MB
Clamp Type:
CP1201
Free Size:
1904 MB A
Range:
200A
Total Size:
1927 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 12
Date 14
Hour 09
Minute 22
Second 41
32
screen 2 ( 4-5-10 )
Folder Name:
WTA01
SETUP
File Name:
3P401026.XLS
REC Date: NO File
Sampling Time:
2
Trans Ref : 220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
23 MB
Clamp Type:
CP1201
Free Size:
1904 MB A
Range:
200A
Total Size:
1927 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 12
Date 14
Hour 09
Minute 22
Second 41
4-5-11 Decimal Type: set the Decimal type to Basic ( .) or Euro ( , )
The numerical data structure of SD card is default used the ” . ” as the
decimal, for example “20.6” “1000.53” . But in certain countries ( Europe …)
is used the ” , ” as the decimal point, for example ” 20,6 ” “1000,53”. Under
such situation, it should change the Decimal character at first.
A : When press SHIFT KEY once the symbol ” SHIFT1 ” will disappear as screen
2, at this time press or to select the Decimal type to ” Basic ” or ” Euro “.
33
- Basic type : The numerical data structure of SD card is default used the ” . ” as the decimal, for example “20.6” “1000.53” .
- Euro type : The numerical data structure of SD card is default used the ” , ” as the decimal, for example “20,6” “1000,53” .
B : Press SHIFT KEY once again will return to screen 1 then press to enter next setting function ( Decimal type Clamp type ).
screen 1 ( 4-5-11 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
SHIFT 1
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10% 10%
SD Format: Use Size:
0% 388 KB
Decimal: Clamp Type:
Basic CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
34
screen 2 ( 4-5-11 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0%
SDVP :
10% 10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
4-5-12 Clamp Type: set the clamp type to Lutron Clamp or other Clamp
A : When press SHIFT KEY once the symbol ” SHIFT1 ” will be disappeared and
show as screen 2, at this time press or to select the Lutron standard clamp or
other Clamp ( CP-200, CP-1201, CP-2000. CP-2011, CP-3000, CP-3001, CP-6001,
Other ).
B : When select the different Clamp type, the V range and the A range will
show the corresponding value.
C : Press SHIFT KEY once again will return to screen 1 then press to enter
next setting function ( Clamp Type A range ).
35
screen 1 ( 4-5-12 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0 % SDVP :
10% 10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
screen 2 ( 4-5-12 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref :
220.0 V
Delete File:
0 % SDVP :
10% 10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
36
4-5-13 A range Setting ( Current range Setting )
A : When press SHIFT KEY once the symbol ” SHIFT1 ” will be disappeared and
show as screen 2, at this time press or to select A range to 20A to 2000A, 30A
to 3000A or 60A to 6000A. * The setting value should accoding your Clamp type.
- The CP-200 clamp can set 20A, 200A. The CP-1201 clamp can set 20A, 200A, 1200A. The CP-2000 clamp can set 20A, 200A, 2000A. The CP-2011 clamp can set 200A, 2000A. The CP-3000, CP-3001 clamp can set 30A, 300A, 3000A. The CP-6001 clamp can set 60A, 600A, 6000A. The Other clamp can set 20A, 200A, 2000A, 30A 300A, 3000A.60A, 600A, 6000A.
Attention : The meter’s A range ( Current range ) value should same as the Clamp’s current selecting range value.
B : Press SHIFT KEY once again will return to screen 1 then
press to enter next setting function ( A Range V range ).
screen 1 ( 4-5-13 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time:
2 Trans Ref :
220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal: Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A Range:
200A
Total Size:
1946 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
37
screen 2 ( 4-5-13 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2 Trans Ref :
220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal: Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
4-5-14 V range Setting ( Voltage range Setting )
A : When press SHIFT KEY once the symbol ” SHIFT1 ” will be disappeared and show as screen 2, at this time press or to select V range to 200mV, 300mV, 500mV, 1V, 2V, 3V. * The setting function only available for the Other clamp.
- The V range value of CP-200, CP-1201 will default to 200mV, it can not be adjusted. The V range value of CP-2000 will default to 2V, it can not be adjusted. The V range value of CP-2011, CP-3000, CP-3001, CP-6001, will default to 3V, it can not be adjusted.
B : Press SHIFT KEY once again will return to screen 1 then press to enter next setting function ( A Range RS232 OUT SEL ).
38
screen 1 ( 4-5-14 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref : 220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
screen 2 ( 4-5-14 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2017-11-28 00:03:17
Sampling Time:
2
Trans Ref : 220.0 V
Delete File:
0%
SDVP :
10%
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
39
4-5-15 RS232 Out Sel setting
A : When press SHIFT KEY continuously at least two seconds as screen 2 and now
press or to select the item that intend to output, maximum up to nine items,
when the cursor stops on the selected item and then press SETUP KEY again, the
selected item will be displayed in highlight.
B : Press SHIFT KEY it can change the screen page from Screen 2 Screen 5.
C : If the selected items are over nine, the low right display will show
indicator ” full ” as screen 6.
D : After the selecting is completed, press SHIFT KEY continuously at least
two seconds again will return to screen 1 and show all the selected items at
the same time.
E : Press in screen 1 to enter next setting function ( RS232 Out Sel Year )
screen 1 ( 4-5-15 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2017-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range:
200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year 2010
Month 11
Date 13
Hour 14
Minute 37
Second 25
40
screen 2 ( 4-5-15 )
RS232 OUTPUT SELECT
1. V12 2. V23 3. V31 4. V1 5. V2 6. V3 7. I1 8. I2 9. I3 10. P1 11. P2
12. P3 13. P 14. S1 15. S2 16. S3 17. S 18. Q1 19. Q2 20. Q3 21. Q 22. PF1
23. PF2 24. PF3 25. PF 26. PFH 27. 1 28. 1 2 29. 1 3 30. WH 31. SH 32. QH 33. FREQ
screen 3 ( 4-5-15 )
RS232 OUTPUT SELECT
34. H01 35. H02 36. H03 37. H04 38. H05 39. H06 40. H07 41. H08 42. H09 43. H11 44. H01
45. H12 46. H13 47. H14 48. H15 49. H16 50. H17 51 H18 52 H19 53. H20 54. H21 55. H22
56 H23 57 H24 58 H25 59 H26 60 H27 61 H28 62 H29 63 H30 64 H31 65 H32 66 H33
41
screen 4 ( 4-5-15 )
RS232 OUTPUT SELECT
67. H34 68. H35 69. H36 70. H37 71. H38 72. H39 73. H40 74. H41 75. H42 76. H43 77. H44
78. H45 79. H46 80 H47 81. H48 82. H49 83. H50 84. THD 85. Vpp 86. CFV 87. App 88 CFA
89 V12 90 V23 91 V31 92 V1 93 V2 94 V3 95 A1 96 A2 97 A3 98 AveV 99 AveA
screen 5 ( 4-5-15 )
RS232 OUTPUT SELECT
Vn
An
dV
VUR
Vd0
Vd2
dA
AUR
Ad0
Ad2
42
screen 6 ( 4-5-15 )
RS232 OUTPUT SELECT
1. V12 2. V23 3. V31
4. V1 5. V2 6. V3 7. I1 8. I2 9. I3 10. P1 11. P2
12. P3 13. P 14. S1 15. S2 16. S3 17. S 18. Q1 19. Q2 20. Q3 21. Q 22. PF1
23. PF2 24. PF3 25. PF 26. PFH 27. 1 28. 1 2 29. 1 3 30. WH 31. SH 32. QH 33. FREQ
FULL
4-5-16 Year/Month/Date/Hour/Minute/Second setting
A : When press SHIFT KEY once the symbol ” SHIFT1″ will disappear as screen 2,
at this time press or to adjust expect numbers, and press or continuously at
least two seconds can skip the numbers faster.
B : When press SHIFT KEY once, the symbol ” SHIFT1″ will appear as screen 1,
at this time press to enter next setting function ( Year Month ).
C : The settings about ( Month Date ), (Date Hour ), (Hour Minute ), ( Minute
Second ) are same as above step A and step B.
43
D : In this setting function ( Year Minute ), press or in addition to adjust
the numbers, and the setting value will also be saved during the adjusting.
E : In the function of setting ” second “, press or to adjust numbers. at this
point the number of second is at a standstill condition and then press setup
key that will save setting value and also start counting function of ” second
“.
screen 1 ( 4-5-16 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time:
2 Trans Ref : 220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range:
200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
44
screen 2 ( 4-5-16 )
Folder Name: WTA01
SETUP
File Name: 3P401001.XLS
REC Date: 2008-11-28 00:03:17
Sampling Time:
2 Trans Ref : 220.0 V
Delete File:
0 % SDVP :
10%
SD Format:
0 % Decimal:
Basic
Use Size:
388 KB Clamp Type:
CP1201
Free Size:
1946 MB A
Range:
200A
Total Size:
1946 MB V
Range:
200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep: ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
4-5-17 When all settings are completed, press EXIT KEY to return measuring screen.
4-5-18 The descriptions about SD CARD memory space
A : Use Size – To show the space data numbers that have been used.
B : Free Size – To show the data numbers of balance space. C : Total Size – To
show the data numbers of total space. D : Typical SD CARD and SDHC both can be
used with the
instrument, except the SD CARD memory size is less than 32MB.
4-5-19 RESET KEY : Press this key to reboot the instrument
45
MEASURING PROCEDURES
5-1 12W ( one phase by two wires ) measurement
A : Diagram
SCREEN 1 ( 5-1 )
B : Operation Instructions: B-1 : Power on the instrument by pressing POWER
KEY, and then press 13 KEY to select the 12W system, At the time, display will
show 12W connect diagram approx 4 sec. and the selected name of system will be
appeared on bottom left display of screen 2. B-2 : Connect the line voltage
L1, Vn ( Neutral ) to V1 and N terminals of the instrument. B-3:Place the
conductor of CP-1201(A1)to A1 as screen 1. B-4: Connect the output of clamp
meter ” CP-1200(A1) ” to A1 terminal of the instrument. B-5: The related
measuring factors will be appeared on display, about the instruction of factor
please refer appendix 1 ( 5-16, page 68 ). Remark: During connection ,If want
to check connect Correct or not,please press and hold the “” key, display will
show 12W connect diagram,when release the “” key , will back to measurement.
46
screen 2 ( 5-1 )
V 1 : 0.0
V
A 1 : 0.00
A
P1 : – 0.000KW S1: 0.000KVA Q1: – 0.000KVAR
WH 0.000KWH SH 0.000KVAH QH 0.000KVARH
P F1 P FH 1: :
: – 0.00 : 0.00
– 0.0°
F R E Q
: 50.1
Hz
CP1201 20A
12W
SEC: 2
CT: 1
PT: 1
5-2 13W (one phase by three wires) measurement A : Diagram
screen1 ( 5-2 )
47
B : Operation Instructions:
B-1 : Power on the instrument by pressing POWER KEY,
and then press 13 KEY to select the 13W system,At the
time, display will show 13W connect diagram approx 4 sec.,
and the selected name of system will be appeared on bottom
left display of screen 2.
B-2 : Connect the line voltage L1, L2 and Vn (Neutral) to
V1, V2 and N terminals of the instrument.
B-3 : Place the conductor of CP-1201(A1), CP-1201(A2)
hook to A1 and A2 as screen 1.
B-4 : Connect the outputs of clamp meter CP-1201(A1)CP-1201(A2) to A1 and A2 terminals of
the instrument.
B-5 : The related measuring factors will be appeared on
display, about the instruction of factor please refer
appendix 1 ( 5-16, page 68 ).
Remark:
During connection ,If want to check connect Correct or not,
please press and hold the “” key, display will show 13W
connect diagram,when release the “” key , will back to
measurement.
screen 2 ( 5-2 )
V1 :
0.0
V
P 1 : – 0.000KW
V2 :
0.0
V
P 2 : – 0.000KW
A1 :
0.00
A
S1 :
0.000KVA
A2 :
0.00
A
S2 :
0.000KVA
Q1 : – 0.000KVAR
Q2 : – 0.000KVAR
P: 0.000 KW
PF1: – 0.00
PFH:
0.00
S: 0.000 KVA PF2: – 0.00 1: – 0.0°
Q: PF: 2: –
0.000 KVAR 0.00 0.0°
WH: 0.000 KWH QH: 0.000 KVARH
SH: FREQ:
0.000 KVAH 50.0 Hz
CP1201 20A
13W
SEC: 2
CT: 1
PT: 1
48
5-3 33W (three phases by three wires) measurement
A : Diagram
screen 1 ( 5-3 )
B : Operation Instructions: B-1 : Power on the instrument by pressing POWER
KEY, and then press 13 KEY to select the 33W system,At the time, display will
show 33W connect diagram approx. 4 sec. and the selected name of system will
be appeared on bottom left display of screen 2. B-2: Connect the line voltage
L1, L2 and L3 to V1, V2 and V3 terminals of the instrument. B-3: Place the
conductor of CP-1201(A1), CP-1201(A2), CP-1201(A3) hook to A1, A2 ,A3 as
screen 1. B-4 : Connect the outputs of clamp meter CP-1201(A1) , CP-1201(A2),
CP-1201(A3) to A1, A2, A3 terminals of the instrument. B-5: The related
measuring factors will be appeared on display, about the instruction of factor
please refer appendix 1 ( 5-16, page 68 ). Remark: During connection ,If want
to check connect Correct or not, please press and hold the “” key, display
will show 33W connect diagram,when release the “” key , will back to
measurement.
49
screen 2 ( 5-3 ) V1 1 : 0.0 V V2 3 : 0.0 V V3 1: 0.0 V
A1 : A2 : A3 :
0.00 A 0.00 A 0.00 A
P – 0.000 KW
S
0.000 KVA
Q
0.000 KVAR
PF:
0.00
P F H : 0.00
WH: 0.000 KWH QH: 0.000 KVARH
SH: FREQ:
0.000 KVAH 50.0 Hz
CP1201 20A
33W
SEC: 2
CT: 1
5-4 34W (three phases by four wires) measurement
A : Diagram
PT: 1
screen 1 ( 5-4 ) 50
B: Operation Instructions:
B-1 : Power on the instrument by pressing POWER KEY,
and then press 13 KEY to select the 34W system,At the
time, display will show 34W connect diagram approx. 4 sec.
and the selected name of system will be appeared on bottom
left display of screen 2.
B-2 : Connect the line voltage L1, L2, L3 and Vn to
V1, V2, V3 and N terminals of the instrument. B-3 : Place the conductor of CP-1201(A1), CP-1201(A2)
CP-1201(A3) hook to A1, A2, A3 as screen 1.
B-4 : Connect the outputs of clamp meter
CP-1201(A1), CP-1201(A2), CP-1201(A3) to A1A2A3 terminals of the instrument.
B-5 : The related measuring factors will be appeared
on display, about the instruction of factor please refer
appendix 1 ( 5-16, page 68 ).
Remark:
During connection ,If want to check connect Correct or not,
please press and hold the “” key, display will show 34W
connect diagram,when release the “” key , will back to
measurement.
screen 2 ( 5-4 )
V12:
0.0 V V1:
0.0 V A1:
0.00 A
V23:
0.0 V V2:
0.0 V A2:
0.00 A
V31:
0.0 V V3:
0.0 V A3:
0.00 A
P1: -0.000 KW
S1:
0.000 KVA Q1: -0.000 KVAR
P2: -0.000 KW
S2:
0.000 KVA Q2: -0.000 KVAR
P3: -0.000 KW
S3:
0.000 KVA Q3: -0.000 KVAR
P : PF1: PF: 1:
-0.000 KW – 0.00
0.00 – 0.0°
S: PF2: PFH:
2:
0.000 KVA – 0.00
0.00 – 0.0°
Q: -0.000 KVAR PF3: 0
3: -0.0°
WH: QH:
0.000 KWH 0.000 KVARH
SH:
0.000 KVAH
FREQ: 0.0
Hz
CP1201 20A
34W
SEC: 2
CT: 1
PT: 1
51
5-5 The CT and PT measurement
A : Diagram
screen 1 ( 5-5 )
B : Operation Instructions B-1 : Power on the instrument by pressing POWER
KEY, and then press 13 KEY to select the 34W system,At the time, display will
show 34W connect diagram approx. 4 sec. the selected name of system will be
appeared on bottom left display of screen 2. B-2 : Connect the line voltage
L1, L2, L3 and Vn to V1, V2, V3 and N terminals of the instrument. B-3 : Place
the conductor of CP-1201(A1), CP-1201(A2), CP-1201(A3) hook to A1, A2 , A3 as
screen 1. B-4: Connect the outputs of clamp meter CP-1201(A1), CP-1201(A2),
CP-1201(A3) to A1, A2, A3 terminals of the instrument. B-5: The related
measuring factors will be appeared on display, about the instruction of factor
please refer appendix 1 ( 5-16, page 68 ). Remark: During connection ,If want
to check CT and PT measurement connect Correct or not, please press and hold
the “”and ” ” key, display will show CT and PT measurement connect
diagram,when release the ” ” and ” ” key , will back to measurement .
52
screen 2 ( 5-5 )
V12:
0.0 V V1:
V23:
0.0 V V2:
V31:
0.0 V V3:
0.0 V A1: 0.0 V A2:
0.0 V A3:
0.00 A 0.00 A 0.00 A
P1:
-0.000 KW S1:
0.000 KVA Q1: – 0.000 KVAR
P2:
-0.000 KW S2:
0.000 KVA Q2: – 0.000 KVAR
P3:
-0.000 KW S3:
0.000 KVA Q3: – 0.000 KVAR
P : PF1:PF: 1: –
-0.000 KW S:
– 0.00
PF2:
– 0.00
PFH:
-0.0°
2:
0.000 KVA Q: – 0.000 KVAR
– 0.00
PF3: – 0.00
0.00
– 0.0°
3: – 0.0°
WH: QH:
0.000 KWH 0.000 KVARH
SH: 0.000 KVAH
FREQ: 0.0
Hz
CP1201 20A
34W
SEC: 2
CT: 1
PT: 1
5-6 ZERO adjustment for Watt Hour If reset the ” Exit key button ” ( 3-8, Fig. 1 ) continuously and > 6 seconds, the measurement value of ” WH “, ” SH “, ” QH ” will reset to Zero value.
53
5-7 Harmonic Function Measurement 1) Press ” Harmonic Key ” ( 3-25, Fig. 1 )
will enter
the Screen 1. 2) Press ” V/A 1. 2. 3 Key ” ( 3-27, Fig. 1 ) will enter
the Screen 2. 3) If the wave show the distortion, Press ” V/A range Key ”
( 3-28, Fig. 1 ), switch to VH or AH to let the waveform not existing
distortion as Screen 3, Screen 4. 4) Press ” Left Key ” ( 3-24, Fig. 1) or ”
Right Key ” ( 3-26, Fig. 1) will show the voltage or current Nth harmonic
value Screen 1 ( 5-7 )
54
55
5-8 Graphic Phasor Diagram 1) Press ” Phase Diagram Key ” ( 3-30, Fig. 1 )
will display
the phasor diagram as the Screen 1 ( 5-8 ). If the wrong phase sequence, will
display the phasor diagram as the Screen 2 ( 5-8 ). 2) Description of phasor
diagram : a. V1, V2, V3 :
Phase voltages in phasor format with respect to V1. A1, A2, A3 : Line currents
in phasor format with respect to A1. b. AVE : Average of the line voltages
V12, V23 and V31 an the line current A1, A2 and A3. c. AVn : Calculated
voltage and current of neutral with respect to ground.
56
d. dV% : Historical maximum % value of ( Max. ( V1, V2, V3 ) – Min. ( V1, V2,
V3 ))/ Min. ( V1, V2, V3 ) * 100%
e. VUR : Voltage unbalance ratio. f. do2 ( do, d2 ) :
- do – The first number is Zero Sequence Unbalance Ratio in % ( d0 ) of voltage or current.
- d2 – The second number is the Negative Sequence Unbalance Ratio in % ( d2 ) of voltage or current.
g. dA% : Historical maximum % value of ( Max. ( A1, A2, A3 ) – Min. ( A1, A2, A3 ))/ Min. ( A1, A2, A3 ) * 100%
h. AUR : Current unbalance ratio.
Screen 1 ( 5-8 )
57
Screen 2 ( 5-8 )
5-9 Voltage/Current Waveform 1) Press ” Waveform Key ” ( 3-31, Fig. 1 ) will
enter to
Voltage Waveform screen as Screen 1, then Press ” 1/3 Key ” ( 3-2, Fig. 1 )
once in sequence will switch the Voltage waveform from V1 to V2, V3. 2) Press
” Waveform Key ” ( 3-31, Fig. 1 ) once again will enter to Current Waveform
screen as Screen 2, then ” 1/3 Key ” ( 3-2, Fig. 1 ) once in sequence will
switch the Current waveform from A1 to A2, A3. 3) Press ” Waveform Key ” (
3-31, Fig. 1 ) once again will enter to Voltage/Current Waveform screen as
Screen 3, then press ” 1/3 Key ” ( 3-2, Fig. 1 ) once in sequence will switch
the Voltage/Current waveform from V1/A1 to V2/A2, V3/A3.
58
Screen 1 ( 5-9 ) Screen 2 ( 5-9 )
59
Screen 3 ( 5-9 )
5-10 Transient Capture ( Dips, Swells, Outage ) 1) If intend to make the
Transient Capture measurement it
should set the transient voltage level ( high level, low level ) at first ,
the setting procedures, please refere to chapter 4-5-9 and chapter 4-5-10. 2)
Press ” Transient Key ” ( 3-32, Fig. 1 ) will enter to Transient Capture
screen, insert the SD memory card then press the ” REC Button ” ( 3-9, Fig. 1
) will make the measurement, refer as the Screen 1 3) Definition : a. SWELL :
Vrms > ( Vref + ( Vref SDVP% ) ) b. DIP
Vrms < ( Vref – ( Vref SDVP% ) ) c. OUTAGE
Vrms < 30 V to 40 V.
60
d. Line item : V is the code show the all phase V1, V2, V3 ever happen the
transient event. V1, V2, V3 is the code that show each phase V1, V2, V3 ever
happen the transient event. * Refer to Screen 2.
4) Press the ” REC Button ” will exit the Transient Capture function as Screen
3.
5) One screen can show 13 transient events. One file can record 99 transient
events. When the transient even more than 13 no, then press the ” Button ” , ”
Button ” can show more transient events. If the transient events less than 13
no., ” Button ” , ” Button ” are disable. Screen 1 ( 5-10 )
Remark : When press ” 1 3 Button ” ( 3-2, Fig. 1 ) once in sequence, it can
switch to the the transient measurement of different Wire connections such as
1P2W, 1P3W, 3P3W, 3P4W.
61
Screen 2 ( 5-10 ) Screen 3 ( 5-10 )
62
5-11 Data Logger Function
Remark : Please do the following , then execution data logger function. 1.
First connect the mains adaptor, with no batteries installed. 2. Check that
the unit power on. 3. then install the batteries, as a backup in case there is
a power
failure during data logging. 4. After installing the battery, remove the
adaptor and confirm that the
meter action is normal after installing the battery. If no problem, connect
the adaptor to the meter. 5. Then start data logging.
A : Press REC KEY once to start the data record function.
A-1 : If the bottom right shows as ” Change Card “, it
indicates the memory space is already full either or the
SD CARD exist some wrong.
A-2 : If the SD CARD is normal, the data logger function
will start to be executed.
V12: 0.0
V
V1:
0.0
V
A1:
0.00
A
V23: 0.0
V
V2:
0.0
V
A2:
0.00
A
V31: 0.0
V
V3:
0.0
V
A3:
0.00
A
P1: -0.000 KW S1: P2: -0.000 KW S2: P3: -0.000 KW S3:
0.000 KVA 0.000 KVA 0.000 KVA
Q1: – 0.000 KVAR Q2: – 0.000 KVAR Q3: – 0.000 KVAR
P : -0.000 KW S:
0.000 KVA Q:
– 0.000 KVAR
PF1: – 0.00 PF2:
– 0.00
PF3:
– 0.00
PF:
0.00 PFH:
0.00
1: – 0.0°
2: – 0.0°
3: – 0.0°
WH: QH:
0.000 KWH 0.000 KVARH
SH:
0.000 KVAH
FREQ: 0.0 Hz
CP1201 20A
34W
SEC: 2
CT: 1
Change
PT: 1
Card
B : The bottom right display will show the recorded data points. B-1 : Each file can record up to 30,000 data points as screen 1 when the record points exceed 30,000 points, system will create a new file automatically. (For example, WTA01001.XLS will be replaced by WTA01002.XLS) B-2 : While pressing REC KEY once, the data logger function will stop to execute, the record points will disappear on bottom right display as screen 2.
63
screen 1 ( 5-11 B )
V12: 0.0 V V1:
0.0 V A1:
0.00
A
V23: 0.0 V V2:
0.0 V A2:
0.00
A
V31: 0.0 V V3:
0.0 V A3:
0.00
A
P1: -0.000 KW S1: P2: -0.000 KW S2: P3: -0.000 KW S3:
0.000 KVA 0.000 KVA 0.000 KVA
Q1: – 0.000 KVAR Q2: – 0.000 KVAR Q3: – 0.000 KVAR
P : -0.000 KW S:
0.000 KVA Q:
– 0.000 KVAR
PF1: – 0.00 PF2: – 0.00
PF3: – 0.00
PF:
0.00 PFH:
0.00
1: – 0.0°
2: – 0.0°
3: – 0.0°
WH: QH:
0.000 KWH 0.000 KVARH
SH:
0.000 KVAH
FREQ: 0.0 Hz
CP1201 20A
34W
SEC: 2
CT: 1
REC
PT: 1
9
screen 2 ( 5-11 B )
V12: 0.0 V V1:
0.0 V A1:
0.00
A
V23: 0.0 V V2:
0.0 V A2:
0.00
A
V31: 0.0 V V3:
0.0 V A3:
0.00
A
P1: -0.000 KW S1: P2: -0.000 KW S2: P3: -0.000 KW S3:
0.000 KVA 0.000 KVA 0.000 KVA
Q1: – 0.000 KVAR Q2: – 0.000 KVAR Q3: – 0.000 KVAR
P : -0.000 KW S:
0.000 KVA Q:
– 0.000 KVAR
PF1: – 0.00 PF2: – 0.00
PF3: – 0.00
PF:
0.00 PFH:
0.00
1: – 0.0°
2: – 0.0°
3: – 0.0°
WH: QH:
0.000 KWH 0.000 KVARH
SH:
0.000 KVAH
FREQ: 0.0 Hz
CP1201 20A
34W
SEC: 2
CT: 1
PT: 1
64
5-12 Data HOLD Function
A: During the measurement, press HOLD KEY once, the
bottom right display will show “HOLD symbol as screen 1.
B: Press the HOLD KEY once will disable the Data HOLD
function and the “HOLD” symbol will disappear in the
meantime
screen 1 ( 5-12 )
V12: 0.0
V
V1:
0.0
V
A1:
0.00
A
V23: 0.0
V
V2:
0.0
V
A2:
0.00
A
V31: 0.0
V
V3:
0.0
V
A3:
0.00
A
P1: -0.000 KW S1: P2: -0.000 KW S2: P3: -0.000 KW S3:
0.000 KVA 0.000 KVA 0.000 KVA
Q1: – 0.000 KVAR Q2: – 0.000 KVAR Q3: – 0.000 KVAR
P : -0.000 KW S:
0.000 KVA Q:
– 0.000 KVAR
PF1: – 0.00 PF2:
– 0.00
PF3:
– 0.00
PF:
0.00 PFH:
0.00
1: – 0.0°
2: – 0.0°
3: – 0.0°
WH: 0.000 KWH QH: 0.000 KVARH
SH:
0.000 KVAH
FREQ: 0.0 Hz
CP1201 20A
34W
SEC: 2
CT: 1
PT: 1
HOLD
screen 2 ( 5-12 )
V12: 0.0
V
V1:
0.0
V
A1:
0.00
A
V23: 0.0
V
V2:
0.0
V
A2:
0.00
A
V31: 0.0
V
V3:
0.0
V
A3:
0.00
A
P1: -0.000 KW S1: P2: -0.000 KW S2: P3: -0.000 KW S3:
0.000 KVA 0.000 KVA 0.000 KVA
Q1: – 0.000 KVAR Q2: – 0.000 KVAR Q3: – 0.000 KVAR
P : -0.000 KW S:
0.000 KVA Q:
– 0.000 KVAR
PF1: – 0.00 PF2:
– 0.00
PF3:
– 0.00
PF:
0.00 PFH:
0.00
1: – 0.0°
2: – 0.0°
3: – 0.0°
WH: 0.000 KWH QH: 0.000 KVARH
SH:
0.000 KVAH
FREQ: 0.0 Hz
CP1201 20A
34W
SEC: 2
CT: 1
PT: 1
65
5-13 BACKLIGHT KEY Depending on the brightness of the environment, can choose from 3rd-order LCD Backlight brightness.
5-14 A Range ( Current Range ) KEY function a) The A Range ( Current Range )
function key is used to
change the current range quickly. b) Press A RANGE KEY once will entry to
screen
as following ” screen 1 ( 5-14 ) ” , it is the same screen as ” screen 2 (
4-5-13 ) , page 38 “. c) The detail Current range Setting procedures, please
refer to section ” 4-5-13 A range Setting ( Current range Setting ), page 37 ”
Remark : The function of the ” A Range ( Current Range ) key ” is available for the Clamp Type, A Range, V Range setting only.
screen 1 ( 5-14 )
Folder Name: WTA01
SETUP
File Name: 3P401001.XLS
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
Trans Ref :
220.0 V
Delete File:
0%
SDVP
10%
0
SD Format:
0%
Decimal:
Basic
Use Size:
388 KB
Clamp Type:
CP1201
Free Size:
1946 MB
A
Range:
200A
Total Size: 1946 MB
V
Range: 200mV
RS232 Out Sel:
PT:
1 : 1
V1
I1
P1
CT:
1 : 1
S1
Q1
PF1
Beep:
ON
1
FREQ
Year Month 2010 11
Date 13
Hour 14
Minute 37
Second 25
66
5-15 The LOWBAT screen: as show on lower right display of the following screen.
V12: 0.0 V V1:
0.0 V A1:
0.00
A
V23: 0.0 V V2:
0.0 V A2:
0.00
A
V31: 0.0 V V3:
0.0 V A3:
0.00
A
P1: -0.000 KW S1: P2: -0.000 KW S2: P3: -0.000 KW S3:
0.000 KVA 0.000 KVA 0.000 KVA
Q1: – 0.000 KVAR Q2: – 0.000 KVAR Q3: – 0.000 KVAR
P : -0.000 KW S:
0.000 KVA Q:
– 0.000 KVAR
PF1: – 0.00 PF2: – 0.00
PF3: – 0.00
PF:
0.00 PFH:
0.00
1: – 0.0°
2: – 0.0°
3: – 0.0°
WH: QH:
0.000 KWH 0.000 KVARH
SH:
0.000 KVAH
FREQ: 0.0 Hz
CP1201 20A
34W
SEC: 2
CT: 1
LOWBAT PT: 1
Remark: * During power on , when battery voltage < 7.0 V , the power analyzer
meter will show as 5-15 The LOWBAT screen .
- During power off ,press power button want to power on the meter, if the battery voltage < 7.0 V , the power analyzer meter will auto power off again.
- When the meter is turned on the screen stops and cannot continue, At this time, please check the battery power, If not enough 7.0 V, please replace the battery.
67
5-16 Appendix 1 V12, V23, V31 : Line Voltage V1, V2, V3 : Phase Voltage
A1, A2, A3 : Line Current P1, P2, P3 : True Power of each phase. (W) S1,
S2, S3 : Apparent Power of each phase. (VA) Q1, Q2, Q3 : Reactive Power of
each phase (VAR) P: Total True Power (W) S: Total Apparent Power (VA) Q:
Total Reactive Power (VAR) PF1, PF2, PF3 : Power Factor of each phase PF :
Total Power Factor PFH : Long Term Average Power Factor ( WH/SH ) 1, 2, 3
: Phase Angle of each phase WH : Watt Hour SH : Apparent Power Hour QH :
Reactive Power Hour 12W : One phase by two wires 13W : One phase by three
wires 33W : Three phases by three wires 34W : Three phases by four wires
SEC : The sampling time of data logger CT : Current transformer * PT :
Potential transformer
68
MAINTENANCE
Caution :
Remove test leads before opening the battery cover or housing case !
6-1 Cleaning
Caution :
Cleaning – Only use the dry cloth to clean the plastic case !
6-2 Replacement of batteries 1) When Display show the ” LOWBAT ” indicator (
ref. 5-15
page 67 ), it should change the batteries. 2) open the ” Battery Cover ” (
3-19, Fig. 1 ) away from the
instrument and remove the battery. 3) Replace with batteries ( DC 1.5V,
AA/UM-3 battery
X 8 PCs ) and reinstate the cover.
- When install the batteries, should make attention the battery polarity.
- Make sure the battery cover is secured after changing the batteries.
69
7. RS232 PC SERIAL OUTPUT
The instrument is provided an 3.5 mm dia. phone socket ( 3-16, Fig. 1 ) for
RS232 computer interface socket.
The connector output is a 16 digits data stream which can be utilized to the
user’s specific application.
A RS232 lead with the following connection will be required to link the
instrument with the PC serial input.
Meter (3.5 mm jack plug)
PC (9W ‘D” Connector)
Center Pin……………………………..P…in…4…
Ground/shield…………………………….P..i.n…2…
Pin 5
2.2 K resister
The 16 digits data stream will be displayed in the following format :
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
70
Each digit indicate the following status :
D15 D14 D13 D12 & D11
D10 D9 D8 to D1 D0
Start Word
4
1 CH = 1
2 CH = 1 to 2 3 CH = 1 to 3
4 CH = 1 to 4 5 CH = 1 to 5 6 CH = 1 to 6
7 CH = 1 to 7 8 CH = 1 to 8 9 CH = 1 to 9
Annunciator for Display
03=%
B9 = MACA
D0 = MW/Hr
31=HZ
C0 = MW
D1 = GW/Hr
32=DEGREE C1 = GW
D2 = TW/Hr
48=K WATT C2 = TW
D3 = KVA/Hr
50=ACV
C3 = MVA
D4 = MVA/Hr
52=ACA
C4 = GVA
D5 = GVA/Hr
64=KVA
C5 = TVA
D6 = TVA/Hr
65=KW/HR
C6 = KVAR
D7 = KVAR/Hr
B6 = KACV
C7 = MVAR D8 = MVAR/Hr
B7 = MACV
C8 = GVAR
D9 = GVAR/Hr
B8 = KACA
C9 = TVAR
E0 = TVAR/Hr
Polarity
0 = Positive
1 = Negative
Decimal Point(DP), position from right to the left
0 = No DP, 1= 1 DP, 2 = 2 DP, 3 = 3 DP
Display reading, D1 = LSD, D8 = MSD
For example :
If the display reading is 1234, then D8 to D1 is :
00001234
End Word
RS232 setting
Baud rate
9600
Parity
No parity
Data bit no. 8 Data bits
Stop bit
1 Stop bit
71
8. Download the saving data from the SD card to the computer ( EXCEL software )
- After execute the Data Logger function, take away the SD card out from the ” SD card socket ” ( 3-15, Fig. 1 ).
- Plug in the SD card into the Computer’s SD card slot ( if your computer build in this installation ) or insert the SD card into the ” SD card adapter “. then connect the ” SD card adapter ” into the computer.
- Power ON the computer and run the ” EXCEL software “. Down load the saving
data file ( for example the file name : 3P401001.XLS, 1P201001.XLS,
1P301001.XLS, 3P301001.XLS……..) from the SD card to the computer. The saving
data will present into the EXCEL software screen ( for example as following
EXCEL data screens ) , then user can use those EXCEL data to make the further
Data or Graphic analysis usefully.
EXCEL data screen 1 ( for example )
72
EXCEL data screen 2 ( for example ) EXCEL data screen 3 ( for example ) EXCEL
data screen 4 ( for example )
73
EXCEL data screen 5 ( for example ) EXCEL data screen 6 ( for example )
*+
EXCEL graphic screen 1 ( for example )
74
EXCEL graphic screen 2 ( for example ) EXCEL graphic screen 3 ( for example )
75
EXCEL graphic screen 4 ( for example )
EXCEL graphic screen 5 ( for example )
9. PATENT The meter ( SD card structure ) already get patent or patent
pending in following countries :
76
Germany JAPAN CHINA
USA
Nr. 20 2008 016 337.4 3151214 ZL 2008 2 0189918.5 ZL 2008 2 0189917.0 Patent pending
10. THE ADDRESS OF AFTER SERVICE CENTER
77
180910-DW6195
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>