Danfoss ERC 213G Electronic Refrigeration Control Installation Guide
- June 1, 2024
- Danfoss
Table of Contents
- Danfoss ERC 213G Electronic Refrigeration Control
- Electronic refrigeration control Type ERC 213G
- Dimensions (mm)
- Assembly
- Wiring diagram
- User interface
- Menu structure
- Basic functions
- Safety standards
- Technical Data
- Certificates, declarations, and approvals
- Parameters
- Product Information
- Specifications:
- Assembly and Mounting:
- Wiring Diagram:
- User Interface and Button Functions:
- Menu Structure:
- Safety Standards:
- Product Disposal:
- Q: What is the purpose of the ERC 213G?
- Q: How should I adjust the setpoint temperature?
- Q: What should I do in case of an active alarm?
Danfoss ERC 213G Electronic Refrigeration Control
INSTALLATION GUIDE
Electronic refrigeration control Type ERC 213G
The ERC 213G is a smart controller designed for air-dryer application to remove the moisture that is inherent in the compressed air.
Dimensions (mm)
Assembly
Wiring diagram
Note: 2L and 3L must be connected to the same phase.
User interface
Menu structure
Basic functions
Safety standards
Check the input voltage is correct before connecting the instrument.
Do not expose to water or damp: only use the regulator within the design
operating limits, avoiding sudden temperature changes with high atmospheric
humidity to prevent condensate forming.
Product disposal
The device (or product) must be disposed of in compliance with local waste disposal legislation.
EU design registration
002566703-0001
Technical Data
Features | Description |
---|---|
Power supply | 230 V AC 50/60 Hz, galvanic isolated low voltage regulated power |
supply
Rated power| Less than 0.7 W
Inputs| Sensor inputs, Digital inputs, Programming key Connected to SELV
limited energy <15 W
Types of sensors allowed| NTC 5000 Ohms at 25 °C (beta= 3,980 at 25/100 °C-
EKS 211 for example) NTC 10000 Ohms at 25 °C (beta= 3,435 at 25/85 °C- EKS 221
for example) PTC 990 Ohms at 25 °C (EKS 111 for example)
Ptl 000 (AKS 11, AKS 12, AKS 21 for example)
Accuracy| Measuring range: -40 – 1OS °C (-40 – 221 °F)
Controller accuracy:
+/-1 K below -35 °C
+/-0.5 K between -35 – 25 °C, +/-1 K above 25 °c
Output| Relay DOl:
16A, 16(16)A,EN60730-1
10 FLA/ 60 LRA at 230 V, UL60730-1| RelayDO2:
8 A, 2 FLA/ 12 LRA, UL60730-1
8 A, 2 (2 A), EN60730-1| Relay DO3:
3 A, 2 FLA/ 12 LRA, UL60730-1
3 A, 2 (2 A), EN60730-1
Display| LED 3-figure display, decimal point and multifunction icons, °C + °F
scale
Operating Conditions| -10 – 55 °C (14 – 131 °F), 90% Rh
Storage conditions| -40- 70 °C (-40- 158 °F), 90% Rh
Ingress Protection| Front: IP65 (with seal), Rear: IP00
Environmental data| Pollution degree 2, non-condensing
Resistance to heat and fire| UL94-V0
EMC category| Emission: IEC/EN 61000 6-3, Immunity: IEC/EN 61000 6-2
Purpose of control| Operating control for air dryer system
Construction of control| Electronic control for Incorporation for use in Class
I and Class II appliances
Automatic action| Micro – disconnection on operation Type l .B
Overvoltage category| II – 230 V supply version – (ENEC, UL recognized)
Temp. for ball pressure test| According to EN 60730-1, Annex G (EN 60730-1)
For SELV circuits| Input probes or Digital Input connected to SELV limited
energy< 1SW
Certificates, declarations, and approvals
Parameters
Parameter Name – ERC 213G| Code| Min| Max| Unit|
Value
---|---|---|---|---|---
Configuration| cFg| | | |
Main switch. -1=service, 0=OFF, 1=ON| r12| -1| 1| | 1
Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000| o06| n5|
Pt1| | n10
Reference| r–| | | |
Temperature setpoint| r00| -100.0| 200.0| °C/°F| 2.0°C
Differential| r01| 0.1| 20.0| K| 2.0
Min set point limitation| r02| -100.0| 200.0| °C/°F| -35.0
Max set point limitation| r03| -100.0| 200.0| °C/°F| 50.0
Display offset (correction value in display temperature)| r04| -10.0| 10.0| K|
0.0
Display Unit (°C/°F)| r05| -C| -F| | -C
Calibration of Sair (offset for air temperature calibration)| r09| -20.0|
20.0| K| 0.0
Alarm| A–| | | |
Delay for temperature alarm (during normal conditions)| A03| 0| 240| min| 30
High temperature alarm limit| A13| -100.0| 200.0| °C/°F| 8.0
Low temperature alarm limit| A14| -100.0| 200.0| °C/°F| -30-0
Voltage protection enable| A72| no| yES| | no
Minimum cut-in voltage| A73| 0| 270| V| 0
Minimum cut-out voltage| A74| 0| 270| V| 0
Maximum voltage| A75| 0| 270| V| 270
Drain valve (DO2)| d–| | | |
Drain valve activation interval| o94| 0| 30| min| 2.0
Drain valve opening time| o95| 0| 30| sec| 2.0
Secconds setting added to the minutes in o94| P54| 0| 59| sec| 0.0
Cooling relay (DO3)| c–| | | |
Minimum ON time| C01| 0| 30| min| 0
Minimum OFF time| C02| 0| 30| min| 2
Zero crossing selection| C70| no| yES| | YES
Others| o–| | | |
Delay of outputs at startup| o01| 0| 600| sec| 5
Serial address| o03| 0| 247| no.| 0
Password| o05| no| 999| no.|
Display resolution 0.1=steps of 0.1°C, 0.5=steps of 0.5°C, 1.0=steps of
1.0 C| o15| 0.1| 1.0| | 0.1
Readouts| u–| | | |
Controller Status
S0=cooling ON, S2=wait for compressor ON time to elapse, S3=wait for
compressor OFF time to elapse-restart time, S10=cooling stop, S11=cooling
stopped by thermostat,
S25=manual control of outputs, S32=delay of outputs at power up| u00| –| –| –|
–
Sair| u01| | | |
Present regulation reference| u02| | | |
Relay 1 status / Manual override| u58| oFF| on| |
Relay 3 status / Manual override| u59| oFF| on| |
Relay 2 status / Manual override| u60| oFF| on| |
Alarm status| | | | |
Sair air temperature sensor error| E29| | | |
High temperature alarm| A01| | | |
Low temperature alarm| A02| | | |
High voltage alarm| A99| | | |
Low voltage alarm| AA1| | | |
Standby alarm| A45| | | |
Product Information
Specifications:
- Model: ERC 213G
- Manufacturer: Danfoss
- Power Supply: 230 V AC, 50/60 Hz
- Rated Power: Less than 0.7 W
- Inputs: Sensor inputs, Digital inputs, Programming key
- Types of Sensors Allowed: Connected to SELV limited energy
- Accuracy: Not specified
- Output: Not specified
- Display: Not specified
- Operating Conditions: Not specified
- Storage Conditions: Not specified
- Ingress Protection: Not specified
- Environmental Data: Not specified
- Resistance to Heat and Fire: Not specified
- EMC Category: Not specified
- Purpose of Control: Air-dryer application to remove moisture
from compressed air
Product Usage Instructions
Assembly and Mounting:
The ERC 213G should be mounted using the rear mount clip fixing
provided in the assembly. Refer to the drilling template for
accurate placement. The dimensions for mounting are specified as
36mm x 28mm x 71mm x 29mm x 83mm.
Wiring Diagram:
Refer to the wiring diagram for proper connections. Ensure that
the power connectors are torqued to a maximum of 0.4 Nm and signal
connectors to a maximum of 0.2 Nm.
User Interface and Button Functions:
The user interface includes buttons for Drain, Hot gas, and Sair
functions. Follow the button functions listed in the manual for
various operations such as RESET, BACK, TEMPERATURE SETPOINT
adjustment, MENU access, and ON/OFF control.
Menu Structure:
The menu structure allows access to parameters, settings, and
service options. Use the SET button for state adjustments, sensor
type selection, setpoint temperature changes, and alarm code
viewing.
Safety Standards:
Prior to installation, ensure correct input voltage. Avoid
exposing the controller to water or damp conditions. Operate within
design limits to prevent condensation due to sudden temperature
changes with high humidity.
Product Disposal:
Dispose of the device in compliance with local waste disposal
regulations to ensure proper environmental handling.
FAQ
Q: What is the purpose of the ERC 213G?
A: The ERC 213G is designed for air-dryer applications to remove
moisture from compressed air.
Q: How should I adjust the setpoint temperature?
A: Use the SET button to adjust the setpoint temperature and
UP/DOWN buttons to change the temperature value. The setpoint will
flash in setting mode.
Q: What should I do in case of an active alarm?
A: View the active alarm by pressing the SET button. The
temperature setpoint must be saved to resolve the alarm
indication.
Installation Guide
Electronic refrigeration control Type ERC 213G
080R9335 AN194386421321en-000501
The ERC 213G is a smart controller designed for air-dryer application to remove the moisture that is inherent in the compressed air.
Danfoss 80G8101.01
Dimensions (mm)
36
28
71 29
83
Assembly
Mounting
61.2 66 Rear mount (clip fixing)
Wiring diagram
Drilling template
Danfoss 80G8536
Danfoss 80G8391
Dismounting
Hot gas bypass valve
DO3
Sair Drain valve DO2
Condenser fan DO1
Connectors: Max. torque for power connectors = 0.4 Nm Max. torque for signal
connectors = 0.2 Nm
DO1 1 2L
DO2 DO3 3L 4N 5 6 7
GND
GND
8 9 10 11 12 13 14
Danfoss 80G8392
User interface
Button function
~
230 V AC
~
~
230 V AC
~
Drain
Hot gas
Sair
Note: 2L and 3L must be connected to the same phase.
Press and hold down on startup RESET FACTORY SETTINGS (“FAC” is displayed)
Press for one second: BACK
Press for one second: TEMPERATURE SETPOINT/OK Press and hold down: MENU
Press for one second: UP Press and hold down: ON/OFF
Press for one second: DOWN
© Danfoss | Climate Solutions | 2023.08
AN194386421321en-000501 | 1
Danfoss 80G137
Menu structure
SET: press for 3 seconds for state, settings and service 1) Parameters group
Password (if enabled)
Input states Configuration
- Parameter names SET
Main switch
To scroll the
parameter names
Sensor type
To scroll the parameter groups
Basic functions
Adjusting the setpoint temperature
Unlock keyboard
Danfoss 80G8441
Danfoss 80G8453
(short press) SET: adjust the setpoint temperature.
UP/DOWN: change the temperature setpoint (in setting mode the setpoint
flashes).
Temperature and alarm codes alternate flashes until the alarm is resolved. The alarm bell is shown.
Danfoss 80G8442
View an active alarm
SET: saves the temperature setpoint.
· After 5 minutes of inactivity, the keypad will be locked (if P76 = YES).
· When the keypad is locked, if any key is selected, “LoC” appears on the
display.
· Press UP and DOWN buttons simultaneously for 3 seconds to unlock the
keyboard. “unl” is displayed for 3 seconds.
Safety standards
Check the input voltage is correct before connecting the instrument. Do not
expose to water or damp: only use the regulator within the design operating
limits, avoiding sudden temperature changes with high atmospheric humidity to
prevent condensate forming.
Product disposal
The device (or product) must be disposed of in compliance with local waste
disposal legislation.
EU design registration
002566703-0001
2 | AN194386421321en-000501
© Danfoss | Climate Solutions | 2023.08
Technical Data
Features Power supply Rated power Inputs
Types of sensors allowed
Accuracy
Output
Display Operating Conditions Storage conditions Ingress Protection
Environmental data Resistance to heat and fire EMC category Purpose of control
Construction of control Automatic action Overvoltage category Temp. for ball
pressure test For SELV circuits
Description
230 V AC 50/60 Hz, galvanic isolated low voltage regulated power supply
Less than 0.7 W
Sensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W
NTC 5000 Ohms at 25 °C (beta = 3,980 at 25/100 °C – EKS 211 for example) NTC 10000 Ohms at 25 °C (beta = 3,435 at 25/85 °C – EKS 221 for example) PTC 990 Ohms at 25 °C (EKS 111 for example) Pt1000 (AKS 11, AKS 12, AKS 21 for example)
Measuring range: -40 105 °C (-40 221 °F)
Controller accuracy: +/-1 K below -35 °C +/-0.5 K between -35 25 °C, +/-1 K above 25 °C
Relay DO1:
Relay DO2:
16 A, 16 (16) A, EN 60730-1
8 A, 2 FLA / 12 LRA, UL60730-1
10 FLA / 60 LRA at 230 V, UL60730-1 8 A, 2 (2 A), EN60730-1
Relay DO3: 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1
LED 3-figure display, decimal point and multifunction icons, °C + °F scale
-10 55 °C (14 131 °F), 90% Rh
-40 70 °C (-40 158 °F), 90% Rh
Front: IP65 (with seal), Rear: IP00
Pollution degree 2, non-condensing
UL94-V0
Emission: IEC/EN 61000 6-3, Immunity: IEC/EN 61000 6-2
Operating control for air dryer system
Electronic control for Incorporation for use in Class I and Class II appliances
Micro – disconnection on operation Type 1.B
II – 230 V supply version – (ENEC, UL recognized)
According to EN 60730-1, Annex G (EN 60730-1)
Input probes or Digital Input connected to SELV limited energy < 15W
Certificates, declarations, and approvals
Regulatory and Compliance
Directive / Document topic
Standards
Electrical Safety (Incorporated Control for Low Voltage Directive:
use in Class I or Class II equipment)
2014/35/EU
EN IEC 60730-2-9:2019, EN IEC 60730-2-9:2019/A1:2019, EN IEC 60730-2-9:2019/A2:2020, EN 60730-1:2016, EN 60730-1:2016/A1:2019, EN 60730-1:2016/A2:2022
Electrical Safety (control is validated to Recognized Component use as Incorporated)
UL 60730-1 – 2009 – Revision 2014, UL 60730-2-9 : 2010, Revision : 2013
Electrical Safety (control is validated to Recognized Component use as Incorporated)
CSA E60730-1 :2013, CSA E60730-2-9 : 2001, Revision : 2008, AMD 1
Electrical Safety (Incorporated Control for use in Class I or Class II equipment)
GB 14536.1:2008, GB 14536.10:2008
Electrical Safety & Electromagnetic Compatibility
Supplier Declaration of Conformity (SDoC)
EN 60730-1:2016, EN 60730 2-9:2019, EN 610006-2:2005 & EN 61000-6-3:2007+A1:2011
Electrical Safety
Certification of Conformity CU TR 004/2011 (CoC)
Electromagnetic Compatibility
EMC Directive: 2014/30/EU EN 610006-2:2005 & EN 61000-6-3:2007+A1:2011
RoHS
RoHS Directive: 2011/65/EU EN IEC 63000:2018 & 2015/863/EU
Food Safety
Food Equipment
NSF/ANSI standard 2
Approved for use in Flammable Refrigerants
Enclosed Break Device / sealed device nC (Relays)
Sealed Device “nC” IEC 600079-15:2017, Enclosed-Break device “dC” IEC 60079-1:2014, clause 15.5.3
Approved for use in Flammable Refrigerants
Enclosed Break Device (Relays)
Sealed device “nC” UL 60079-15 and CAN/CSA C22.2 No. 60079-15, Enclosed-Break device “dC” IEC 60079-1:2014, clause 15.5.3
Enclosure Material Flammable Class
–
UL 94, V-0
HACCP, Temperature Measuring probe in compliance with EN13485 Class I, when used with AKS 12 sensor
EN 13485:2001
Certification and Manufacturer Declarations on Conformity
CE, CURUS, CQC, UA, EAC, NSF, RoHS
Country Marking Europe – CE
United States CURUS Canada – CURUS
China – CQC
Ukraine – UA
Eurasia – EAC
Europe – CE Europe – CE
United States Europe
US and Canada
US Europe
© Danfoss | Climate Solutions | 2023.08
AN194386421321en-000501 | 3
Parameters
Parameter Name – ERC 213G Configuration Main switch. -1=service, 0=OFF, 1=ON
Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 Reference
Temperature setpoint Differential Min set point limitation Max set point
limitation Display offset (correction value in display temperature) Display
Unit (°C/°F) Calibration of Sair (offset for air temperature calibration)
Alarm Delay for temperature alarm (during normal conditions) High temperature
alarm limit Low temperature alarm limit Voltage protection enable Minimum cut-
in voltage Minimum cut-out voltage Maximum voltage Drain valve (DO2) Drain
valve activation interval Drain valve opening time Secconds setting added to
the minutes in o94 Cooling relay (DO3) Minimum ON time Minimum OFF time Zero
crossing selection Others Delay of outputs at startup Serial address Password
Display resolution 0.1=steps of 0.1°C, 0.5=steps of 0.5°C, 1.0=steps of 1.0 C
Readouts Controller Status S0=cooling ON, S2=wait for compressor ON time to
elapse, S3=wait for compressor OFF time to elapse-restart time, S10=cooling
stop, S11=cooling stopped by thermostat, S25=manual control of outputs,
S32=delay of outputs at power up Sair Present regulation reference Relay 1
status / Manual override Relay 3 status / Manual override Relay 2 status /
Manual override Alarm status Sair air temperature sensor error High
temperature alarm Low temperature alarm High voltage alarm Low voltage alarm
Standby alarm
Code cFg r12 o06 r-r00 r01 r02 r03 r04 r05 r09 A-A03 A13 A14 A72 A73 A74 A75 d-o94 o95 P54 c-C01 C02 C70 o-o01 o03 o05 o15 u–
Min
-1 n5
-100.0 0.1
-100.0 -100.0 -10.0
-C -20.0
0 -100.0 -100.0
no 0 0 0
0 0 0
0 0 no
0 0 no 0.1
Max
1 Pt1
200.0 20.0 200.0 200.0 10.0 -F 20.0
240 200.0 200.0 yES 270 270 270
30 30 59
30 30 yES
600 247 999 1.0
Unit
°C/°F K
°C/°F °C/°F
K
K
min °C/°F °C/°F
V V V
min sec sec
min min
sec no. no.
Value
1 n10
2.0°C 2.0 -35.0 50.0 0.0 -C 0.0
30 8.0 -30-0 no 0 0 270
2.0 2.0 0.0
0 2 YES
5 0
0.1
u00
–
–
–
–
u01 u02 u58 oFF on u59 oFF on u60 oFF on
E29 A01 A02 A99 AA1 A45
4 | AN194386421321en-000501