Danfoss ICAD 600B Motorized Valve Control Installation Guide

June 2, 2024
Danfoss

Danfoss ICAD 600B Motorized Valve Control

Installation Instructions

Before installing ICAD on ICM please read the separate guides “Mechanical in tallation of ICAD on ICM”  and Quick start guide”

Nm LB-feet
Max. 3 Max. 2.2

ICAD 600B / ICAD 600B / ICAD 1200B

ICAD back Ref Color Description
I Black + Fail safe supply. Battery/ UPS* 19 V DC
II White + Supply voltage 24 V DC 2A, or more, per ICAD recommended ICAD

PSU must be SELV, >15 W
III| Brown| –
IIII| Blue| +| UPS Signal of Health- optional depending on ID31: ‘UPS supply’ set to ‘Yes’
| 1| White/Blue| (-) / TX+| Data – (B) / Transmit Pair(+)
---|---|---|---|---
2| White/Orange| GND / RX+| Ground / Receiving Pair(+)
3| Blue| (+) / TX-| Data + (A) / Transmit Pair(-)
4| Orange| GND / RX-| Ground / Receiving Pair(-)
RS 485 / Ethernet RS 485 / Ethernet RS 485 / Ethernet**

**| 1| White/Blue| (-) / TX+| Data – (B) / Transmit Pair(+)
2| White/Orange| GND / RX+| G round / Receiving Pair(+)
3| Blue| (+) / TX-| Data + (A) / Transmit Pair(-)
4**| Orange| GND / RX-| G r o u n d / Receiving Pair(-)

*Uninterruptable Power Supply
** The ICAD is a Class III appliance

ICAD 600B/1200B – Analog I/O for modulating control

  1. Control Cable
  2. Power supply cable
  3. Data cable

ICAD 600B/600B-TS/1200B – Digital I/O for ON/OFF valve operation

Neutral zone/3 points control

Installation

Do not install ICAD before welding. This apply for electrical as well as for mechanical installation. Please observe that ICAD when connected to 24 V DC, will send out acoustic noise at stand still. This has no influence on the function/ operation of the ICAD.

Use

ICAD 600B, ICAD 600B-TS and ICAD 1200B can be used together with the following Danfoss valves (fig. 1, 5a and 5b).

ICAD 600B ICAD 600B-TS ICAD 1200B
ICM 20 ICMTS 20 ICM 40
ICM 25 ICMTS 50 ICM 50
ICM 32 ICMTS 80 ICM 65
ICM 100
ICM 125
ICM 150
CVE pilot valve

Electrical data

Supply voltage is galvanically isolated from in-/output.
ICAD is a Class III product.
PSUs connected to ICAD must be SELV<100 VA

For UL compliance:

PSU must be Class 2 NEC
Control type: Operating Control – Type
1 Action
Pollution Degree: 3

Supply voltage
24 V DC (Tolerances; see below table)
Load ICAD 600B, ICAD 600B-TS : 1.2 A
ICAD 1200B: 2.0 A

24 Volt DC ONLY

Please observe cable voltage drop.
Distance between the applied DC transformer and the ICAD terminal box may cause a voltage drop. Cross section of cables and size of DC transformer must be calculated so that the voltage at all time **at the ICAD terminal box***, both during standstill and during operation of ICAD, is within this range:

Prefabricated ICAD cable length Code number| 1.5 m 027H0426| 3 m 027H0438| 10 m 027H0427| 15 m 027H0435
---|---|---|---|---
Voltage ICAD terminal (600B/1200B) [V DC]| Min.| 21| 22| 23| 24
Max.| 26.4

*Do not measure inside the ICAD itself (value can be checked in ICAD B menu).

Fail safe supply
24 V DC (Tolerances; see table above)
Load ICAD 600B, ICAD 600B-TS: 1.2 A ICAD 1200B: 2.0 A

Data communication

RS 485: It is important that the installation of the data communication cable is done correctly. For further guidance, see literature No. RC8AC902.
Remember termination at the bus termination. Max length of cable: 1200 m with specific cable and limited data rate. Follow RS485 standard.

Insulation from power supply input, metallic part and interface output : 500 V DC: *For input/output connections

Anolog Input – Current or Voltage Current

Input range : 0/4 – 20 mA
Max input range: 0 – 24 mA
Input resistance: 120 W + diode voltage 0.7 V DC
Measurement error: <±1.5% of the full scale
Reverse polarity protection: yes
Overcurrent protection: yes

Voltage

Input range: 0/2 – 10 V DC
Max input range : 0 – 12 V DC
Measurement error: <±1.5% of the full scale
Reverse polarity protection: yes

Analog Output
Output range: 0/4 – 20mA
Load: <800 W
Output error: <±1.5% of the full scale
Recommended external resistor for Hot application: Rext=800 W-load 1W power rate
Digital Input – Digital ON/OFF input by means of volt free contact (Signal/Telecom relays with gold-plated contacts recommended) – Voltage input used

Rth rise(OFF): >10 kΩ
Rth fall(ON): < 45 Ω

Digital Output – 3 pcs. NPN transistor output

External supply: 7 – 24 V DC (same supply as for ICAD can be used, but please note that the galvanically isolated
system will then be spoiled).
On resistance: 55 W + diode voltage 0.7 V DC Max 70 W at 50 mA
Max Output current: 50 mA
Reverse polarity protection: Yes
Overcurrent protection: No

Temperature range (ambient)

-30 °C/+50 °C (-22 °F/122 °F)

Enclosure

IP67 (~NEMA 6)

Electrical connection

Connection to ICAD is done via M12 connectors. ICAD has two M12 male and one M12 female connectors build-in:

Power supply: 4 poled M12 male connector
Control signals: 8 poled M12 male connector
Data communication: 4 poled M12 female connector

Power Supply cable with 4 poled M12 female connector
4 x 0.34 mm2
(4 x ~22 AWG) (fig. 6)
I: Black (+) 19 – 24 V DC fail safe
supply (optional)
II: White (+) 24 V DC
III: Brown (–) 24 V DC
IIII: Blue (+) UPS signal of health

Control cable with 8 poled M12 female connector 7 x 0.25 mm2 (7 x ~24 AWG) (fig. 7)

A: Black (–) Digital output Common Alarm
B: Brown (–) Digital output ICM fully open
C: Red (–) Digital output ICM fully closed
D: Orange (–) GND – Ground
E: Yellow (+) Analog input 0/4 – 20 mA)
F: Green (+) Analog input 0/2 – 10 V / DI1 – Digital ON/OFF input.
G: Blue (+) Analog output 0/4 – 20 mA)

Data communication cable with 4 poled M12 male connector: RS 485 / RS 485 /
Ethernet Ethernet
1: White/Blue (-) / TX+ Data – (B) / Transmit Pair(+)
2: White/Orange GND / RX+ Ground / Receiving Pair(+)
3: Blue (+) / TX- Data + (A) / Transmit Pair(-)
4: Orange GND / RX- Ground / Receiving Pair(-)

Electrical installation

General procedure for ICAD 600B/ICAD 600B-TS/1200B installed on all ICM, ICMTS & CVE valves.
All necessary electrical connections to be made.

Fig. 6

  • Analog operation – 7 wired cable (A-G)
    Modulation control. Valve to be controlled from Danfoss electronics, type EKC/EKE (g. 7), or third party electronics (like e.g. PLC).

    • Connect analog input signals. Current (mA) or Voltage (V). See Parameter list for configuration of analog input signals
    • Yellow (+) and Orange (GND) are used for current (mA) input or
    • Green (+) and Orange (GND) are used for Voltage (V) input
    • Blue (+) and Orange (GND) are used for current (mA) output (optional, not mandatory)

Fig. 6

  • Digital operation – 7 wired cable (A-G)
    ON/OFF ICM solenoid valve operation. ICM valve to be controlled by means of a digital volt free contact.

    • Connect digital input signals (fig. 8). See
      Parameter list for configuration of digital input signals

    • Green (+) and Orange (GND) are connected to a volt free contact

    • Digital output signals are optional, not mandatory.

    • Black (–) and Orange (GND) are connected to auxiliary relay for Common Alarm

    • Brown (–) and Orange (GND) are connected to an auxiliary relay indicating ICM fully open

    • Red (–) and Orange (GND) are connected to an auxiliary relay indicating ICM fully closed

  • Supply voltage – 4 wired cable(I, II, III, IIII)
    ICAD must be connected to a normal 24 V DC supply. As an option, a fail safe supply is possible by means of a battery or UPS (Uninterruptible Power Supply). When voltage is applied as described below, ICAD is ready to be configured.
    See Parameter list.
    ICAD configuration can be done independently whether the ICAD is installed on the valve or not. See Mechanical installation.

  • Connect the White (+) and Brown (–) to 24 V DC supply voltage (fig. 6)
    Fail safe supply as an option (not mandatory).

  • Connect the Black (+) and Brown (–) to a fail safe supply.

Mechanical installation

General procedure for ICAD 600B/ICAD 600B-TS/1200B installed on all valves (fig. 3).

  • Check that the two socket screws are fully unscrewed counter clockwise with a 3 mm Hexagon key
  • If valve is attended with PTFE ring and O-ring, remove both and replace it with O-ring included in ICAD (as instructed in g. 3)
  • Mount ICAD by slowly lowering it on top of the valve.
  • The magnet coupling will drag the valve and ICAD together and in position
  • Push ICAD in place
  • Fasten valve and ICAD with the two socket set screws using a 3 mm Hexagon key

Special moisture seal is damaged if screws are removed (fig. 3).

Power on & start operation

ICAD has a light guide viewable from three sides, which indicates the status. Immediately after power on the light guide and display lights up.

| Steady red| Critical alarm – stopped operating|
---|---|---|---
| Flashing red| Severe alarm – danger of stopping operating
| Flashing blue| ICAD is connected via Bluetooth
| Flashing yellow| Warning
| Flashing green| OK

The main screen layout and navigation is as described below. ICAD will start up in alarm mode as the ICM configuration needs to be defened to start operation. Follow the steps on next page to set this up correctly.

STATUS BAR

Set valve (A1 alarm)

VALVE CONFIGURATION HELP

Change analog input signal (optional)

ICAD will function based on factory settings as soon as the valve configuration has been set. The default settings are Modulation using an analog input of 4–20 mA.

Bluetooth connection

In addition to the onboard display, all configuration and readings from ICAD B actuator can be performed via Bluetooth (using Coolcong mobile app) or via data communication.
CoolConfig can be downloaded and installed from iTunes Store or Google Play Store.
To connect with ICAD actuator, click Start scanning in CoolConfig and the list of available devices will be provided. To connect with a device, a password will be required.
The connection PIN is 0000 and serves to ensure that the connection is intentionally. Access is then read-only.

Further languages and documentation

www.icadb.danfoss.com

DanfossA/S
Climate Solutions
danfoss.com
+45 7488 2222

 Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, on line or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material.

Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/5 or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All rights reserved.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals