Clifford Snell YA80 Yodalarm and Yodalight Series Instruction Manual

June 2, 2024
Clifford Snell

Clifford Snell YA80 Yodalarm and Yodalight Series

Clifford-Snell-YA80-Yodalarm-and-Yodalight-Series-
PRODUCT

Product Specifications

  • Brand: C& S (Clifford & Snell)
  • Model: YO8 Yodalarm & Yodalight Series (Incorporating YA80 and YL80)
  • Type: Audible and/or Visual Signalling Devices
  • Issue: S00625 Issue 4
  • Approvals and Conformities: EN54-3, Factory installed YL80 Ferrite Beads

Installation

  • Installation must be carried out under the latest codes of practice by a qualified electrician.
  • Check that the power supply is correct for the voltage rating of the alarm to be installed.
  • Ensure that the power supply is disconnected before installation or maintenance to avoid electrical shock.
  • The unit should be mounted to a wall or bulkhead formed of suitable material using the two mounting lugs projecting from the side of the enclosure.
  • The lugs have a 10mm diameter mounting hole & sit on 250mm centers. The minimum recommended length of fixing screw is 30mm (not supplied).
  • Avoid mounting the alarm where it could subjected to excessive vibration levels.
  • All YA80 units require 2 additional ferrite beads (included in the box) to be fitted on all input wires, 1 wire per hole. Failure to correctly install the ferrite beads will result in the unit not complying with the EN54-3 approval. (YL80 Ferrite Beads are factory installed).

Ingress Protection
To maintain the IP rating of the product, the below points must be observed.

  • An IP66 cable gland is supplied with the product. This gland (or other suitably rated) must be used.
  • When replacing the front cover, each of the four retaining screws must be torqued to 0.6Nm ±0.1Nm

Sound selection

  • Ensure the supply is OFF before proceeding.
  • All DC and AC units have 2 selectable alarm stages (see table on the back of installation sheet for details) and are set via switches SW1 & SW2.
  • Figure 1 (DC) & Figure 3 (AC) show the wiring to activate alarm stages 1 & 2.
  • Figure 2 shows a second option for DC wiring. This allows for activating a stage 1 or a stage 2 alarm tone depending on the polarity of the connection.
  • All stage 1 alarm tones have a predetermined stage 2 alarm (see back of installation sheet), this will only sound if SW1 & SW2 are configured to the same tone.

Line integrity for DC systems only

  • For 3 wire 2 stage alarm system, monitor via reverse polarity across TB1 & TB2.
  • For 2 wire 2 stage alarm system, monitor via threshold, (applied voltage<1v) an end-of-line (E.O.L) resistor is required for line monitoring and should have a minimum resistance of 3k3 ohms and 0.5watts, wire-wound or metal film type.

AC Systems

  • A second-stage alarm tone can be activated by applying an additional “L” connection to the TB3 terminal on the PCB, as shown in Figure 3.

Additional Voltage Options

  • The Clifford and Snell YO8 series is also available in a 48vDC (F) option.
  • The wiring for this voltage is the same as the 24vDC units as shown in Figure 1.
  • Always confirm correct voltage is applied to relevant terminals.

YA80 Wiring options

Clifford-Snell-YA80-Yodalarm-and-Yodalight-Series-
FIG-1

YO8 Yodalarm/Yodalight Series

Consists of either the YA80 (Audible Unit only) or the YL80 (Combined Audible & Visual unit)
Connections for the YL80 units are made via a 6-way Terminal Block mounted in the base of the unit as shown in Figure 4 diagram below. Using the connections shown, it is possible
to independently control both the Sounder and Beacon sections.

YL80 Wiring options

Clifford-Snell-YA80-Yodalarm-and-Yodalight-Series-
FIG-2

Features Include

  • Termination: Up to 2.5mm2 cable
  • Operating Temperature:
    • Standard Variants -25oC to +70oC
    • EN54-3 Approved -25oC to +55oC
  • Enclosure Material: Fire Resistant & UV Stable UL94-5VB rated ABS
  • Lens Material: Fire Resistant & UV Stable Polycarbonate
  • Ingress Protection: Weatherproof to IP66
  • Sound Pressure Level: 117dB(A) Max.
  • AC Supply: 50/60 Hz

Tone Table

| | Frequency| Rept.| ****

Second

| | Switches| | | dB(A)
---|---|---|---|---|---|---|---|---|---
Tone| Description| (Hz)| rate| Stage| 1| 2| 3| 4| 5| Special Application| @ 1m

(± 3dB)

1| Alternating| 800-1000| 0.5| 3| I| I| I| I| I| Fire Alarms| 116
2| Alternating| 2500-3100| 0.5| 4| O| I| I| I| I| Security Alarms| 108
3| Alternating (fast)| 800-1000| 0.25| 7| I| O| I| I| I| Increased urgency| 117
4| Alternating (fast)| 2500-3100| 0.25| 8| O| O| I| I| I| Security deterrent| 108
5
| Alternating| 440-554| 0.4/0.1| 14| I| I| O| I| I| AFNOR, France (NFS 32001)| 108
6| Alternating| 430-470| 1| 14| O| I| O| I| I| | 107
7| Alternating (v.fast)| 800-1000| 0.13| 12| I| O| O| I| I| | 116
8| Alternating (v.fast)| 2500-3200| 0.07| 13| O| O| O| I| I| | 107
9| Alternating| 440-554| 2| 10| I| I| I| O| I| Turn-out, Sweden| 110
10| Continuous note| 700| –| 1| O| I| I| O| I| All-clear, Sweden| 110
11| Continuous note| 1000| –| 31| I| O| I| O| I| | 116
12| Continuous note| 1000| –| 7| O| O| I| O| I| | 116
13| Continuous note| 2300| –| 2| I| I| O| O| I| | 113
14| Continuous note| 440| –| 9| O| I| O| O| I| | 105
15
| Interrupted tone| 1000| 2| 31| I| O| O| O| I| | 115
16| Interrupted tone| 420| 1.25| 30| O| O| O| O| I| AS2220, Australia| 105
17| Interrupted tone| 1000| 0.5| 1| I| I| I| I| O| | 115
18| Interrupted tone| 2500| 0.25| 4| O| I| I| I| O| | 111
19| Interrupted tone| 2500| 0.5| 2| I| O| I| I| O| | 111
20| Interrupted tone| 700| 6/12| 10| O| O| I| I| O| Pre-vital mess, Sweden| 111
21| Interrupted tone| 1000| 1| 32| I| I| O| I| O| | 116
22| Interrupted tone| 700| 4| 10| O| I| O| I| O| Air-raid, Sweden| 110
23| Interrupted tone| 700| 0.25| 10| I| O| O| I| O| Local warning, Sweden| 110
24| Interrupted tone| 720| 0.7/0.3| 10| O| O| O| I| O| Industrial alarm, Germany| 110
25| Int,fast,rising volume| 1400| 0.25| 26| I| I| I| O| O| | 112
26| Fast siren| 250-1200| 0.085| 11| O| I| I| O| O| | 113
27| Rising constant, fall| 1000| 10/40/10| 17| I| O| I| O| O| Industrial alarm, Germany| 117
28
| ISO 8201 Evacuation| 800-1000| as std| 11| O| O| I| O| O| Int’l evacuation alarm| 116
29| Fast whoop| 500-1000| 0.15| 32| I| I| O| O| O| | 113
30| Slow whoop| 500-1200| 4.5| 12| O| I| O| O| O| Evacuation, The Netherlands| 116
31
| Reverse sweep| 1200-500| 1| 11| I| O| O| O| O| Evacuation, Germany| 115
32| Siren| 500-1200| 3| 26| O| O| O| O| O| | 116

Note: EN54-3 Compatible Tones are marked above with.
Moflash Signalling Limited accepts no liability for any consequences following the use of this document. Any technical specifications and products referred to within this document are subject to change without notice due to continual improvement and product development policies. All dB(A) figures are subject to environmental conditions. The units are sold under Moflash standard conditions of sale, available on request.

Additional resources, including installation sheet translations, certificates, and DoCs are available from the www.moflash.co.uk website.
Moflash Signalling Limited , 11 Upper Conybere Street, Highgate, Birmingham, B12 0EB, UK

FAQ

Frequently Asked Questions

  • Q: What should I do if the device is not compliant with EN54-3 approval?
    • A: Ensure that the ferrite beads are correctly installed during wiring to meet the compliance standards.
  • Q: How can I change the sound output of the device?
    • A: If using a tone board, make sure SW1 & SW2 are set to the same tone for consistent sound.

www.moflash.com
technical@moflash.co.uk

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals