AURORA LIGHTING Utilite 20W 4000K Square Drum Black LED Bulkhead with Emergency Backup Installation Guide
- May 15, 2024
- AURORA LIGHTING
Table of Contents
LIGHTING Utilite 20W 4000K Square Drum
Black LED Bulkhead with Emergency Backup
Installation Guide
BH18R Installation Method
BH18S Installation Method
BH18R & EN-BH18REM
BH18S & EN-BH18SEM
Wiring Instruction
BH18R, EN-BH18RMS, EN-BH18REM, EN-BH18S, EN- BH18SMS & EN-BH18SEM
MICROWAVE SENSOR
DETECTION AREA
Detection area can be reduced by selecting the combination on the DIP switches
to fit precisely each application.
| 1| 2| 3|
---|---|---|---|---
| | | 100%
| | | 75%
| | | 50%
| | | 25%
| | | 10%
HOLD TIME
Refers to the time period the lamp remains at 100% illumination after no
motion detected.
| 4| 5| 6|
---|---|---|---|---
| | | 5s
| | | 30s
| | | 90s
| | | 3min
| | | 20min
| | | 30min
DAYLIGHT SENSOR
The sensor can be set to only allow the lamp to illuminate below a defined
ambient brightness threshold.
When set to Disable mode, the daylight sensor will switch on the lamp when
motion is detected regardless of ambient light level.
50lux: twilight operation, 10lux, 2lux: darkness operation only.
| 7| 8| 9|
---|---|---|---|---
| | | 2lux
| | |
| | | 25lux
| | |
| | |
IMPORTANT INSTALLATION INFORMATION
-
Installation should be carried out in accordance with the latest edition of the National wiring regulations (For Australia please check the latest edition of the Wiring Rules -AS/NZS 3000:2007). If in doubt please consult a qualified electrician.
-
All luminaires run hot. It is the installer’s responsibility to consider fire risk and take appropriate precautions.
-
Input voltage – 180-240V 50/60Hz AC.
-
IP65 Rated suitable to resist low pressure jets of water.
-
These luminaires are not dimmable.
-
LED luminaire, there are no user serviceable parts in this luminaire.
-
Class 2 luminaire
-
These luminaires are for indoor and outdoor use.
-
These luminaires can be installed on the surface of combustible materials.
-
This product contains a light source of energy efficiency class D.
Emergency Versions: -
LED charge indicator: GREEN – Charging
OPERATION -
When charged, the Battery/Invertor unit will provide power to the fitting during an interruption in the power supply.
-
After installation the luminaire should be routinely tested by qualified and competent personnel using the schedule provided on the back of this installation guide.
BATTERIES AND DISPOSAL
- Replacement of complete luminaire or battery pack as appropiate is required when the battery or LEDs no longer meet their rated duration of operation.
Environmental Protection (W.E.E.E.) – Aurora’s WEEE Reg. No. WEE/BG0130YX (UK Only)
Waste Electrical & Electronic Equipment Regulations (WEEE) requires that any
of our products showing this marking (left) must not be disposed of with other
household or commercial waste. Aurora does not levy any WEEE disposal charges
to its customers for affected WEEE related products.
To prevent possible harm to the environment or human health from uncontrolled
waste disposal, please separate any such product from other waste types and
recycle it responsibly at your local facilities. Check with your Local
Authority, Recycling Centre or retailer for recycling advice. If, when you
purchased any Aurora product, your supplier included a WEEE disposal fee, you
should then contact your supplier for advice on his take back of the product
for the correct disposal.
GUARANTEE
This product is guaranteed for a period of 3 years from the date of purchase.
The guarantee is invalid in the case of improper use, installation, tampering,
and removal of the Q.C. date label, installation in an improper working
environment or installation not according to the current edition of the
National Wiring Regulations. Should this product fail during the guarantee
period it will be replaced free of charge, subject to correct installation and
return of the faulty unit. Aurora does not accept responsibility for any
installation costs associated with the replacement of this product. This
warranty is in addition to the statutory rights in your country of purchase.
Aurora reserves the right to alter specifications without prior notice.
Routine Test Record
- Month O Is the Initial Installation & Commissioning test.
NFPA Standard No. 101-31-1.3.7 – “A functional test shall be conducted on every required emergency lig/iing system at 30-day intervals for a minimum of 30 seconds. An annual test shall be conducted for the 1;, hour duration. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the alAhorly having jurisdiction.”
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>