Product Specifications

  • Description: Single-phase Automatic Reset PEN Fault Protection with Type A RCBO, load curtailment, and Type 2 SPD
  • Certification: UKCA, CE
  • Input Volts: Nominal input voltage single-phase 230V 50Hz
  • Max Load: 7.4kW
  • Terminal Capacity:
    • In L/N: 2.5mm2 – 25mm2
    • E: 2.5mm2 – 16mm2
  • Dimensions (H x W x D): 225mm x 275mm x 85mm
  • Weight: Approximately 5kg
  • Enclosure: Mild steel
  • Ingress Protection: IP2X
  • Warranty: 1 year limited warranty for replacement of faulty components

Product Usage Instructions

Installation:

  1. Ensure the power supply is switched off before installation.
  2. Connect the SP-RC-SPD unit to the existing TN-C-S earthing facility.
  3. Select the load curtailment limit (60A, 80A, or 100A) during installation.
  4. Follow the wiring instructions provided in the user manual.

Operation:

The SP-RC-SPD unit will isolate the charge point from the supply if household consumption exceeds the pre-set limit. It will automatically restore power to the charge point once the load falls back within the acceptable range.

Maintenance:

Regularly check for any signs of damage or wear on the unit. If any issues are detected, contact a qualified technician for inspection and potential replacement of faulty components.

Frequently Asked Questions (FAQ):

Q: What is the warranty period for the SP-RC-SPD unit?

A: The unit comes with a 1-year limited warranty from the date of purchase, covering replacement of faulty components.

Q: How do I set the load curtailment limit?

A: The load curtailment limit (60A, 80A, or 100A) must be selected at the time of order and will be configured during installation.

SP-RC-SPD

Single-phase Automatic Reset PEN Fault Protection with Type A RCBO, load curtailment and Type 2 SPD.

The SP-RC-SPD single-phase protection
device offers a compliant, simple, single connection centre, for EV charge point installations, allowing connection to the existing TN-C-S earthing facility without the use earth electrodes. Designed to facilitate compliance with BS:7671 2018, Amendment 2: 2022 Regulation 722.411.4.1 (iv). The SP-RC- SPD units come complete with 40A Type A RCBO, Type 2 SPD, and has the additional functionality for load curtailment, in line with Regulation 722.311.20. Isolating the charge point from the supply once the household consumption rises above the pre-set limit, and automatically restores the power to the charge point when the load falls back within a satisfactory level.

Please note , the load curtailment limit can be set at either, 60A, 80A, or 100A and must be selected at the time of order.

matt-e-SP-RC-SPD-Single-Phase-Automatic-Reset-PEN-Fault-Protection-
fig-1

Product Features and benefits

  • Built in matt:e PEN Fault Protection
  • NO EARTH ELECTRODES REQUIRED
  • Helps reduce disruptive and costly groundworks
  • Removes the risk of striking buried services
  • Simple wire in wire out connection
  • Over current protection
  • 40A Type A RCBO
  • Type 2 SPD
  • Load curtailment
  • Standard 1 Year parts warranty

Simplifying EV connection

matt-e-SP-RC-SPD-Single-Phase-Automatic-Reset-PEN-Fault-Protection-
fig-2

  • Description Single-phase Voltage Monitoring and Protection Unit

  • Certification UKCA, CE

  • Input Volts Nominal input voltage single-phase 230V 50Hz

  • Max Load 7,4kW

  • Terminal Capacity

    • In
      L/N: 2.5mm2 -25mm2
      E: 2.5mm2 —16mm2

    • Out
      L/N 2.5mm2 – 10mm2
      E: 2.5mm2 – 10mm

  • Dimensions ( H x W x D ) 225mm x 275mm x 85mm

  • Weight Approximately 5kG

  • Enclosure Mild steel

  • Ingress Protection IP2X

  • Warranty
    The matt:e SP-RC-SPD is guaranteed for a period of 1 years from the date of purchase. This warranty is limited to the replacement of faulty components only.

T: 01543 227290 | E: info@matt-e.co.uk | W: www.matt-e.co.uk
matt:e Ltd, Unit 1 Langley Brook Business Park, Middleton, Tamworth B78 2BP