RANCO O10-1402 Single Pressure Control Instruction Manual
- May 15, 2024
- RANCO
Table of Contents
RANCO O10-1402 Single Pressure Control
DESCRIPTION/APPLICATION
RANCO commercial pressure controls are used for either operating or protecting commercial refrigeration or air conditioning systems. They are suitable for R12, R22, and R502 refrigerants and are available with either male flare or capillary flare nut connections. Both low-pressure (suction sensing) and high- pressure (discharge sensing) versions are available. These controls, with NEMA 1 enclosures and snap action switches, may be used in a variety of applications: direct control of motors or compressors; with a contactor for pilot duty control; to control solenoid valves. The electrical ratings inside the control cover must not be exceeded.
- O10 Single pole, single throw (SPST) close (cut-in) on rise open (cut-out) on drop
- O11 Single pole, single throw (SPST) open (cut-out) on rise close (cut-in) on drop
- O16 Single pole, double throw (SPDT) 2-3 close on rise, open on drop 2-1 close on drop, open on rise
- O20 Double pole, single throw (DPST) close (cut-in) on rise open (cut-out) on drop
All O series are available in the automatic reset/cycling version. Manual reset versions of the O16 are available.
INSTALLATION
CAUTION
To prevent possible electrical shock or equipment damage, disconnect the
electrical power to the unit before and during installation. DO NOT restore
electrical power to the unit until the control is properly installed and
grounded. DO NOT locate the control in an explosive atmosphere as a safety
hazard can result due to possible spark generation in the control. Controls
are not to be located in areas of extreme moisture, dirt dust, or a corrosive
or explosive atmosphere. These environments can shorten control life.
IMPORTANT NOTICE
MANUAL OPERATION (tripping switch)
The switch can be manually operated by lifting the bellows to tabs as shown.
Operating the control at any other point WILL CAUSE CONTROL DAMAGE AND VOID
THE WARRANTY. DO NOT REMOVE the protective switch cover.
CONTROL BODY MOUNTING
Select a location that will permit proper capillary routing. It is important not to twist or strain the control body as shifting of the calibration may result. RANCO pressure controls can be mounted in any position, either vertically or horizontally, without affecting performance. The control can be mounted on an existing bracket, on the bracket provided, or can be flush- mounted without a bracket. Whichever method is selected, use only the mounting holes provided; no other holes are to be added to the control frame.
- Secure the control to a bracket with the 10-32 x 3/16 screws by using the two tapped holes in the back of the control.
- If other mounting screws are used, they must not protrude into the control more than 1/8” to avoid damage.
- When using the angle bracket, the control can be mounted to the compressor or any flat surface by using two or more of the four slotted holes in the base of the angle bracket.
- When flush mounting the control, use the .20-inch holes in the back of the control frame. Access can be gained by removing the front cover and securing the control body to a wall or any flat surface.
- Mounting to an uneven surface may cause improper control operation.
CAPILLARY CARE AND MOUNTING
Compressors vibrate. Copper work hardens and fractures when flexed beyond its
physical limits. Combining these two factors and broken capillaries can
result. Breakage can be prevented by proper installation practices.
- Minimize the number of times the capillary is bent. Each time it is rebent, it work-hardens making it more susceptible to breakage.
- Avoid sharp bends, kinks, strains or pinch marks in the capillary. Never allow the capillary to rest against sharp edges or rub against metal surfaces where it can be damaged by friction.
- The capillary should be straight within 4 inches of the pressure connection so the pulsations do not work- harming the capillary.
- Purge all tubing and lines before connecting pressure controls.
- Route the capillary so that it will be safe draining to minimize oil logging.
- When the control is mounted directly on the compressor, the capillary must be secured to the compressor so that everything moves together.
- If the capillary or control is shaking or vibrating against the compressor vibration, work-hardening of the capillary may occur, leading to eventual failure.
- When the control body is mounted remotely from the compressor and the pressure connections are on the compressor, vibration coils must be used between the compressor and the mounted control.
- The coils should not touch. A section of rubber pipe insulation inserted into the vibration coils and secured with silicone adhesive will keep the coils separated, yet allow them to absorb vibration.
- The capillary between the vibration coils and the control body should be secured to a stationary member when that distance.
- Coil and secure any excess capillary to avoid possible damage due to vibration. Capillary coils should be no less than 2 inches in diameter (3 inches is recommended).
- Silicone adhesive applied between the coils will keep them from rubbing.
- Although coiling and securing the excess capillary is important to dampen the effects of vibration, it is just as important to allow enough slack in the capillary so that it is not taut like a “banjo string”.
- On startup of the equipment, observe the capillary for excessive vibration and make corrections as required.
CONTROL WIRING
- Disconnect electrical power to the unit.
- All electrical wiring should conform to the National Electrical Code and local regulations.
- The electrical rating inside the control cover must not be exceeded. See below for DC ratings.
- Use copper conductors only.
- When mounting a conduit connector to the control frame, take care to not damage the control mechanism or the hinge pin.
- The terminals must not be bent, cut off, drilled or retapped. Electrical leads must not be taut; slack must be allowed for temperature change and vibration.
- Attach electrical leads to the switch terminals using the screws provided (also, see below for the O16), tightened to 15-20 inch pounds.
Volts | FLA | LRA | NIA | PD VA |
---|
010 and 011
with 1397004-2 magnet package installed
| 32| 9.3| 93| |
72| 7.3| 73| |
115| 4.6| 46| | 57.5
230| 2.3| 23| | 57.5
020
| 120| 4.6| 46| 3| 57.5
240| 2.3| 23| 0.5| 57.5
600| | | | 57.5
Refrigerant| Cut-Out Setting
---|---
Type| Air Cooled| Water Cooled
R12| 230 psi| 230 psi
R22| 360 psi| 300 psi
R502| 380 psi| 300 psi
The furnished cup washers are to be used on the O16 when the conductor wires are directly connected to the terminals. The stripped end of the conductors should be made into a clockwise-formed eye with an inside diameter to slip over the shank of the terminal screw. The cup washer, with its flanges outward, should be placed between the terminal and the screw head to capture the eye of the conductor
REMOTE MOUNTING
The capillary between the vibration coils and the control body should be secured to a stationary member when that distance exceeds 6 inches
CONTROL SETTINGS AND ADJUSTMENTS
ALL CONTROL SETTINGS are to be as specified by the equipment manufacturer and
as required for the application. DO NOT adjust the pointers beyond the highest
and lowest marks on the scaleplate. The scaleplate is only for reference and
the final setting should be verified with a gauge set. As a final check, the
system should be run through several cycles to ensure proper settings and
installation.
LOWEST EVENT
DO NOT set the control below the lowest event. On automatic reset controls,
if the combination of the Range (R.H. pointer) minus the Differential (L.H.
pointer) is lower than the Lowest Event, the control will not operate. See
Specifications on page 4 for the Lowest Event.
LOW-PRESSURE CONTROLS
Low-pressure controls which are used to cut out the compressor on pressure
drop should never be set to cut-out (cut-in minus differential) lower than 20
inches of vacuum on R12; single-stage R22 and R502 systems should never be set
lower than 3 inches of vacuum. Excessively low settings can cause compressor
damage. Manual reset O16 low-pressure controls have a scale plate that
indicates the pressure at which switch terminals 2-3 will lock open on
pressure drop (DO NOT set the pointer below the Lowest Event). The pressure
must rise approximately 10 PSIG above this setting before the control can be
reset.
HIGH PRESSURE CONTROLS
High-pressure controls which are used to cut out the compressor on pressure,
rise should normally be set no higher than the values shown below: Some high-
pressure controls are equipped with limit stops. Although the control setting
can be adjusted, the limit stop prevents adjustment higher than the limit stop
factory setting. DO NOT force the adjustment beyond the limit stop setting.
Manual reset O16 high-pressure controls have a scale plate that indicates the
pressure at which switch terminals 2-1 will lock open on pressure rise. The
pressure must drop by approximately 40 PSIG below this setting before the
control can be reset.
ADJUSTMENT EXAMPLES (See Control Settings and Adjustment P.3)
CLOSE ON RISE CONTROLS with Automatic reset 010 and 020; 016 terminals 2-3 The
scale plate directly indicates the cut-in and differential. The cut-out is
calculated by subtracting the differential from the cut-in:
- Adjust the range screw until the scale pointer indicates the desired cut-in setting.
- Adjust the differential screw until the scale pointer indicates the desired differential setting. The cut-out setting equals the cut-in setting, less the differential.
OPEN ON RISE
The scale plate directly indicated the cut-out and differential. The cut-in is
calculated by subtracting the differential from the cut-out:
- Adjust the range screw until the scale pointer indicates the desired cut-out setting.
- Adjust the differential screw until the scale pointer indicates the desired differential setting. The cut-in setting equals the cut-out setting, less the differential.
LOW-PRESSURE CHECK
Low-pressure controls can be preset by using a container of refrigerant and a
gauge set. Use a continuity meter to indicate the closing and opening of the
switch. Adjust the control to the desired settings; pressurize the control
while adjusting the settings. Low-pressure settings can be rechecked when the
unit is running by connecting a gauge to the suction line service valve. Close
the liquid line valve and allow the system to pump down, observing the low
switch opening (or closing). Open the liquid line valve and allow the pressure
to increase, observing the high switch closing (or opening). Adjust the
settings as necessary.
HIGH-PRESSURE CHECK
High-pressure control settings can be checked by selectively disconnecting
various stages of fans or by blocking the airflow on air-cooled condensers. On
water-cooled condensers, reduce or shut off the water flow while observing the
cut-out and adjust it as required.
CAUTION: These checks must be for a brief time only
| SPECIFICATIONS| O10
O11 O16
O20
---|---|---
Pressure Range P.S.I.G.
(Inches Mercury Vacuum)
| ****
Differential P.S.I.
| Lowest Event P.S.I.G.
(Inches Mercury Vacuum)
| ****
SPST-Opens Low
| ****
SPST-Opens High
| ****
SPDT-Opens High or Low
| ****
DPST-
Opens Low
Male Flare
| 36”
Capillary with Flare Nut
| 48”
Capillary with Flare Nut
| ****
Male Flare
| 36”
Capillary with Flare Nut
| ****
Male Flare
| 36”
Capillary with Flare Nut
| 48”
Capillary with Flare Nut
| 36”
Capillary with Flare Nut
LOW PRESSURE
| (12”) to 50| 5 to 35| (20”)| O10-1401| O10-1402| O10-1842| Use O16| O16-120| O16-557| –| O20-7002
(10”) to 100
| 10 to 40| (20”)| O10-1831| O10-1483| O10-1093| O11-1799| O11-3099| ****
O16-107
| ****
O16-527
| ****
–
| ****
O20-7004
Manual* Reset| (20”)| ****
Use O16
| ****
Use O16
| ****
O16-585
| ****
–
| ****
O16-261
| ****
–
HIGH PRESSURE
| 50 to 150| 10 to 40| 10| Use O16| Use O16| –| O16-166| –| –
100 to 250| 20 to 100| 0| O10-1807| –| O10-2000| Use O16| –| –| O16-593| –
100 to 400
| 40 to 150| 0| O10-1894| O10-2054| –| Use O16| O16-5870| O16-108| –|
O20-7006
17 Fixed| 83| Use O16| Use O16| –| O16-142| –| –
150 to 450
| 40 to 150| 0| Use O16| 011-1713| 011-1711| O16-503| –| –| –
Manual** Reset| 110| Use O16| Use O16| O16-209| –| O16-200| –
Locks on Pressure decrease. Pressure must rise approx. 10 PSI to be reset.
Locks on pressure increase. Pressure must stop approx. 40 PSI to be reset.
North Avenue
Carol Stream Illinois 60188 USA
Customer Service Telephone 1.800.304.6563
Customer Service Facsimile 1.800.426.0804
HVACCustomerService@Invensys.com
Invensys™, Robertshaw®, Ranco®, and Eliwell are trademarks of Invensys plc.,
its subsidiaries and/or affiliated companies.
All other brands mentioned may be the trademarks of their respective owners.
www.Uni-Line.com
www.InvensysControls.com
2013 Invensys
1515064 Rev C
For Technical Service
Telephone 1.800.445.8299
Facsimile 1.630.260.7294
TechnicalService@Invensys.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>