BITAMIN ANTPDU PW12V1 Antminer Distribution Europe Instruction Manual

May 15, 2024
BITAMIN

BITAMIN ANTPDU PW12V1 Antminer Distribution Europe

BITAMIN-ANTPDU-PW12V1-Antminer-Distribution-Europe-
product

Specifications

  • Name: ANTPDU PW12V1

Input Parameter:

  • Input Voltage: 346~480VAC, 3P+N+PE
  • Frequency: 50/60Hz
  • Input Current: 3Phase 100A

Output Parameters:

  • Output Rating: 83kW
  • Output Voltage: 3Phase 346~480VAC
  • Output Voltage (Single Phase): 200~277VAC
  • Output Bits: 12 Port 6pin + 1 Port 4pin
    Protect Grade: IP20

Working Environment

  • Working Temperature: -20°C~40°C
  • Working Humidity: 5%~90%RH Non-condensing
  • Altitude: 2000m

Store Environment:

  • Storage Temperature: -40°C~70°C
  • Storage Humidity: 5%~95%RH Non-condensing

Product Installation

Preparation before Installation
Before installation, ensure you have the necessary tools and materials ready. Check the electrical wiring diagram and PDU installation requirements.

Start Installation
Install according to the electrical wiring diagram and PDU installation requirements. Use cables that comply with the installation ground regulations for connection. The total lead length should not exceed 3m to prevent impedance issues. Ensure the input fixed wire buckle specification is PG36, and the input wireouter diameter does not exceed 32mm.

Inspection after Switch On
After connecting the PDU output port to all loads and closing the PDU circuit breaker, check the three-phase current imbalance detection function. The LED lights up based on the detected current, and corresponding LEDs light up when the N line current reaches specific values.

Outline Dimension
Refer to the product manual for the outline dimension details.

Frequently Asked Questions (FAQ)

  1. Q: What should I do if the red light indicating three-phase imbalance is on?
    A: Pay attention to the current imbalance display and check whether the server load is balanced. Use the product to test the load current imbalance situation.

PW12V1 Product Manual

BITAMIN TECHNOLOGIES INC. www.bitmain.com

Product specification

Product information Name ANTPDU
Model PW12V1
Input parameter Input voltage 346~480VAC,3P+N+PE
Frequency 50/60Hz
Input current 3Phase 100A
Output parameters Output rating 83kW
Output voltage 3Phase 346~480VAC
Output voltage 200~277VAC Single phase
Output bits 12 Port 6pin+1Port 4pin
Protect Grade IP20
Working environment Working temperature -20~40℃
Working humidity 5%~90%RH( Non-condensing)
Altitude ≤2000m
Store environment Storage temperature -40~70℃
Storage humidity 5%~95%RH( Non-condensing)

Certification

BITAMIN-ANTPDU-PW12V1-Antminer-Distribution-Europe-1

Overview

PW12V1 is a new generation of supercomputer power distribution unit. The product is equipped with 12 output ports, which can realize three-phase or single-phase voltage and current output of each output socket according to the actual needs of customers. Equipped with 125A three-phase hydraulic magnetic circuit breaker, the product can achieve overall overload protection, short circuit protection, the product provides each phase power LED status indication and three-phase load unbalance LED status indication. The product can adapt to the more complex working environment, through CB, cTUVus, CE-LVD and other safety certification.

Product installation

Preparation before installation
This power supply intelligent distribution unit PDU can only be installed and maintained by qualified professionals, and the installation location is a place that cannot be directly touched by human hands. Before installation, non-electric installation must be confirmed. The intactness of the entire PDU must be also checked. If any damage or damage to the appearance of the output terminals exists hence violating the basic requirements for product installation, please replace immediately or contact the manufacturer for replacement.

Start installation.
Install according to the electrical wiring diagram and PDU installation requirements. Use cables that comply with the installation ground regulations for connection. The total lead length should not exceed 3m, too long will increase the impedance. The input fixed wire buckle specification is

  • PG36, and the input wire outer diameter should not exceed 32mm.
  • L1, L2, L3, N recommended 3AWG (or 25mm²) cable, crimp terminal 25-6 OT terminal.
  • PE recommended 4AWG (or 16mm²) yellow-green cable, crimp terminal 25-8 OT terminal.

Inspection after switch on.

When the PDU output port is connected to all loads and the PDU circuit breaker is closed, the three-phase current imbalance detection function is checked and the LED lights up according to the actual detected current, and the corresponding LED lights up when the N line current reaches the set value.

That is

  • 10A corresponds to the first LED light,
  • 30A corresponds to two LEDs,
  • 55A for three LEDs,
  • 80A corresponds to four LEDs.

Note: LED light is only an alarm display, even if the light will not affect the operation of the equipment, only to remind customers that each phase load balance, three-phase imbalance will correspondingly increase the overall loss, the need to adjust according to the current display is to try to access the same number of miners in each group.

Outline Dimension

BITAMIN-ANTPDU-PW12V1-Antminer-Distribution-Europe-2

Wiring Schematic BITAMIN-ANTPDU-PW12V1-Antminer-Distribution-
Europe-3

installation Schematic BITAMIN-ANTPDU-PW12V1-Antminer-Distribution-
Europe-4

Caution
PDU Installation Please try to install the outlets centered on the shelf so that each cable is long enough to connect to the miner.

BITAMIN-ANTPDU-PW12V1-Antminer-Distribution-Europe-5 BITAMIN-ANTPDU-PW12V1-Antminer-Distribution-
Europe-6

Three‐phase unbalance alarm light schematic BITAMIN-ANTPDU-PW12V1
-Antminer-Distribution-Europe-7

Caution
When the red light is on, the user should pay attention to the current imbalance display, need to check whether the server is load balanced, the product should be used to test the load current imbalance light situation.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals