METRAVI Rapid Pro UNIKS RAPID PRO Multifunctional Tester User Manual
- May 15, 2024
- METRAVI
Table of Contents
Rapid Pro
Multifunction Installation Testers in your Pocket
Rapid Pro UNIKS RAPID PRO Multifunctional Tester
Loop
Non-Trip Earth Impedance| RCD
Tripping Time A, AC, F and AUTO| Har
Voltage Harmoncis (49Th)| Volt
TRMS AC Voltage Socket Test| MEM
Internal memory Report
---|---|---|---|---
Speed and Accuracy
Rapid Pro is a multifunction installation tester, socket size and performs
measure related to verification of electrical installation. It can be used as
a TRMS Multimeter, a SOCKET TESTER and more for electrical installation.
Safety certificate in accordance to IEC/EN61557-3 & IEC/EN61557-6. Powered by
a SUPERCAP component to keep the instrument powered on even when there is no
voltage in the line.
CAT III 300V
Volt e Socket Test
Measure TRMS VOLTAGE between L-N and Frequency (Hz).
SOCKET TESTER: No Ground – Voltage contact >50V L – N reverse. RCD
Measure Tripping time of RCD with outcome OK or NO OK.
– I∆n 30mA type A, AC ,F – Test x1, x5 , x1/2 and AUTO
– Complies with IEC/EN61557-6. Loop
Measure Non-trip Earth Impedance / Loop L-PE in TT or TN system with
Prospective short-circuit current complies with IEC/EN61557-6. Accuracy: 5%+
8digits in Std mode. Har
THD% and Voltage Harmonics up to 49th and shows result in graphical form or
numerical with THD%. MEM
AUTO Saving measurements (64) and REPORT via Smartphone with the RAPID PRO
REPORT APP.
TECHNICAL SPECIFICATIONS
RCD | IEC/EN61557-6 |
---|
Voltage L-Pe 190÷265V – Frequency 50Hz ± 5%
Type (RCD)| Resolution| Accuracy
AC , A , F| <0.1I∆n| ±(0.0% + 5%I∆n)
Time| 0.1 ms| ±(2 ms + 2 dgt)
LOOP (Fault Loop Impedance)| IEC/EN61557-3
Voltage L-Pe 190÷265V – Frequency 50Hz ±5% Min.Value > 0,3 Ω
Std Current test 15mA
RANGE (Ω)| Resolution (Ω)| Accuracy
0.01Ω – 9.99Ω| 0.01| ±(5.0% + 8 dgt)
10Ω – 99.9Ω| 0.1| ±(5.0% + 8 dgt)
100Ω – 999Ω| 1| ±(5.0% + 8 dgt)
LOW Test Current 6mA| ±(8.0% + 12 dgt)
Voltage AC TRMS (Phase-Neutral)
Crest Factor 1,5 ; Frequency 42 ÷ 69.0 Hz ±5%
RANGE (V)| Resolution (V)| Accuracy
120V – 265V| 1| ±(1.0% + 3 dgt)
Frequency
Voltage L-N 190÷265V – Frequency 50Hz ±5%
RANGE (Hz)| Resolution (Hz)| Accuracy
42Hz – 69Hz| 0.1| ±(2.0% + 1 dgt)
Voltage Harmonics
1 ÷ 50th Harmonics <0.8V will not be shown
RANGE (V)| Resolution(V)| Accuracy
0.8V – 256V| 0.1| ±(3.0% + 5 dgt)
Socket Test Voltage L-N 190÷265V
Open Ground or Neutral,Phase/Neutral Phase/Ground reverse – Vc>50V
GENERAL SPECIFICATIONS
INPUT:
Overvoltage Category: CAT III 300V
Max Voltage input: 265V AC
INPUT:
Measures Guidelines: IEC/EN61557-3 IEC/EN61557-6
Safety Guidelines: IEC/EN61010-1 IEC/EN61010-2-030
EMC: IEC/EN61326-1
Display and Memory:
Display: TFT 1.77” Full Colour
Memory Slot: 62
Enviromental Specification:
Reference Temperature: 23°C ±5°C
Operat onal Temperature: 5°C to 40°C
Maximum Humidity: <80%RH
Storage Temperature: 20°C to 60°C
Storage Humidity: <80%RH
Mechanical Characteristics:
Size: 81.5 x 70 x 83 mm
Weight: 110gms
W: www.metravi.com
E: erp@metravi.com