TRUE NORTH TN10-NA TN10 Wood Stove Instruction Manual

June 17, 2024
True North

**TRUE NORTH TN10-NA TN10 Wood Stove Instruction Manual

**

INSTALLATIO AND OPERATING INSTRUCTIONS

IMPORTANT:
THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER SAVE THESE INSTRUCTIONS

SAFETY NOTICE: If this stove is not properly installed, a house fire may result. For your safety, follow the installation instructions. Contact local building or fire officials about restrictions and installation inspection requirements in your area.

TESTED and LISTED to CAN/ULC S627 AND UL 1482 Meets the Environmental Protection Agency’s Crib wood Particulate Emission Standards

WARNING

HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
NEVER ALLOW CHILDREN TO TOUCH GLASS

NOTE: WE STRONGLY RECOMMEND THAT SMOKE AND CARBON MONOXIDE DETECTORS BE INSTALLED IN THE AREA WHERE THE HEATER IS TO BE INSTALLED.

If smoke detectors have been previously installed, you may notice that they are operating more frequently.

This may be due to curing of stove paint or fumes caused by accidentally leaving the fire door open. Do not disconnect the detectors.

SAFETY NOTICE: If this stove is not properly installed, a house fire may result. For your safety, follow the installation instructions. Contact local building or fire officials about restrictions and installation inspection requirements in you area.

Please read this entire manual before you install and use your new room heater. Failure to follow instructions may result in property damage, bodily injury, or even death.

Experience will give you the right settings for proper combustion and efficient burning. Remember the correct air inlet setting is affected by variables such as type of wood, outside temperature, chimney size and weather conditions. With practice, you will become proficient in operating your heater and will obtain the performance for which it was designed.

Specifications

Rating label location

The Rating label is located on the lower portion of the rear cover.

This manual describes the installation and operation of the True North, TN10 Freestanding wood heater.

SAFETY NOTICE:

This wood heater needs periodic inspection and repair for proper operation. It is against federal regulations to operate this wood heater in a manner inconsistent with the operating instructions in this manual.

This heater meets the 2020 U.S. Environmental Protection Agency’s crib wood emission limits for wood heaters sold after May 15, 2015.

Under specific test conditions this heater has been shown to deliver heat at rates ranging from 13,100 to 17,600 Btu/ hr.

Efficiency and BTU Output

EPA Certified Emissions : 1.4 grams per hour
LHV Tested Efficiency 1: 80.4%
HHV Tested Efficiency 2: 72.6%
EPA BTU Output 3: 13,084 – 17,623 btu/hr
Maximum Wood Length: 14 inches
Ideal Wood Length : 12 inches
Fuel: Seasoned Cord wood

  1. Weighted Average Lower Heating Value (LHV) efficiency as tested using CSA B415 Performance testing of solid-fuel burning heating appliances. LHV assumes the moisture is already in a vapor state so there is no loss of energy
  2. Weighted Average Higher Heating Value (HHV) efficiency as tested using CSA B415 Performance testing of solid-fuel burning heating appliances. HHV includes the energy required to vaporize the water in the fuel
  3. The range of BTU outputs is based on efficiency using CSA B415 Performance testing of solid-fuel-burning heating appliances and burn rates from the low and high EPA tests using Douglas Fir dimensional lumber.

Safety and Maintenance

WARNING: Never use chemicals or any other volatile liquid to start a fire. Do not burn garbage, or flammable fluids such as gasoline, naphtha, or engine oil.

WARNING: ONLY USE MATERIALS SUPPLIED BY MANUFACTURER WHEN DOING MAINTENANCE OR REPLACEMENTS.

  1. Burn only dry and well seasoned cord wood. The denser or heavier the wood when dry, the greater its heat value. This is why hardwoods are generally preferred. Green or wet wood will cause a rapid buildup of creosote. If you feel it is necessary to burn wet or unseasoned wood, do so only with the air inlet set open enough to maintain a good strong fire and fairly high chimney temperatures. Do not attempt to burn overnight using green wood or wet wood. Wet wood can cause up to 25% drop in heater output, as well as contributing significantly to creosote buildup.

  2. Remove ashes frequently. Embers can roll out the door and create a fire hazard. Maintain a 1″(25mm) minimum ash base.

  3. If glass becomes darkened through slow burning or poor wood, it can readily be cleaned  with fireplace glass cleaner when stove is cold. Never scrape with an object that might scratch the glass. The type and amount of deposit on the glass is a good indication of the flue pipe and chimney buildup. A light brown dusty deposit that is easily wiped off usually indicates good combustion and dry, well seasoned wood and therefore relatively clean pipes and chimney. On the other hand, a black greasy deposit that is difficult to remove is a result of wet and green wood and too slow a burning rate. This heavy deposit is building up at least as quickly in the chimney.

  4. DOOR GASKETS – The gasket used for the True North (5/8″(16mm) medium density fiberglass rope) requires only light pressure to seal. This will prolong seal life. It is important that the doorseal be maintained in good condition. Periodically inspect seals and replace if necessary. Follow instructions included in the TN19.DGKIT kit obtainable from your nearest True North dealer.

  5. DOOR GLASS – Do not slam loading door or otherwise impact glass. When closing door, make sure that no logs protrude to impact the glass. If the glass gets cracked or broken, it must be replaced before using the stove. Replacement glass can be obtained from your dealer. Use 9-1/4″(235mm) x 13-1/4 (337mm) x 5 mm. Ceramic glass only. Do not substitute with any other type.

    • To remove broken glass, undo the four retaining screws and remove clamps, noting position for re-assembly. Remove all particles of glass. Be careful as they are very sharp. Install new glass complete with gasket. Replace clamps and screws.
      CAUTION:

    • do not overtighten, tighten screws very carefully

    • do not clean glass when hot

    • do not use abrasive cleaners on glass

  6. The area where boost combustion air enters the firebox must be kept clear of excessive ash buildup which will block air flow. This area is at the front of the firebox.

  7. Do not store wood within heater installation clearances, or within the space required for  fuel loading and ash removal. Keep the area around the heater clean and free of loose combustibles, furniture, newspapers, etc.

  8. Establish a routine for the fuel, wood burning and Lighting techniques. Check daily for creosote buildup in the firebox, until you are experienced and are operating the stove cleanly and safely.

  9. Be aware that the hotter the fire, the less creosote is deposited. More frequent chimney cleaning may be necessary in mild weather or when burning “wet” or unseasoned wood.

  10. Instruct all members of your family on the safe operation of the heater. Ensure they have enough knowledge of the entire system if they are expected to operate it. Stress the section on chimney fires and the importance of following the steps outlined “In Case of Chimney Fire”.

Maintenance Checks

Check the following parts for damage such as cracks, excessive corrosion, burned out sections and excessive warping:

Weekly:

  • Firebrick – Visual, for cracking.
  • Door Gasket – sagging, placement, damage.

Monthly

  • Brick rail tabs and brick rails.
  • Back side of air wash chamber.
  • Boost tube cover.
  • Top baffle board.
  • Baffle Tubes.

As Needed

  • It is recommended that the chimney be inspected a minimum of every 2 months and cleaned as needed a minimum of 2 times a year

When Cleaning the Chimney System:

  • Top heat shield and mounting bolt.
  • Brick Rails.
  • Manifold.
    • Replace the baffle tubes if they show signs of cracking or breakage.
    • Please contact your Dealer for replacement parts, if you experience any of the damage listed above’s Continuing to operate your stove with broken parts may accelerate damage to other parts and will void your warranty

Blower :

The blower should be cleaned out a minimum every six months by using a vacuum on the grill openings in the back and bottom of the blower casing to remove any dust and debris.

Reducing Visible Emissions and Creosote

When wood is burned too slowly, it produces tar and other organic vapours, which combine with expelled moisture to form creosote. The creosote vapours condense in the relatively cool chimney flue of a slow burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an extremely hot fire. The chimney connector and chimney should be inspected periodically (at least once every two months) during the heating season to determine if a creosote buildup has occurred. If creosote has accumulated (3 mm. or more), it should be removed to reduce the risk of a chimney fire.

  1. Highest smoke densities and visible emissions occur when a large amount of wood is added to a bed ofhot coals and the air inlet is closed. The heated wood generates smoke, but without ample air, the smoke cannot burn. Smoke-free, clean burning requires small fuel loads, two or three logs at a time or 1/4 to 1/2 of fuel load and leaving the air inlet relatively wide open, especially during the first 10 to 30 minutes after each loading, when most of the smoke generating reactions are occurring. After 30 minutes or so, the air inlet can be turned down substantially without excessive smoke generation. Wood coals create very little creosote-producing smoke.
  2. The cooler the surface over which the wood smoke is passing, the more creosote will be    condensed. Wet or green wood contributes significantly to creosote formation as the excess moisture that is boiled off cools the fire, making it difficult for the tars and gases to ignite, thus creating dense smoke and poor combustion. This moisture-laden smoke cools the chimney, compounding the problem by offering the smoke the ideal place to condense.

In summary, a certain amount of creosote is inevitable. Regular inspection and cleaning is the solution. The use of dry, seasoned wood and ample combustion air will help to minimize annoying smoke emissions and creosote buildup.

Chimney Fires

The dangerous side effect of excessive creosote buildup is a chimney fire. This causes much higher than normal temperatures in the chimney and on its exterior surfaces. Temperatures inside the chimney can exceed 2000°F (1100°C). Ignition of nearby or touching combustible material is more likely during a chimney fire. Proper clearances are critical to prevent damage during such a fire. Chimney fires are easy to detect; they usually involve one or more of the following:

  • Flames and sparks shooting out of the top of the chimney
  • A roaring sound
  • Vibration of the chimney

To Avoid a Chimney Fire

  1. Burn wood cleanly. Do not burn wet wood or turn down the unit too quickly after loading.
  2. Do not let creosote build up to a point where a chimney fire is possible.
  3. Do not have fires in the heater that may ignite chimney fires. These are excessively hot fires, such as when burning household trash, cardboard, Christmas tree limbs, or even ordinary fuel wood; (eg. with a full load on a hot bed of coals and with the air inlet wide open for more time than is needed to completely char a fresh fuel load.)
  4. The Chimney and connector pipe should be inspected /cleaned periodically.

In the event of a Chimney Fire

Have a fire extinguisher handy. Contact your local municipal or state/provincial fire authority for further information on how to handle a chimney fire. It is most important that you have a clearly  understood plan on how to handle a chimney fire.

  1. Close down the air inlet on the stove.
  2. Call the local fire department.
  3. Prepare to evacuate to ensure everyone’s safety. Have a well understood plan of action for evacuation. Have a place outside where everyone is to meet.
  4. After the chimney fire is out, the chimney must be cleaned and checked for stress and  cracks before starting another fire. Also check combustibles around the chimney and the roof. The services of a competent or certified installer, (certified by the Wood Energy Technical Training program (WETT) – in Canada, National Fireplace Institute (NFI) – in U.S.A., are strongly recommended.

Operation

CAUTION: Hot while in operation. Keep children, clothing and furniture away. Contact may cause skin burns.

WARNING: Always keep loading door closed when burning. This heater is not designed for open door burning.

WARNING: No alteration or modification of the combustion air control assembly is permitted. Any tampering will void warranty and could be very hazardous.

WARNING: Do not use grates or andirons to elevate the fuel. Burn directly on the fire bricks. Replace broken or missing bricks. Failure to do so may create a hazardous condition.

WARNING: Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or ‘freshen up’ a fire in this heater. Keep all such liquids well away from the heater while in use.

Your True North heater is designed for maximum overall efficiency at a moderate firing rate. Overfiring is hazardous, a waste of fuel and will damage your stove. Too slow a burn may contribute to creosote buildup and lowers combustion efficiency.

Wood Selection

This heater is designed to burn natural wood only. Higher efficiency and lower emissions generally result when burning air-dried seasoned hardwoods, as compared to softwoods or to green or freshly cut hardwoods.

Wood should be properly air dried (seasoned) for six months or more. Wet or undried wood will cause the fire to shoulder and produce large amounts of creosote. Wet wood also produces very little heat and tends to go out often.

DO NOT BURN:

  • Salt water wood
  • Wet or green wood
  • Garbage
  • Lawn clippings/yard waste
  • Railroad ties
  • Materials containing rubber, including tires
  • Waste petroleum products, paints or paint thin- nears, or asphalt products
  • Construction or demolition debris
  • Treated wood
  • Coal/charcoal
  • Solvents
  • Unseasoned wood
  • Manure or animal remains
  • Materials containing plastic
  • Materials containing asbestos
  • Paper products, cardboard, plywood, or particleboard.
  • These materials contain chlorides which will rapidly destroy metal surfaces and void warranty.

Burning these materials may result in the release of toxic fumes or render the heater ineffective and cause smoke.

The prohibition against burning these materials does not prohibit the use of fire starters made from paper, cardboard, saw dust, wax and similar substances for the purpose of starting a fire in an affected wood heater.

Do not burn anything but cord wood. Other fuels, eg. charcoal, can produce large amounts of carbon monoxide, a tasteless, odorless gas that can kill. Under no circumstances should you attempt to barbecue in this heater.

How to Test Your Wood

Add a large piece of wood to the stove when it has a good large bed of coals. It is dry if it is burning on more than one side within one minute. It is damp if it turns black and lights within three minutes. If it sizzles, hisses and blackens without igniting in five minutes it is soaked and should not be burned.

Lighting a Fire

Remove the retaining clip on the front of the baffle before lighting for the first time.

  1. Move air control lever to the left-most position (maximum firing rate) and open door.
  2. Place crumpled newspaper in the center of the heater and crisscross with several pieces of dry kindling. Add a few small pieces of dry wood on top.
  3. Ignite the paper and leave the door ajar approximately 1/2″(13mm) – 1″(25mm) until the wood kindling is fully engulfed in flame.
  4. After the kindling is fully engulfed add a few small logs. Close door.
  5. Begin normal operation after a good coal base exists and wood has charred.

Normal Operation

WARNING: This wood heater has a manufacturer-set minimum low burn rate that must not be altered.

It is against federal regulations to alter this setting or otherwise operate this wood heater in a manner inconsistent with the operating instructions in this manual.

  1. Set air control to a desired setting. If smoke pours down across the glass (waterfall effect) this indicates you have shut the control down too soon or you are using too low a setting. The wide range control panel makes finding the desired setting for your application easy. As every home’s heating needs vary (ie. insulation, windows, climate, etc.) the proper setting can only be found by trial and error and should be noted for future burns.
  2. To refuel, adjust air control to high, and give the fire time to brighten. Open the door slowly, this will prevent back puffing.
  3. Use wood of different shape, diameter and length (up to 14″ (355mm)). Load your wood and try to place the logs so that the air can flow between them. Always use dry wood.
  4. Do not load fuel to a height or in such a manner that would be hazardous when opening the door.
  5. For extended or overnight burns, unsplit logs are preferred. Remember to char the wood completely on maximum setting before adjusting air control for overnight burn.

Restarting After Extended or Overnight Burns

  1. Open door and rake hot embers towards the front of the heater. Add a couple of dry, split  logs on top of embers, close door.
  2. Adjust air control to high (control lever to the left) and in just a few minutes, logs should begin burning.
  3. After wood has charred, reset air control to desired setting.
  4. To achieve maximum firing rate, set air control lever to the left-most position. Do not use this setting other than for starting or preheating fresh fuel loads.

DO NOT OVERFIRE THIS HEATER : Attempts to achieve heat output rates that exceed heater design specifications can result in permanent damage to the heater and chimney.

Proper Draft

  1. Draft is the force which moves air from the appliance up through the chimney. The amount of draft in your chimney depends on the length of the chimney, local geography, nearby obstructions and other factors.
  2. Too much draft may cause excessive temperatures in the appliance. An uncontrollable burn or a glowing red stove part or chimney indicates excessive draft.
  3. Inadequate draft may cause back puffing into the room and plugging of the chimney. Smoke leaking into the room through appliance and chimney connector joints indicates inadequate draft.

Curing of the Paint Finish

To achieve the best finish, the paint on your stove must be baked on with small fires. When burning your stove for the first 2-3 times it is very important that the room be well ventilated. Open all windows and doors. Smoke and fumes caused by the curing process may cause discomfort to some individuals.

Ash Removal

Caution: Ashes are to be removed only when the heater is cold. Whenever ashes get 3″(76mm) to 4 (102mm) deep in your firebox, and when fire has burned down and cooled, remove excess ashes. Leave an ash bed approximately 1″ (25 mm) deep on the firebox bottom to help maintain a hot charcoal bed.

Disposal of Ashes

Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed outside on a non-combustible floor or on the ground, well away from all combustible materials, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in closed container until all cinders have thoroughly cooled. Other waste should not be placed in this container.

Heat Output

Experience will give you the right settings for proper combustion and efficient burning. Remember that the correct air inlet setting is affected by variables such as type of wood, outside temperature, chimney size and weather conditions. With practice, you will become proficient in operating your heater and will obtain the performance for which it was designed.

Stove Dimensions

Stove Dimensions

Residential Installation

Warning: Under no circumstances is this heater to be installed in a makeshift or “temporary” manner. It may be fired only after the following conditions have been met.

  • DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
    DO NOT INSTALL IN ANY FIREPLACE.

  • DO NOT INSTALL IN A SLEEPING ROOM.

  • THIS ROOM HEATER MUST BE CONNECTED TO:

    1. A CHIMNEY SYSTEM LISTED TO: UL 103HT (USA) or ULC-S629 (CANADA) or
    2. A CODE APPROVED MASONRY CHIMNEY WITH A FLUE LINER.
  • DO NOT ATTEMPT TO CONNECT THIS HEATER TO ANY AIR DISTRIBUTION DUCT.

  • The services of competent installer are strongly recommended.

  • Outside combustion air or fresh air into the room may be required in your area, consult local building codes (See “Combustion Air” on page 20).

NATIONAL FIREPLACE INSTITUTE

CERTIFIED
www.nficertified.org

We recommend that our products be installed and serviced by professionals who are certified in the U.S. by the National Fireplace Institute (NFI) or in Canada by Wood Energy Technical Training (WETT)

Crate Removal

  1. Carefully remove wood top and supports.
  2. Remove plastic cover.
    • Remove the retaining clip on the front of the baffle before lighting for the first time

Residential Clearances

  • BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE 6″(150mm) DIAMETER AND LISTED TO: CANADA – CONNECTOR – LISTED to ULC S-641 and CHIMNEY LISTED to ULC-S-629 USA – CONNECTOR AND CHIMNEY LISTED to UL-103 HT
  1. Residential Clearances to Combustible surfaces and materials; This heater may be installed using a single-wall connector (smoke pipe) as per local and National fire and Installation codes. See Single wall Connector in Figure 3. Clearances may be reduced with various heat shielding or insulating materials. Consult national fire codes and authorities for approval ( U.S. -NFPA 211 or CAN. – CSA B365) For for close clearances, use a listed double-wall connector, See Figure 2. “Double Wall Connector”.
  2. Mobile Home installation must use listed double-wall connector, For installation in a mobile home, see clearances in Figure 8 on page 19.

**Minimum Clearance to Combustibles

**

Ember Protection

The stove may be installed on a combustible floor, provided ember protection made from a non-combustible material (a minimum K value of 23.7 btu/ft h °F /the equivalent of 20 Gauge steel) is used. UL 1618 type 1 protection

This protection must extend as follows:

In Canada: 18″ (457 mm) from the loading door on the firing side and 8″ (203 mm) from the sides. See Figure 3, below.

In USA: 16″ (406 mm) to the front of the firebox and 8″ (203 mm) from the sides of the fuel loading door opening. See Figure 4, below. This protection is also required under the chimney connector and 2″ (51 mm) beyond each side.

Securing Bracket Installation:

These will be needed to anchor the stove in a mobile home installation and are recommended when installing combustion air to prevent movement of the unit and separation of the combustion air intake.

  1. The hold down brackets are provided in a bag with the unit. Insert the brackets by sliding them through the slots in the rear legs. Then lag the bracket to the floor or hearth pad.

Double-Wall Connector

  • Use a listed double-wall connector.
  • Install all components to the chimney connector manufacturer’s installation requirements.

Single-Wall Connector

Smoke pipe (chimney connector) must be:

  • As short and straight as possible, use 6″(150mm) diameter, minimum 24 gauge black pipe, that is clean and in new condition.
  • Secured at every joint and collar with 3 sheet metal screws.
  • Installed with the crimped or male ends pointing down. This will carry any liquid creosote or condensation back into the stove.
  • The Smoke pipe/chimney connector shall not pass through an attic, roof space, closet or similar concealed space, or a floor, or ceiling. Where passage through a wall, or partition of combustible material is desired, the installation shall conform to CAN/CSA-B365, INSTALLATION CODE FOR SOLID-FUELBURNING APPLIANCES AND EQUIPMENT or NFPA 211 STANDARD FOR CHIMNEYS, FIREPLACES AND SOLID FUEL BURNING APPLIANCES

Procedure

  1. Position stove and floor protection (with hole for combustion air if required) in accordance with the clearances as stated on the label and in Figure 2., and Figure 3 or Figure 4.
  2. Mark the position for the hole in the ceiling and roof by using a string and plumb-bob.
  3. Check that the intended location will not interfere with floor joists, ceiling joists or rafters before proceeding further.
  4. As per the chimney manufacturer’s instructions;
    • Cut a hole in the ceiling and roof to suit the chimney system and frame in the sides. The chimney support is mounted to the framing. If a roof or ceiling support is used in the installation, you will find the chimney manufacturer’s complete instructions packed with the roof support.
    • Assemble the chimney sections so the finished length is resting on the support and protruding through the roof. Install the radiation shield. Avoid having chimney joints between ceiling and roof.
    • Assemble flashing and storm collar and be sure to secure the flashing and seal with the appropriate sealant. Attach rain cap and check flashing for leaks.
  5. If double-wall connector pipe is to be connected between the stove and the listed insulated chimney, install all components to the pipe manufacturer’s installation requirements.
  6. If smoke pipe is being used to connect between the stove and the listed insulated chimney,
  7. Install the smoke pipe (chimney connector), crimped edge of the pipe down and inside the stove collar. Use holes provided in collar to secure pipe with three screws.
  8. Install the remaining lengths of pipe, one on top of the other to the finished height of the listed insulated chimney adapter and secure to each other. A slip-section will make attaching the smoke pipe to the chimney system adapter easier.

The chimney may incorporate an offset. To do this safely, all sections of listed connector, offset elbows and chimney section must be screwed together by at least three sheet metal screws per joint.

The chimney must be suitably supported by the chimney manufacturer’s listed offset support. All vent manufacturer or national are code clearances to combustible must be observed.

Ensure that the Masonry chimney meets all National Fire Protection Association and local building codes. Have the chimney cleaned and inspected by a professional to ensure there are no cracks, weak mortar or other signs of deterioration. See pipe manufactures installation instructions for further information

Through Wall Installations
(as per NFPA 211-2013)

ATTENTION: VAPOUR BARRIER MUST BE MAINTAINED WHEREVER CHIMNEY OR OTHER
COMPONENTS PENETRATE TO THE EXTERIOR OF THE STRUCTURE. SEE LOCAL BUILDING CODES FOR PROPER AND APPROVED METHODS OF MAINTAINING VAPOUR BARRIER.
Through Wall Installations

System A. Minimum 3.5 in. (90 mm) thick brick masonry wall framed into combustible wall with  minimum of 12 in. (305 mm) brick separation from clay liner to combustibles. Fireclay liner (ASTM C 315, Standard Specifications for Clay Fire Linings, or equivalent), minimum 5/8 in. (16 mm) wall thickness, shall run from outer surface of

Minimum Clearance 12 in. (305mm)
Through Wall Installations

System B. Solid-Insulated, listed factory-built chimney length of the same inside diameter as the chimney connector and having 1 in. (25.4 mm) or more of insulation with a minimum 9 in. (229 mm) airspace between the outer wall of the chimney length and combustibles.

The inner end of the chimney length shall be flush with the inside of the masonry chimney flue and shall be sealed to the flue and to the brick masonry penetration with non-water-soluble refractory cement.

Supports shall be securely fastened to wall surfaces on all sides. Fasteners between supports and the chimney length shall not penetrate the chimney liner.

Minimum Clearance 9 in.
Through Wall Installations

System C. Sheet steel chimney connector, minimum 24 gauge [0.024 in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24 gauge [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 mm) air channels, separated from combustibles by a minimum of 6 in. (152 mm) of glass fiber insulation.

Opening shall be covered, and thimble supported with a sheet steel support, minimum 24 gauge [0.024 in. (0.61 mm))] in thickness.

Supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold chimney section. Fasteners used to secure chimney section shall not penetrate chimney flue liner.

Minimum Clearance: 6 in. (152mm)
Through Wall Installations

Mobile Home Installation

Warning: Under no circumstances is this heater to be installed in a makeshift or “temporary” manner. It may be fired only after the following conditions have been met.

  • DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
  • DO NOT INSTALL IN A SLEEPING ROOM.

THIS HEATER MUST BE INSTALLED WITH LISTED DOUBLE-WALL CONNECTOR. BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE 6″(150mm) DIAMETER AND LISTED TO: IN CANADA – ULC S-641 LISTED CONNECTOR AND ULC-S-629 LISTED CHIMNEY, IN USA – UL-103 HT LISTED CONNECTOR AND CHIMNEY

  • Outside combustion air supply must be used for Mobile Home installations see “Combustion Air” on page 20

**Mobile Home Clearances

**

Installation

Minimum chimney height from top of unit is 12′ (3.66 m) or as per chimney manufacturers roof clearances whichever is greater.

NOTE: Longer chimney lengths and different pitch flashings may be used. Install all components to the connector or chimney manufacturer’s installation requirements. Consult your chimney supplier for installation advice.

Procedure:

Follow Installation procedures “Securing Bracket Installation:” on page 13 plus the following extra steps.

WARNING: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED.

Note: See “Combustion Air” on page 20.

  • Attach stove to floor using two 1/4″ x 1″ or longer lag screws.
    If installing a leg model, insert anchor tabs into slot on bottom of two rear legs and secure to floor with 1/4″ x 1″ or longer lag screws.

  • If installing the Optional Blower Kit the unit must be grounded to the mobile home

Combustion Air

Combustion air can be supplied to the stove in one of two ways. Consult your local building code or CAN/ CSA-B365, or NFPA 211

  1. Direct outside air supply – (Necessary for mobile home installation, optional for residential installation.)

    • To draw outside air through the floor; Attach the outside air adapter to the underside of the stove. Mark then cut or drill a 3″(76mm) diameter or larger hole in the floor under the adapter. This hole must get its air from a ventilated crawl space or be extended with duct to the outdoors (Figure 6 on page 15. or Figure 7 on page 16 If you are getting the intake air from a well ventilated crawl space, Connect the adapter to 3″(76mm) flexible or rigid metal venting passing thru the hole using into the ventilated space. Cover the inlet of the pipe with a 20GA wire mesh minimum rodent screen, and clamp in place.
      If you are extending the pipe thru to the outside, Install an approved 3″(76mm) inlet vent cap into the closest outside wall. Connect the stove’s adapter to the Inlet vent through the hole using 3 (76mm) flexible and/or rigid metal venting.

    • To draw air from behind the stove. Cut or drill a corresponding hole in the closest exterior wall. Install an approved 3″(76mm) inlet vent cap. Attach the outside air adapter to the underside of  thestove. Connect the adapter to the inlet vent cap using 3″(76mm) flexible and/or rigid metal venting. Provide water protection as required.

  2. Room air supply – Remove the knockout or cover plate from the bottom of the Air box enclosure. The stove will now draw its air from the room through this opening and into the firebox intake

Note:

The use of outside combustion air for installation requires the unit to be secured to the structure to prevent dislodging of the air duct (“Securing Bracket Installation:” on page 13).

The living space around the heater must be well ventilated with good air circulation. Anything that may cause a negative pressure can cause gases or fumes to be pulled into the living area. During extremely cold weather, and especially when burning at very slow rates, the upper parts of the exposed chimney may ice up, partially blocking the flue gases. If blockage occurs, flue gases may enter living space.

This unit is not designed to be operated with the firing door open. In addition to the obvious hazard of sparks landing on combustibles, an open fire door will cause the heater to draw air from the living space and possibly cause suffocation in an air tight home.

Baffle Board / Tube Installation

The Chimney connector pipe should be disconnected from the wood stove to clean and inspect the chimney. Only if this is not possible should you remove Baffle Board.

DO NOT OPERATE WITH BAFFLE BOARD INSULATION OR TUBES REMOVED.

Removal

  1. With a set of vise-grips, grasp the front baffle tube on the right, slightly away from the baffle air assembly.
    While squeezing tightly, use a hammer to hit the pliers and pull the tube to the right to disengage the tube from the hole on the left. Allow the tube to hang freely from the hole on the right.

  2. Repeat step #1 for second baffle tube.

  3. Grasp the front edge of the left half of the baffle board and tilt up at the back. Guide the board down and through the door opening. Caution – Baffle Board material is very fragile.

  4. Grasp the right half of the baffle board and slide it over to the left.

  5. Tilt the back of the board up and guide it down and through the door opening.

  6. Reverse the process to replace the baffle assembly.

Installation

  1. Insert one half of baffle board above the two back baffle tubes inside the firebox, slide over  to the right and allow to rest on the baffle air assembly.
  2. Ensure that the second half is inserted to allow the two cuts in the baffle boards to overlap. Insert the other half of the baffle board and allow to rest on the left side baffle air assembly.
  3. With the holes facing forward and the notch to the left side, insert a baffle tube into the hole in the baffle air channel on the right at an angle and then raise and insert into the opposite hole on the left side baffle air assembly.
  4. With a set of vise-grips, grasp the baffle tube on the left, slightly away from the baffle air assembly. While squeezing tightly, use a hammer to hit the pliers and push the tube to the left to engage the tube in the hole on the left.
  5. Repeat steps #3 & #4 with the remaining baffle tube.
  6. Slide the baffle board halves in with the notches overlapping (one notch facing up and one notch facing down). Then separate, to ensure there are no gaps on either side, between the baffle board and the Secondary Air Chambers.
  7. Push baffle board tight against the rear of the

Optional Blower

The optional blower kit, (part #31140001) is equipped with a three prong power cord and may be installed at any time. Route power supply cord away from heater.

Electrical rating: 115V, 60Hz, 0.5 amps.

Blower Installation

  1. Remove the 4 screws and cover plate from the rear shield on the stove (Figure 10).
  2. Using the same 4 screws, place the blower into the opening in the rear shield with the blower outlet pointing up (Figure 11).
  3. Tighten the screws.

Blower Operation

Proper blower speed matched with air control setting will ensure peak performance from your stove.

  • Except on “High” setting, wait 30 minutes before turning on blower to desired setting.

Remove the cover plate

Firebrick Installation

Firebrick Installation

This package contains 10 full-size firebricks.

With the heater in the upright position, install firebricks as follows:

  • Install each side brick, insert the brick under the retaining flange near the front of the baffle air box on each side of the firebox and then slide the brick to the back of the unit.
  • Next install 3 firebricks on the bottom of the unit. Place them to the rear of the firebox.
  • Finally place 3 firebricks at the back of the heater, by inserting the bricks under the rear retainer

Appendix A

Troubleshooting
Problem Cause Cure
Glass is Dirty
  1. Wood is wet
  2. Turning down air control or damper too soon
  3. Draft too low
  4. Door gasket leakage

|

  • Use dry wood
  • Do not turn down until) there is a good bed of coals) the wood is charred
  • Improper chimney height and / or diameter
  • Chimney plugged or restricted, check flue
  • Provide outside air for combustion
  • Replace gasket
  • Check latch

Excessive Creosote Buildup – See 1, 2, 3, above.
Low Heat Output|

  1. Wood is wet
  2. Fire too small
  3. Draft too low

|

  • Use dry wood- Build a larger fire
  • Chimney plugged or restricted, inspect and clean

Won’t Burn Overnight|

  1. Air control is set too high
  2. Not enough wood
  3. Draft too high

|

  • Set control lower
  • Unsplit wood is preferred for overnight burns
  • Excessive chimney height and/or diameter, See “Proper Draft” on page 10.

Stove Won’t Burn|

  1. Combustion air supply blocked
  2. Draft too low

|

  • Check outside air supply for obstruction
  • Check that room air cover is removed
  • Chimney plugged or restricted, inspect and clean
  • Chimney oversized or otherwise unsuitable, consult Dealer

Parts Diagram

Parts Diagram

(WHEN ORDERING, INCLUDE PART NUMBER WITH DESCRIPTION)

ITEM DESCRIPTION PART NO
1 Baffle Board (2pcs.), TN10 80002159
2 Baffle Tube Set (4pcs.), TN10 80002162
3a Secondary Air Chamber Left, TN10 (c/w gasket/screws) 80002162
3b Secondary Air Chamber Right, TN10 (c/w gasket/screws) 80002163
4 Door Assembly – No Glass, TN19/20/10, Met Black 80000621
5 Door and Glass Gasket, TN10/19/20/40. 80000600
6 Glass, TN10/19/20/40 (c/w clamps / gasket) 80000616
7 4 pc Glass Clamp set (c/w screws.) 80000617
8 Firebrick Set, TN10. 80002161
9 Flame Shield, TN10 80002164

Not Shown
| Rear Brick Rail, TN10| 80002165
| Blower, Wood/Gas, Insert, Hinge Side| 80000905
| Switch, Rheosta| 80000908
| Blower, Knob, Speed Contro| 80000909
| Optional Blower Kit| 31140001

©2023 Copyright Pacific Energy Fireplace Products LTD.

Reproduction, adaptation, or translation without prior written permission is prohibited except as allowed under the copyright laws.

For technical support, please contact your retailer
Web site: www.truenorthstoves.com
2975 Allenby Rd., Duncan, BC V9l 6V8

Company Logo

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals