PHILIPS EM164C Emergency Twin Spot Instruction Manual

June 17, 2024
Philips

PHILIPS EM164C Emergency Twin Spot

PHILIPS-EM164C-Emergency-Twin-Spot-product

WHAT IS IN THE BOX

PHILIPS-EM164C-Emergency-Twin-Spot-fig-1

SPECIFICATION

PHILIPS-EM164C-Emergency-Twin-Spot-fig-2

Dimensions

PHILIPS-EM164C-Emergency-Twin-Spot-fig-3

Inrush current

PHILIPS-EM164C-Emergency-Twin-Spot-fig-4

ATTENTION
OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC-SENSITIVE DEVICES

  • The luminaire shall be installed bv a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
  • When the light source reaches its end of life the whole luminaire shall be replaced.
  • Clean with dry cloth.
  • Philips Lighting warranty is applicable only if the indicated drivers are used.

INSTALLATION

PHILIPS-EM164C-Emergency-Twin-Spot-fig-5 PHILIPS-EM164C-Emergency-Twin-Spot-fig-6 PHILIPS-EM164C-Emergency-Twin-Spot-fig-7 PHILIPS-EM164C-Emergency-Twin-Spot-fig-8

  1. For indoor use only.
  2. The luminaire complies with IEC60598-1IEC 60598-2-22.
  3. The luminaire must be installed by a qualified electrician and wired in accordance with the latest IEE Electrical regulations or the national requirements.
  4. Turn off the power supply before checking, installation, maintenance or moving.
  5. Do not switch on before complete installation.
  6. Batteries shall only be replaced by the manufacturer or his service agent or a similar qualified person. Batteries should be replaced when the luminaire no longer meets the 3 hours duration performance. Product mains surge immunity is 0.5/1KV (diff. / comm. mode). To prevent excessive currents and voltages from damaging the device, make sure that the power supply input is equipped with additional protection devices such as surge protectors. For any questions regarding the product’s surge protection, please consult the manufacturer’s professional.

Please inform yourself about the local waste disposal, separation and collection system for electrical and electronic products and packaging. Please act according to your local rules and do not dispose your old product and packaging with your normal household waste. The correct disposal of the packaging, your product and/or batteries will help prevent potential negative consequences for the environment and human health.Batteries should be disposed separately from the municipal waste stream via designated collection facilities.When disposing a product that contains non-user replaceable batteries, the non-user replaceable batteries shall be removed by a professional.

Testing Record

PHILIPS-EM164C-Emergency-Twin-Spot-fig-9

Emergency Twin Spot

Specifications For Self Test

Function Test
The function test is conducted every month for 3 minutes to check whether the battery connection is abnormal and discharge the battery. Duration Test An initial duration test is conducted when the battery is connected to the controller for the first time and connected to mains, but after 24 hours charging.
The yearly duration test is conducted for 3 hours on one day within the 300th day to the 365th day every year. It will also check the connection of battery.

Description corresponding to the color and status of the charge indicator

PHILIPS-EM164C-Emergency-Twin-Spot-fig-10

It should be taken to check connectivity or replace the abnormal battery or lamp.

Test button for manual inspection on function test or duration test mode of operation

Duration Description
Press for <2s Simulate emergency mode.

Press for 3-5s

| Start duration test manually. The test can be aborted by pressing off (1-2s).

  • Must be conducted when the initial duration test finished and after another 24 hours battery charging.

Press for 5-8s| Start Function test manually for 60s. The test can be aborted by pressing off (1-2s).
Press for >10s| Time Reset.

Note:

  • When the mains is on, the green indicator will be permanently on. It will check the connection of battery and LED module. When the mains is off, no test will perform.
  • The luminaires whick perform the function and duration tests must be connected to the mains supply for at least uninterrupted 24 hours. If the mains is off during these tests, the tests will be postponed for 3 days.
  • When the fault is corrected, the indicator will only be reset to its normal status after mains reconnected or test switch pressed.
  • An accuracy of the timing of the test interval is ensured that it has an accuracy of ±75 s per week. The timing function will be retained through periods of mains supply failure or interruption for up to 7 days.

Read User Manual Online (PDF format)