ELFBULB EBW-05-10 Wall Mounted Lithium Battery
Product Information
Specifications:
- Model: ELF52V-200-10K-WM
- Nominal Voltage: 51.2V
- Capacity: 200Ah
- Energy: 10.24KWh
- Equalization Charge Voltage: 58.4V
- Float Charge Voltage: 54.4V
- Max. Continuous Charging Current: 200A
- Max. Continuous Discharge Current: 200A
- Max C Rating: 1C
- Parallel Connection: Up to 15 packs with full communications RS485/RS232/CAN
- Battery Cells: Lithium Iron Phosphate (LifePO4)
- Design Life: 10+ Years
- Cycle Life: Above 6000 cycles @80% DOD, +/-3500 cycles @100% DOD
- Certification: CE, UN38.3, MSDS
- Operating Temperature: Charging: 0 to +50°C, Discharging: -10 to +50°C, Storage: -10 to +55°C
- Protection: Electronic Circuit Breaker, BMS Voltage Protection, Current Limiting
- Net Weight: 88KGS
- Dimension: 590375245 mm
- Warranty: 10 years or 3500 cycles, whichever comes first
- Baud Rate: 500K (for most communication interfaces)
Frequently Asked Questions
- Q: Can I install the battery in a corrosive environment?
- A: No, it is not recommended to install the battery in a corrosive environment as it may damage the components.
- Q: What should I do if I encounter a fire near the battery?
- A: Do not use water to extinguish the fire. Use appropriate fire extinguishing methods and evacuate the area immediately.
- Q: How long is the warranty for the product?
- A: The warranty period is 10 years or 3500 cycles, whichever comes first.
Brands
BMS communication protocol is compatible with the following brands of inverters
SPECIFICATIONS
ITEM | SPECIFICATIONS |
---|---|
Model | Wall-Mounted |
Nominal Voltage | 51.2V |
Capacity | 200Ah |
Energy | 10.24KWh |
Equalizad Charge Voltage | 58.4V |
Float Charge Votage | 54.4V |
Max.Continuous Charging Current | 200A |
Max.continuous Discharge Current | 200A |
Max C Rating | 1C |
Parallel | Parallel Connection up to 15 packs with full communications |
Communication interface | RS485/RS232/CAN |
Battery Cells | Lithium Iron Phosphate(LifePO4) |
Design Life | 10+ Years |
Cycle Life | Above 6000 cycles @80%DOD,+/-3500 cycles@100%DOD |
Certification | CE,UN38.3,MSDS |
Operating Temperature | Charging:0 to +50℃,Discharging:-10 to +50℃ |
Storage | -10 to +55℃ |
Protection | Electronic Circuit Breaker,BMS Voltage Protection,Current Limiting |
Net Weight(KGS) | 88KGS |
Dimension | 590375245 |
Warranty | 10 years or 3500 cycles whichever comes first |
Featres
Wall-mounted Lithium Battery 51.2V200Ah
- Easy for installation and maintenance with software BMS monitoring
- Support high current charging/discharging
- Support RS485,RS232 and CAN communications
- Intelligent BMS can be compatible with most of the inverter brands in the market
Thank you for using this product, ELFBULB is committed to providing high- quality, most cost-effective energy products to users all over the world
Important Safety Instructions, Precautions
Please keep this manual for future reference
This manual contains all safety, installation and operation instructions for EBW-05-10 wall-mounted energy storage.
Please read all instructions and precautions in the manual carefully before installation and use. The company does not undertake the violation of general safety operation requirements or safety standards in the design, production and use of equipment any responsibility. There is an unsafe voltage inside the energy storage battery. To avoid personal injury, users should not disassemble it by themselves. For maintenance, please contact professional maintenance personnel.
Precautions
- During the installation process, it is strictly forbidden to operate with power on, and connect the wires correctly during installation, and do not connect them in reverse.
- Please ensure that the parameters between related devices are compatible and matched.
- Please ensure that the installation environment of the equipment is well ventilated.
- When the equipment is running, do not block the vents or heat dissipation system to prevent fire caused by high temperature.
- Do not place the device in an environment of flammable, explosive gas or smoke, or high-salt spray environment, nor perform any operations in this environment.
- The load strength of the mounting surface should be greater than the load caused by the weight of the product.
- Please be properly grounded before use to ensure your safety.
- The annual temperature of the installation area should be between 0°C and 50°C.
- The relative humidity of the air should be less than 85%
Warning
Basic Information
Product overview and features
Our products have been strictly tested and inspected before leaving the factory. If you find any abnormalities in the equipment, please contact the provider. EBW-05-10 wall-mounted energy storage battery is a device used to store energy in a photovoltaic solar system.
Product features: This product is composed of high-quality lithium iron phosphate aluminum shell cells, high-efficiency BMS, and an anti-static metal shell. The square aluminum shell cell has high stability and fast heat dissipation. The BMS effectively manages overcharge and over discharge, short circuit, and over temperature. The thickened metal shell has better protection performance.
Features of the system: EBW-05 can provide 100A continuous discharge and 100A charging capacity (recommended charging below 100A); EBW-10 can provide 200A continuous discharge and 200A charging capacity (recommended 100A) .It supports 6000 cycles of 80% DOD. A larger capacity battery pack can be formed by parallel connection to meet the long-term power supply needs of users. The closed line design is adopted to effectively prevent dust and mosquitoes from blocking the interface and increase the safety of use.
Basic parameters
EBW-05: 51.2V100Ah EBW-10: 51.2V200Ah
ITEM | SPECIFICATIONS |
---|---|
Model | ELF52V-100-5.12K-WM |
Nominal Voltage | 51.2V |
Capacity | 100Ah |
Energy Power | 5.12Kwh |
Equalized Charge Voltage | 58.4V |
Float Charge Voltage | 44.8V |
Max.Continuous Charging Current | 100A(Recommended 50A ) |
Max.Continuous Discharging Current | 100A |
Max C Rating | 1C |
Model| ELF52V-200-10K-WM
Nominal Voltage| 51.2V
Capacity| 200Ah
Energy Power| 10.24Kwh
Equalized Charge Voltage| 58.4V
Float Charge Voltage| 44.8V
Max.Continuous Charging Current| 200A(Recommended 100A )
Max.Continuous Discharging Current| 200A
Max C Rating| 1C
Product function introduction
- Handle
- Display screen
- Button
- Indicator light
- Self-locking switch.
- Bracket
- Cable hole
- Cover plate
- Foothold
- Negative terminal
- RS485-B
- RS485-A
- Positive terminal
- RS232
- CAN
- RS485
- Dry contact
- ADS
- Breakers
- Heat Sink Hole
Function table
NO | Name | Function |
---|---|---|
1 | Handle | For moving |
2 | Display screen | Show battery status |
3 | Button | Battery Settings, battery status checking |
4 | Indicator light | Battery status indicator |
5 | Self-locking switch | ON / OFF |
6 | Bracket | Support or fix the battery |
--- | --- | --- |
7 | Cable hole | Make the positive .negative wire and communication cable pass |
through
8| Cover plate| Keep out dust and safety protection
9| Foothold| Prevent the battery from directly touching the ground and
damaging the surface
10| Negative terminal| Connect the negative wire
11| RS485-B| RS485-B Communication
12| RS485-A| RS485-A Communication
13| Positive terminal| Connect the positive wire
14| RS232| RS232 Communication
15| CAN| CAN Communication
16| RS485| RS485 Communication
17| Dry contact| /
18| ADS| Battery parallel Communication settings
19| Breakers| Leakage short circuit protection
20| Heat sink hole| Heat dissipation and dust isolation
Dimensions
Installation instructions
Installation preparation
- Safety Requirements: This system should only be installed by personnel who have received training in power systems and have sufficient knowledge of power systems. During installation, the safety regulations described below and local safety regulations should always be followed.
- Make sure that all devices are powered off before operating, and use devices or accessories that match the battery parameters.
- The wiring of power distribution cables should be reasonable and have protective measures to avoid contact with these cables when operating power equipment.
- Wear appropriate protective measures, such as: goggles, gloves, installation clothing, etc.
- Need to prepare installation tools:
Drill | Hammer | Wrench | Screw | Wire strippers |
---|---|---|---|---|
Insulating tape | Electric pencil | Multi meter | Pliers | Measuring ruler |
Engineering Coordination
Attention should be paid to the following items before construction.
- Power line specification:The power line specification shall meet the requirements of maximum discharge current for each product.
- Mounting space and bearing capacity: Make sure that the batteries has enough room to install, and that the batteries rack and bracket have enough load capacity.
- Make sure the power line and ground wire are reasonable. Not easy to short-circuit water and corrosion
Equipment installation
- Align the bracket with the hole, place the expansion screw, and lock the expansion screw
- Align the clasp and hang the battery on the mounted bracket
- Installation complete
Step1| Installation preparation| Confirm that the ON/OFF switch is off on the
front panel of EBW-05-10
---|---|---
Step2
| Mechanical Installation| 1.Cabinet placement position determination
2.Top cable harness pre-installed
3.Batteries module installation
Step3
| ****
Electrical Installation
|
1. Batteries module parallel cable installation
2. Batteries module total positive cable installation
3. Batteries module total negative cable installation
4. Internal RS485 communication interface connection
Step4
| ****
Batteries System self-test
| 1. Press the ON/OFF switch to the “ON” state
2.BMS system power on activation
3. Check the system output voltage
4. Shut down the system
Step5
| Connecting inverter| 1.Connect total positive & total negative cable
2. Connect the external RS485 communication cable to the inverter
Parallel connection
Introduction
- Prepare the screwdriver, cable set, communication line
- Remove the cover plate with a screwdriver, pass the positive pole, negative pole, and communication wire through the cover plate and the coil respectively. After debugging, lock the cover plate and press the switch before use. As shown in the picture:
Electrical interface check
Devices that connected directly to the batteries can be user equipments, power supplies,and other power supplies.
- Please check if the user’s PV power generation equipment, power supplier or other power supply equipment has a DC output interface, and the voltage meet the requirements of the inverter.
- And check the maximum discharge current capability of the DC power interface of the user’s photovoltaic power generation equipment, power supply or other power supply equipment should be greater than the maximum charging current of the products.
Electrical installation
Before connecting the power cables, using multi meter to measure cable continuity, short circuit, confirm positive and negative, and accurately mark the cable labels.
Measuring methods:
- Cable availability: select the buzzer and use the probe to measure the ends of the same color cable. If the buzzer calls, it means the cable is available.
- Short circuit judgment: choose multi meter resistor file, probe the same end of positive and negative pole, if the resistor shows infinity, means that the cable is available.
- After visual testing of power line is connected well, the positive and negative poles of the batteries shall be connected respectively to the positive and negative poles of the opposite terminal.
It is better to add a circuit breaker between the inverter and the batteries system. The selection of the circuit breaker requires:
Use, maintenance and troubleshooting
Batteries system usage and operation instructions
After completing the electrical installation, follow these steps to start the batteries system
- Refer to 1.3, Press the self-locking switch to ON position, The display screen and indicator will light up
- After the indicator self-test, the RUN indicator will light and the SOC indicator will be on.
Note:
- After pressing the power button, if the batteries status indicator on the front panel continues to be red, please refer to the “3.5 Alarm description and processing “.If the failure cannot be eliminated, please contact the dealer timely.
- Use a voltmeter to measure whether the voltage of the circuit breaker batteries access terminal is greater than 43V, and check whether the voltage polarity is consistent with the inverter input polarity. If the circuit breaker batteries input terminal has a voltage output and is greater than 43V, then the batteries has started normal work.
- After confirming that the batteries output voltage and polarity are correct, turn on the inverter, close the circuit breaker.
- Check if the indicator of the inverter and batteries connection (communication indicator and batteries access status indicator)is normal. if it is normal, successfully complete the connection between the batteries and the inverter. If the indicator light is abnormal, please refer to the inverter manual for the cause or contact the dealer.
Operating mode
Charging voltage protection and charging current protection
ELF52V-100-5.12K-WM
Charging voltage protection
Overcharge protection
| Overcharge warning voltage| 56.8V
---|---|---
Overcharge protection voltage| 57.6V
Overcharge protection delay| 1.0S
Charging current protection
Charging over current protection
| Charging over current warning current| 100A
---|---|---
Charging over current protection current| 105A
Charge over current protection delay| 1.0S
ELF52V-200-10K-WM
Charging voltage protection
overcharge protection
| Overcharge warning voltage| 56.8V
---|---|---
Overcharge protection voltage| 57.6V
Overcharge protection delay| 1.0S
Charging current protection
Charging over current protection
| Charging over current warning current| 205A
---|---|---
Charging over current protection current| 210A
Charge over current protection delay| 1.0S
Discharge voltage protection and discharge current protection
ELF52V-100-5.12K-WM
Discharge voltage protection
over-discharge protection
| Over-discharge warning voltage| 44.8V
---|---|---
Over-discharge protection voltage| 44V
Over-discharge protection delay| 1.0S
Discharge current protection
Discharge over current 1 protection
| Discharge over current 1 alarm current| 100A
---|---|---
Discharge over current 1 protection current| 105A
Discharge over current 1 protection delay| 5.0S
Discharge over
current 2
| Discharge over current 2 protection current| ≥120A
Discharge over current 2 protection delay| 1500mS
ELF52V-200-10K-WM
Discharge voltage protection
over-discharge protection
| Over-discharge warning voltage| 44.8V
---|---|---
Over-discharge protection voltage| 44V
Over-discharge protection delay| 1.0S
Discharge current protection
Discharge over current 1 protection
| Discharge over current 1 alarm current| 205A
---|---|---
Discharge over current 1 protection current| 210A
Discharge over current 1 protection delay| 5.0S
Discharge over
current 2
| Discharge over current 2 protection current| ≥250A
Discharge over current 2 protection delay| 1500mS
Ambient temperature alarm protection
Ambient temperature warning
| Ambient low temperature warning temperature| -15℃
---|---|---
Ambient low temperature protection temperature| -20℃
Ambient low temperature protection release temperature| -15℃
Ambient high temperature warning temperature| 65℃
Ambient high temperature protection temperature| 75℃
Environmental high temperature protection contact temperature| 65℃
Other Protection
- Short Circuit Protection
- When there is a short circuit situation, the short- circuit protection will be trigered and the protection will be released after the load is removed or there’s a charging source connected.
- Self- Shutdown
- When there are no external loads and power supply and no external communication for over 24 hours , the device will dormant standby automatically.
Key description and buzzer action description
Key description
- When the BMS is in sleep state, press the button (3~6S) and release it, the protection board will be activated, and the LED indicators will light up sequentially for 0.5 seconds from “RUN”.
- When the BMS is active, press the button (3~6S) and then release it, the protection board will be dormant, and the LED indicators will light up for 0.5 seconds from the lowest battery light.
- When the BMS is active, press the button (6~10S) and release it, the protection board will be reset, and all LED lights will light up simultaneously for 1.5 seconds.
- After the BMS is reset, it still retains the parameters and functions set by the host computer. If it is necessary to restore the initial parameters, it can be realized through the “restore default value” of the host computer. However, the relevant operating records and stored data remain unchanged (such as power, cycle times, protection records, etc.)
buzzer action description
- When there is a fault, it will beep 0.25S every 1S;
- During protection, it beeps for 0.25S every 2S (except for over voltage protection);
- When alarming, beep 0.25S every 3S (except for over voltage alarm);
The buzzer function can be enabled or disabled through the host computer, and the factory default is disabled.
Working status of the indicator light
LED working status indication
State
| Normal /
Alarm /
Protection
| ON/ OFF| RUN| ALM| SOC Indication LEDs|
Instructions
---|---|---|---|---|---|---
| | | | | | | |
Power Off| Sleep| OFF| OFF| OFF| OFF| OFF| OFF| OFF| OFF| OFF| All off
Standby
| Normal| ON| Flash1| OFF|
Indication by SOC
| Standby
Alarm| ON| Flash1| Flash3| Cell low
voltage
Charge
| Normal| ON| ON| OFF|
Indication by SOC (The top SOC Led Flash 2)
| Maximum power LED flash(flash 2),ALM does not flash for over-charge
warning
Alarm
|
ON
|
ON
|
Flash3
Over Charge Protection|
ON
|
ON
|
OFF
|
ON
|
ON
|
ON
|
ON
|
ON
|
ON
| If no mains supply, LED as
standby
Temperature. Over-current Fault Protection|
ON
|
OFF
|
ON
|
OFF
|
OFF
|
OFF
|
OFF
|
OFF
|
OFF
|
Close charge
Discharge
| Normal| ON| Flash3| OFF|
Indication by SOC
|
Alarm| ON| Flash3| Flash3
Under| ON| OFF| OFF| OFF| OFF| OFF| OFF| OFF| OFF| Close
Temperature. Over-current. Short Circuit Fault Protection|
ON
|
OFF
|
ON
|
OFF
|
OFF
|
OFF
|
OFF
|
OFF
|
OFF
|
Close discharge
Fault
| |
OFF
|
OFF
|
ON
|
OFF
|
OFF
|
OFF
|
OFF
|
OFF
|
OFF
| Close charge
Close discharge
Capacity Instructions
State | Charge | Discharge |
---|---|---|
Capacity indicator light | L6 |
| L5
| L4
| L3
| L2
| L1
| L6
| L5
| L4
| L3
| L2
| L1
Electricity(%)
| 0~16.6%| OFF| OFF| OFF| OFF| OFF| flash2| OFF| OFF| OFF| OFF| OFF| ON
16.6~
33.2%
|
OFF
|
OFF
|
OFF
|
OFF
|
flash2
|
ON
|
OFF
|
OFF
|
OFF
|
OFF
|
ON
|
ON
33.2~
49.8%
|
OFF
|
OFF
|
OFF
|
flash 2
|
ON
|
ON
|
OFF
|
OFF
|
OFF
|
ON
|
ON
|
ON
49.8~
66.4%
|
OFF
|
OFF
|
flash2
|
ON
|
ON
|
ON
|
OFF
|
OFF
|
ON
|
ON
|
ON
|
ON
66.4~
83.0%
|
OFF
|
flash2
|
ON
|
ON
|
ON
|
ON
|
OFF
|
ON
|
ON
|
ON
|
ON
|
ON
83.0~100%|
flash2
|
ON
|
ON
|
ON
|
ON
|
ON
|
ON
|
ON
|
ON
|
ON
|
ON
|
ON
Running light | ON| flash(flash 3)
Communication Description
RS232
The BMS can communicate with the host computer through the RS232 interface, so that various information of the battery can be monitored through the host computer, including battery voltage,Current, temperature, status and battery production information, etc., the default baud rate is 9600bps.
CAN
- CAN communication, the default communication rate is 500K
RS485
- With dual RS485 interfaces, you can view the information of PACK, and the default baud rate is 9600bps.
- If you need to communicate with the monitoring device through RS485, the monitoring device acts as the host and polls the data according to the address
DIP switch setting
- When the PACKS are used in parallel, different PACKS can be distinguished by setting the address through the DIP switch on the BMS.
- It is necessary to avoid setting the same address. For the definition of the BMS DIP switch, refer to the table below:
Form 4.4
Address | Dial code switch position |
---|---|
#1 | |
0 | OFF |
1 | ON |
2 | OFF |
3 | ON |
4 | OFF |
5 | ON |
6 | OFF |
7 | ON |
8 | OFF |
9 | ON |
10 | OFF |
11 | ON |
12 | OFF |
13 | ON |
14 | OFF |
15 | ON |
Demonstration of DIP switch for 4 unit batteries in parallel
Communication interface definition as shown below
Electrical interface definition
RS232–Adopt 6P6C vertical RJ11 socket
RJ11 pin| Definition description
2| NC
3| TX(veneer)
4| RX(veneer)
5| GND
CAN and RS485 interface
CAN– adopts 8P8C vertical RJ45 socket | RS485– 8P8C vertical RJ45 socket |
---|---|
RJ45 pin | specifies |
1、2、3、6、8 | NC |
5 | CANL |
4 | CANH |
7 | GND |
Parallel communication port
Interface | Definition |
---|---|
B+ | The positive pole of the battery PACK is used to supply power to the BMS; |
the positive power P+ is directly connected to the positive pole of the
battery
B-| Battery PACK negative pole
P-
| The negative electrode of the battery PACK, that is, both the negative
electrode for charging and the negative electrode for discharging (the same
port for charging and discharging)
| J2-1| NTC1| J4-1| NTC2
J2-2| NTC| J4-2| NTC
J2-3| CELL1-| J4-3| CELL5+
J2-4| CELL1+| J4-4| CELL6+
| J2-5| CELL2+| J4-5| CELL7+
---|---|---|---|---
J2-6| CELL3+| J4-6| CELL8+
J2-7| CELL4+| |
J5-1| NTC3| J6-1| NTC4
J5-2| NTC| J6-2| NTC
J5-3| NC| J6-3| CELL13+
| J5-4| CELL9+| J6-4| CELL14+
J5-5| CELL10+| J6-5| CELL15+
J5-6| CELL11+| J6-6| CELL16+
J5-7| CELL12+| |
Compatible to brand inverter
NO | Brand of inverter |
---|---|
1 | Deye |
2 | Pylontech |
3 | Growatt |
4 | Sofar |
5 | Luxpower |
6 | VOLTRONIC POWER |
7 | Sunsynk |
8 | Goodwe |
9 | Megarevo |
10 | Solis |
11 | Must |
12 | Srne |
13 | Schneider |
14 | Phocos |
15 | Victron energy |
16 | Sorotec |
17 | SMA |
18 | Aoguan |
19 | Invt |
20 | Sako |
21 | Solark |
22 | Afore |
23 | Mppsolar |
Storage and use environment requirements
- Working temperature: -20℃~+55℃
- The charging temperature range: 0C~+55℃
- Discharge temperature range: -20℃~+55℃
- Storage temperature: -10℃~+35℃
- Relative humidity: 5% ~ 85%RH
- Altitude: no more than 4000m
- During storage, recharge once every 6 months to 60%-80%DOD
- Working environment: indoor installation, the site is protected from the sun, no wind, no conductive dust and corrosive gas
Attachment table
Pay attention to check before unpacking
Loading and unloading should be carried out in accordance with the rules and
regulations to prevent the sun and rain.
The total number of packages should be indicated on the shipping manifest
accompanying each package and checked for completeness.
During the unpacking process, handle with care to protect the surface coating
of the object.
When opening the package, the installer should read the technical documents,
verify the list, and ensure that the items are complete and complete according
to the configuration sheet and packing list. If the internal package is
damaged, the shipper should be contacted in time
Thank for choosing ELFBULB