APC by Schneider Electric 750VA Smart UPS Uninterruptible Power Supply Instruction Manual

June 17, 2024
APC by Schneider Electric

APC by Schneider Electric 750VA Smart UPS Uninterruptible Power Supply Instruction Manual
APC by Schneider Electric 750VA Smart UPS Uninterruptible Power Supply
Instruction Manual

Important Safety Instructions

SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.

Read the instructions carefully and look at the equipment to become familiar with the device before trying to
install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to either a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury
NOTICE
NOTICE
is used to address practices not related to physical injury.

Product Handling Guidelines

Product Handling Guidelines

Safety and General Information

Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage

General safety

  • Adhere to all national and local electrical codes.
  • All wiring must be performed by a qualified electrician.
  • Changes and modifications to this unit not expressly approved by APC by Schneider Electric could the warranty.
  • This UPS is intended for indoor use only.
  • Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
  • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation
  • For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
  • The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.

Deenergizing safety
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit (mains). Before installing or servicing the equipment check that the:

  • Input circuit breaker is in the OFF position.
  • Internal UPS batteries are removed

Electrical safety

  • Use tools with insulated handles.
  • Do not handle any metallic connector before power has been disconnected.
  • For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a qualified electrician.
  • 230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe, output cords attached to the UPS must not exceed 10 meters in length.
  • The protective earth conductor for the UPS carries the leakage current from the load devices (computer equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the UPS. The conductor must have the same size and insulation material as the grounded and ungrounded branch circuit supply conductors. The conductor will typically be green, with or without a yellow stripe.
  • Leakage current for a pluggable, Type A UPS may exceed 3.5 mA when a separate ground terminal is used.
  • The UPS input ground conductor must be properly bonded to protective earth at the service panel.
  • If the UPS input power is supplied by a separately derived system, the ground conductor must be properly bonded at the supply transformer or motor generator set.

Battery safety

WARNING
RISK OF CHEMICAL HAZARD AND EXCESSIVE HEAT

  • Recycle the UPS when the UPS battery error is detected at the end of its service life. Power off the UPS and unplug it from the AC input.
  • The battery is not user replaceable. Contact APC by Schneider Electric Worldwide Customer Support if there are defects in the product and the product is within warranty.

Failure to follow these instructions can result in death or serious injury.

Note : Servicing of user replaceable batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions. In this case, the battery is not user replaceable.

  • The battery typically lasts for five to ten years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life.

  • For longest battery performance, the ambient temperature should be maintained between 68 and 77 °F (20 and 25 °C).

  • Replace the UPS immediately if the unit indicates battery replacement is necessary.

  • The batteries are not user replaceable. Under normal operating conditions, there is no need for replacement.
    If attempting to replace batteries, contact APC by Schneider Electric customer support.

  • APC by Schneider Electric uses Lithium Ion batteries. Under normal use and handling, there is no contact with the internal components of the battery.

  • Do not drive nails into the battery pack.

  • Do not strike the battery pack with a hammer.

  • Do not stand on the battery pack.

  • Do not place or use the battery pack near heat or fire.

  • Do not use a dropped, damaged or deformed battery pack

  • Do not use the battery pack to power other equipment.

  • CAUTION: Before installing or replacing the batteries, remove conductive jewelry such as chains, wrist watches and rings. High energy through conductive materials could cause severe burns.

  • CAUTION: Do not dispose of battery pack in a fire. The batteries may explode.

  • CAUTION: Do not open or tamper with the battery enclosure. Doing so will expose the cell terminals which pose an energy hazard.

  • CAUTION: A battery can present a risk of electric shock and burns by high short-circuit current.

  • CAUTION: Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

  • CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.

General information

  • The model and serial numbers are located on a small label on the rear panel. For some models, an additional label is located on the chassis under the front bezel.
  • Always recycle used batteries. For information on recycling batteries, go to apc.com/recycle.
  • Recycle the package materials or save them for reuse.

FCC Class A radio frequency warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are intended to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Specifications

For additional specifications, refer to the APC Web site at www.apc.com

Environmental specifications

**Temperature** Operating 0 to 40 °C (32 to 104 °F)
Storage -40 to 35 °C (-40 to 95 °F)
Transporting -40 to 80 °C (-40 to 176 °F)
**Maximum Elevation** Operating 10,000 ft. (3,048 m)
Storage 25,000 ft. (7,620 m)
Transporting 50,000 ft. (15,240m)
**Shelf Life** **Storage** Limited by battery state of charge. If

initial state of charge is 100%, batteries must be recharged when storage time exceeds 12 months.
Transporting| 2 weeks maximum
Humidity| 0% to 95% relative humidity, non-condensing
International Protection Code| IP20

**Dimensions and weights
SMTL750RM2UC/SMTL750RM2UCNC /
SMTL1000RM2UC/SMTL1000RM2UCNC

SMTL1500RM3UC/SMTL1500RM3UCNC

**

Model Dimensions H x W x D Weight
SMTL750RM2UC/SMTL750RM2UCNC 3.4 x 17.25 x 12.52 in (86.35 x 438.15 x 318.1
mm 34 lb (15.4 kg
SMTL1000RM2UC/SMTL1000RM2UCNC 36 lb (16.3 kg)
SMTL1500RM3UC/SMTL1500RM3UCNC 5.14 x 17.25 x 11.89 in (130.6 x 438.15 x 302
mm) 43 lb (19.5 kg)

Product Overview

SMTL750RM2UC/SMTL750RM2UCNC and
SMTL1000RM2UC/SMTL1000RM2UCNC
SMTL1500RM3UC/SMTL1500RM3UCNC

1 Display (refer “Front panel display features” on page 9 for details
2 Bezel
3 Bezel Screws
4 Battery
5 Battery Door
6 Battery Door Screw
7 Battery Connector

Rear panel features
SMTL750RM2UC/SMTL1000RM2UC
Rear panel features
SMTL750RM2UCNC/SMTL1000RM2UCNC
Rear panel features
SMT1500RM3UC
Rear panel features
SMT1500RM3UCNC
Rear panel features

1 Chassis ground connection screw 8 Outlets
2 QR code for online user manual 9 UPS input power cord
3 QR code for SmartConnect setup 10 Input circuit breaker
4 APC SmartConnect port 11 Smart Slot
5 Serial port 12 Network Management Card (NMC). For details of

the features, refer to model AP9641 in the supplied user guide for UPS Network Management Card 3
6| USB port
7| Controlled outlet group

Installation

UPS
For UPS installation information, refer to the Installation Guide supplied with the UPS.

Network Management Card
The NMC is installed in the factory for SMTL750RM2UCNC, SMTL1000RM2UCNC and SMTL1500RM3UCNC models. The user guide for the NMC is available for download at https://[www.apc.com](http://www.apc.com)/us/en/download/document/SPD_CCON- AYCEFJ_EN.

Placement
The UPS is intended for IT environments. Avoid placement where there is excessive dust and humidity. Note that temperature in excess of 25 o C may have an adverse effect on battery and UPS life. All vents on the side or rear of the UPS should be free of obstructions. The UPS is heavy. The UPS should be placed near the bottom of the rack.

Connect to equipment and AC input power
The UPS will charge the battery to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.
CAUTION

RISK OF INJURY OR DAMAGE TO EQUIPMENT

  • Adhere to all local and national electrical codes.
  • Wiring should be performed by a qualified electrician.
  • Always connect the UPS to a grounded outlet.

Failure to follow these instructions can result in injury or equipment damage

  1. Connect the battery (refer “Installation Guide” supplied with the UPS).
  2. Connect equipment to the outlets in the rear of the UPS. Some models are equipped with controlled outlet groups. Refer to the “Configuration” section of this manual for further instructions on the use of controlled outlet groups.
  3. Connect the UPS input to AC power. Once power is connected the display will be active.
  4. Press the POWER ON/OFF button on the UPS display to turn on the UPS output. The On-line LED will illuminate green when the output is on.

Rear panel features
SmartConnect
SmartConnect

Connect the APC™ SmartConnect port to your nearest network switch using the cable provided. APC SmartConnect allows you to monitor the health and status of your UPS from any device connected to the Internet. Visit www.smartconnect.apc.com to learn more.
Log onto www.smartconnect.apc.com or scan the SmartConnect QR code to launch the registration process. The
website includes instructions to setup your online account, activate your warranty and begin monitoring your UPS remotely.
By connecting this product to the Internet using the APC SmartConnect port, you are agreeing to APC SmartConnect Terms of Use, as found at www.smartconnect.apc.com. Schneider Electric Data Privacy Policy can also be found at www.smartconnect.apc.com.

Start up settings
When the UPS is powered on for the first time the LCD screen displays the Setup Wizard and asks a number of basic set-up questions. They can be answered simply by using the UP/DOWN button and ENTER button on the display. Configuration can also be performed using PowerChute™ software.

Note: If the start up settings asked by the Setup Wizard are not selected completely, turning on UPS output is inhibited. The Setup Wizard will disappear from the display if the start up settings remain idle for 2 minutes. Pressing the POWER ON/OFF button on the front panel will relaunch the Setup Wizard and allow completion of the start up settings.

Function Factory Default Options Description
Language English English French German Spanish Italian
PortugueseJapanese The language for the display interface.

*Language options will vary by model.
Local Power Quality| Good| Good Fair Poor| Select the quality of input AC power.• If Good is selected, the unit will go on battery power more often to provide the cleanest power supply to the connected equipment.• If Poor is selected, the UPS will tolerate more fluctuations in power and will go on battery power less often.If unsure of the local power quality, select Good.
Menu Type| Standard| Standard Advanced| The standard menu displays the most commonly required menus for most users. The advanced menus include all parameters.
Today’s Date| Manufacture date| | Use the UP/DOWN buttons to change the date, and the ENTER button to set the date displayed.

Connect and install management software
Smart-UPS is provided with PowerChute management software for unattended operating system shutdown, UPS  monitoring, UPS control and energy reporting. The following diagram is a representation of a typical server
installation.

  1. Connect the USB cable from the USB port on the rear of the UPS to the protected device such as a server.
  2. For a server or other device with an operating system, load the PowerChute CD and follow the on-screen set-up instructions. PowerChute provides for graceful shutdown in the event of an extended power outage and is a powerful management interface on the local network.
  3. A built-in serial port is also available for additional communication options with an optional serial cable. For more detailed information on supported protocols and options refer to application note #181 at www.apc.com.
  4. Even more management options are available via the built-in Smartslot (applicable only for SMTL750RM2UC, SMTL1000RM2UC and SMTL1500RM3UC models). Refer to www.apc.com for more information.

Operation

Using the display
These Smart-UPS models are equipped with an intuitive and configurable LCD display. This display complements the software interface as they convey similar information and either may be used to configure the UPS settings.

**Front panel display features

**

1| POWER ON/OFF Button| Press this button for turning on/off the UPS output power.
---|---|---
2| On-line LED| Illuminates Green when the UPS output is turned on and the UPS is operating on AC power.
3| On Battery LED| Illuminates orange when the unit is operating on battery. The UPS emits a series of short audible alarm indicating that the UPS is operating on battery power.
4| Error Detected LED| Illuminates red when the UPS detects an internal error. The display screen may also indicate the detected error message or code.
5| Replace Battery LED| Illuminates red when the battery does not pass the self test and requires replacement.
6| Display Screen| Displays the UPS parameters and is also used for configuring the UPS settings.
7| UP/DOWN Buttons| These buttons are used for navigating through the menu.
8| ENTER Button| Used for confirming a selection and/or to enter menu mode.
9| ESCAPE Button| Used for returning to the previous display screen. This button is also used for exiting various display menus.

The display has two status screen/menu options – standard and advanced.
Standard Menu Display
Default setting with fixed status screen and fewer menus

Advanced Menu Display
Optional setting withautomatically scrolling status screen and additional menus.

Note: The standard menu is the default setting and does not contain all of the menus and attributes of the advanced menu. The advanced menu automatically scrolls through multiple screens.

Standard menus
The Standard menus are the most commonly used menus. The following is a list of some items displayed in this
menu mode.

Menu| General Functions|
---|---|---
Status|

  • View UPS information:
  • Operating Mode
  • Efficiency
  • Load Power
  • Load VA
  • Battery Charge state
  • Estimated Runtime

|

  • Battery Temp
  • Input
  •  Output
  •  SmartConnect
  • Probe 1, Probe 2, when NMC and sensor probes are installed

Configuration|

  • Configure UPS settings:•
  • Language
  • Green Mode
  • Local Power Quality: Good, Fair, Poor
  • Menu Type: Standard or Advanced
  •  Audible Alarm

|

  • Display (Auto Dim, Auto Off, Always On)
  • Reset to Factory Default
  • SmartConnect Control
  • Install FW?

Test & Diags| Perform UPS tests and diagnostic functions:

  • UPS Self Test
  • UPS Alarms Test

|
About|

  • View UPS information:
  • UPS Model
  • UPS Part No.
  • UPS Serial No.
  • UPS Manufacture Date
  • Battery Part No.
  • Battery Install Date

|

  • Replace Battery by
  • Running UPS FW
  • Available UPS FW
  • UPS MAC
  • UPS IP Address
  • UPS Product Key
  • SmartSlot Card (if installed)

Advanced menus
The Advanced menus provide additional options for the UPS and are available only if the display interface is
configured to use the Advanced menus.

Menu| General Functions|
---|---|---
Status| View detailed UPS information:•  Operating Mode

  • Efficiency
  • Load Power
  • Load VA
  • Load Amps
  • Load Energy
  • Battery Charge State
  • Estimated Runtime

|

  • Battery Voltage
  • Battery Temp
  • Input
  • Output
  • Outlet Groups
  •  SmartConnect
  • Probe 1, Probe 2, when NMC and sensor probes are installed

Control| Control the Main and Controlled Outlet Group to turn on, turn off, shutdown, or reboot:•  UPS Control•  Outlet Group Control
Configuration| Configure advanced UPS settings

  •  Language

|

  • Enter Setup Wizard
  • Reset to Factory Defaults
  • Site Wiring Fault
  • Modbus
  • Modbus Address
  • Config Main Group Outlets
  • Config Group Outlets
  • ModBus Settings
  • SmartConnect Control
  • Install FW? (only available if a firmware update is available)
  • NMC IP Address Settings (if NMC is available)

|

  • Green Mode

|

  • Local Power Quality

|

  • Menu Type

|

  • Audible Alarm

|

  • Display

|

  • Sensitivity

|

  • Low Transfer

|

  • High Transfer

|

  • Auto Self Test

|

  • Reset Energy Meter

Menu| General Functions|
---|---|---
Test & Diag| Perform UPS tests and diagnostics functions:•  UPS Self Test•  UPS Alarms Test|
Logs| View the error log for information about UPS errors that have occurred.
About| View UPS information:•  UPS Model•  UPS Part No.•  UPS Serial No.•  UPS Manufacture Date•  Battery Part No.•  Battery Install Date•  Replace Battery by| •  Running UPS FW•  Available UPS FW•  UPS MAC•  UPS IP Address• UPS Product Key•  NMC information•  SmartSlot Card (if installed)

Configuration

General configuration settings
Configuration settings may be changed at any time using the LCD interface or PowerChute software. This tableprovides a brief description of the general settings.

Function Factory Default Options Description
High Transfer 127 Vac 127 Vac – 136 Vac To avoid unnecessary battery

usage, set the transfer point higher if the AC voltage is chronically high and the connected equipment is known to work under this condition. The Power Quality setting will automatically change this setting. Note: Use the Advanced Menus to configure this setting.
Low Transfer| 106 Vac| 97 Vac – 106 Vac| Set the transfer point lower if the AC voltage is chronically low and the connected equipment can tolerate this condition. This setting may also be adjusted using the power quality setting
. Note: Use the Advanced Menus to configure this setting.
Sensitivity| Normal|

  • Normal
  • Reduced
  •  Low

| Select the level of sensitivity to power events that the UPS will tolerate.

  • Normal: The UPS will go on battery power more often to provide the cleanest power supply to the connected equipment.
  • Low: The UPS will tolerate more fluctuations in power and will go on battery power less often.If the connected load is sensitive to power disturbances, set the sensitivity to Normal.

Date of Last Battery Replacement| Date set at factory. User will be prompted to update this when the battery module is replaced.
Display| Auto Off|

  • Auto Off
  • Auto Dim
  •  Always On

|

  • The UPS can be configured to change the LCD brightness when the interface has not been used for 4 minutes.
  • Auto Off: The LCD turns off. This is used as the default to extend LCD lifetime
  • Auto Dim: The LCD switches to a lower brightness
  • Always On: The LCD is always at the lower brightness and does not change due to inactivity.

Audible Alarm| On|

  • On
  • Off

| The UPS will mute all audible alarms if this is set to Off or when the display buttons are pressed while there is an audible alarm.
Function| Factory Default| Options| Description
---|---|---|---
Auto Self Test| On start-up and every 14 days since the last test|

  • Never
  • Start-up only
  • Frequency of test (every 7 to 14 days)

| The interval at which the UPS will execute a self-test.
Reset to Factory Default| No| Yes/No| Restore the UPS factory default settings.
Site Wiring Fault| Enable| Enable/Disable/ Can Ack| Set the Site Wiring Fault detection to Enable, Disable or User Can Acknowledge
Green Mode| Enable|

  • Enable
  • Disable

| This will enable or disable Green Mode function. Green Mode conserves energy while the UPS is operating on line.
SmartConnect Control| Disable|

  • Enable
  • Disable

| This will permit remote configuration changes.
Install FW?| Don’t Install|

  • Next off (Updates the UPS Firmware next time that the UPS is turned off)•
  • Now (Updates the UPS firmware immediately without interrupting operations)•
  • Don’t Install

| Firmware update: this only appears when new firmware is available in the flash memory of the UPS and is ready to be installed

Outlet group configuration settings
The Main Outlet Group and the Controlled Outlet Group can be configured to independently turn off, turn on, shut down, or reboot connected equipment.

  • Turn off: Disconnect from power immediately and connect only with a manual command.
  • Turn on: Connect to power immediately.
  • Shutdown: Disconnect from power and automatically connect when AC power becomes available.
  • Reboot: Disconnect from power, wait for a specified amount of time, then connect to power. In addition, the Main Outlet Group and the Controlled Outlet Group can be configured to do the following:
  • Turn on or off in a specified sequence.
  • Automatically turn off or shut down when various conditions occur.
    Note: If the Main and Controlled Outlet Groups are not configured, all of the outlets on the unit will still provide
    battery back-up power.
    Note: The Main Outlet Group must be turned on for the Controlled Outlet Group to turn on.
Function Factory Default Options Description
Name String Outlet Group Outlet Group 1 Edit these names using an

external interface, such as the Network Management Card Web interface.
UPS Name String| UPS Outlets
Turn On Delay| 0 sec| Set the value in seconds| The amount of time the UPS or the Outlet Group will wait between receiving the command to turn on and the actual startup.
Turn Off Delay| •  0 sec (Main Outlet Group)•  90 sec (ControlledOutlet Groups)| Set the value in seconds| The amount of time the Outlet Group will wait between receiving the command to turn off and the actual shut down.
Reboot Duration| 8 sec| Set the value in seconds| The amount of time that the Outlet Group must remain off before it will restart.
Minimum Return Time| 0 sec| Set the value in seconds| The amount of battery runtime that must be available before the Outlet Group will turn on.
Function| Factory Default| Options| Description
---|---|---|---
Load Shed On Battery| Disabled| •  Shutdown with Delay•  Shutdown immediately•  Turn off immediately•  Turn off with delay•  Disabled| When the unit switches to battery power, the UPS can disconnect power to the Controlled Outlet Group to save runtime.To configure this delay time, use the LOAD SHED TIME WHEN ON BATTERY setting.
Load Shed Time when On Battery| Disabled| Set the value in seconds| The amount of time the UPS will keep the Outlet Group on when operating on battery.When the battery runtime falls below the specified value, the Outlet Group will turn off.Configure this time using the LOAD SHED RUNTIME REMAINING setting.
Load Shed On Runtime| Disabled| •  Shutdown with delay•  Shutdown immediately•  Turn off immediately•  Turn off with delay•  Disabled
Load Shed On Runtime Remaining| Disabled| Set the value in seconds| When the remaining runtime reaches this level, the Outlet Group will turn off.
Load Shed on Overload| Disabled| •  Disabled•  Enabled| In the event of an overload (greater than 100% output power), the Outlet Group will immediately turn off to conserve power for essential loads. The Outlet Group will only turn on again with a manual command.

Modbus settings

Setting Factory Default Options Description
Slave ID 1 1- 223 Sets the Modbus slave address of UPS
Ser + USB Disable •  Enable•  Disable Enables or disables UPS Modbus

protocol over serial and USB ports
TCP Settings •  TCP Protocols| Disable| •  Disable•  Read-Only• Read-Write| Enables or disables UPS Modbus TCP/IP protocol provided by the embedded SmartConnect port.•  Disable: Disables UPS Modbus TCP/IP protocol•  Read-Only: Modbus master over TCP/IP protocol is only allowed to get UPS status.•  Read-Write: Modbus master over TCP/IP protocol is allowed to get UPS status and control the UPS.The port number of UPS Modbus TCP/IP protocol is fixed at 502.
TCP Settings •  Master IP Addr| 000.000.000.000| A valid IPv4 address| Specifies the IPv4 address of the Modbus master.The Master IP Addr when set as 000.000.000.000 will allow connection of external Modbus master with any IP address. When not set as 000.000.000.000, only the Modbus master with the specified IP address is allowed to connect to the UPS.Example: Master IP Address is set to 192.168.0.10, only Modbus master with IP address 192.168.0.10 could connect to the UPS.

UPS IP Address settings

Setting Factory Default Options Description
UPS IP Address Mode DHCP •  DHCP•  Manual Selects the IP address

configuration mode of UPS embedded SmartConnect port:•  DHCP: UPS will automatically configure its IPv4 address via DHCP protocol.•  Manual: Manually assigns a static IPv4 address to UPS
IP Address| 000.000.000.000| A valid IPv4 address| This is the IPv4 address assigned to the embedded SmartConnect port.When DHCP IP address mode is selected, it will display the UPS IPv4 address assigned by DHCP server.When Manual IP address mode is selected, you need to manually specify a static IPv4 address.
Subnet Mask| 000.000.000.000| A valid IPv4 subnet mask| Assigns the subnet mask of the network where UPS IPv4 address belongs.When DHCP IP address mode is selected, it will display the subnet mask assigned by DHCP server.When Manual IP address mode is selected, you need to manually specify the subnet mask of the network where the specified static IPv4 address belongs.
Default Gateway| 000.000.000.000| A valid IPv4 address| This is the IPv4 address of the host from where the UPS sends data to another network or Internet.When DHCP IP address mode is selected, it will display the default gateway assigned by DHCP server.When Manual IP address mode is selected, you need to manually specify the IPv4 address of default gateway.
DNS Server 1| 000.000.000.000| A valid IPv4 address| The IPv4 address of first domain name server (DNS) the UPS uses to resolve host names to IPv4 addresses.When DHCP IP address mode is selected, it will display the IPv4 address of the first DNS server assigned by DHCP server.When Manual IP address mode is selected, you need to manually specify the IPv4 address of the first DNS server.
DNS Server 2| 000.000.000.000| A valid IPv4 address| The IPv4 address of second domain name server (DNS) the UPS uses to resolve host names to IPv4 addresses (only when UPS is unable to resolve IP address through first domain name server). This setting is optional.When DHCP IP address mode is selected, it will display the IPv4 address of the second DNS server assigned by DHCP server.When Manual IP address mode is selected, you can manually specify the IPv4 address of the second DNS server or leave it as 000.000.000.000.

Network Management Card Settings
Note: This is applicable only for SMTL750RM2UCNC, SMTL1000RM2UCNC and SMTL1500RM3UCNC.
These settings can only be modified using an external interface, like the NMC web interface.

  • NMC IP Address Mode
  • NMC IP Address
  • NMC Subnet Mask
  • NMC Default Gatew ay

Troubleshooting

Problem and Possible Cause Solution

The UPS will not turn on or there is no output.
The unit has not been turned on.| Press the POWER ON/OFF button once to turn on the UPS.
The UPS is not connected to AC power.| Be sure the power cable is securely connected to the unit and to the ACpower supply.
The input circuit breaker has tripped.| Reduce the load on the UPS. Disconnect nonessential equipment and resetthe circuit breaker.
The unit shows very low or no input AC voltage.| Contact a qualified electrician to correct wiring issue.
The battery connector plug is not securelyconnected.| Be sure that all battery connections are secure.
There is an internal UPS error detected.| Do not attempt to use the UPS. Turn off the UPS and unplug it from AC.Contact APC by Schneider Electric Customer Support for assistance.
If the UPS is not connected to AC Power, then there will be up to a 1-minute delay between the initial connection of the battery and the UPS being ready to start| Wait 1 minute before pressing the POWER ON/OFF button, or connect the UPS to AC power to eliminate the delay.
The UPS is operating on battery, while connected to input AC power.
The input circuit breaker has tripped.| Reduce the load on the UPS. Disconnect nonessential equipment and resetthe circuit breaker.
There is very high, very low, or distorted input line voltage.| Move the UPS to a different outlet on a different circuit. Test the input voltage with the AC voltage display. If acceptable to the connectedequipment, reduce the UPS sensitivity.
UPS is emitting intermittent beeps.
The UPS is operating normally.| None. The UPS is protecting the connected equipment.
UPS does not provide expected backup time.
The UPS battery is weak due to a recent power outage or is near the end of its service life.| Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator has notilluminated.
The UPS is experiencing an overload condition.| Check the UPS load display. Unplug unnecessary equipment, such asprinters.
Display interface LEDs flash sequentially.
The UPS has been shut down remotely throughsoftware or an optional accessory card.| None. The UPS will restart automatically when AC power is restored.
The Error LED is illuminated. The UPS displays an error message and emits a constant beeping sound.
Internal UPS error detected.| Do not attempt to use the UPS. Turn the UPS off and contact APC bySchneider Electric Customer Support immediately.
The Replace Battery icon is illuminated and the UPS beeps for one minute every five hours.
The battery has a weak charge.| Allow the battery to recharge for at least four hours. Then, perform aself-test. If the problem persists after recharging, replace the battery.
The Replace Battery icon is flashing and the UPS beeps once every 2 seconds.
The battery is not properly connected.| Be sure that the battery connector is securely connected.
The UPS displays a site wiring error message.
Wiring errors detected include missing ground, hot- neutral polarity reversal, and overloaded neutralcircuit.| If the UPS indicates a site wiring error, have a qualified electrician inspect the building wiring. (Applicable to 120 V units only.)

Limited Factory Warranty

Schneider Electric IT Corporation (SEIT), warrants this product to be free from defects in materials and workmanship for a period of five(5) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com. SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installation, testing, operation or use of the product contrary to SEIT’s recommendations or specifications. Further, SEIT shall not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.

THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT’S LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.

To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from
customer support. Customers with warranty claims issues may access the SEIT worldwide customer support
network through the SEIT Web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.

Transport the Unit

  1. Shut down and disconnect all equipment.

  2. Disconnect the unit from utility power.

  3. Disconnect batteries.

  4. Follow the shipping instructions outlined in the Service section of this manual.

  5. Service
    If the unit requires service, do not return it to the dealer. Follow these steps:

  6. Review the Troubleshooting section of the manual to eliminate common problems.

If the problem persists, visit www.apc.com for APC by Schneider Electric Customer Support contact information.

  1. * Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD interface on select models.
    • Call APC by Schneider Electric Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
    • If the unit is under warranty, it will be repaired or replaced at no cost.
    • Service procedures and returns may vary internationally. Refer to the APC web site for country specific instructions.
  2. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.
  3. Before shipping, always disconnect all battery modules.
  4. Write the RMA# provided by Customer Support on the outside of the package.
  5. Return the unit by insured, prepaid carrier to the address provided by Customer Support.

APC by Schneider Electric Worldwide Customer Support
Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways:

  • Visit the APC by Schneider Electric web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests.
  • www.apc.com (Corporate Headquarters) Connect to localized APC by Schneider Electric web sites for specific countries, each of which provides customer support information.
  • Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
    • Local, country specific centers: go to www.apc.com/support/contact for contact information.
    • For information on how to obtain local customer support, contact the APC by Schneider Electric representative or other distributor from whom you purchased your APC by Schneider Electric product.

2021 APC by Schneider Electric. APC, the APC logo and APC, the APC logo, Smart-UPS, SmartConnect
and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals