Ideal Evojet Condensing Pressure Jet Boilers 210kW User Guide

June 17, 2024
IDEAL

Ideal Evojet Condensing Pressure Jet Boilers 210kW

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
product

Specifications

  • Model: EVOJET 210kW
  • Type: Pressure jet Floor standing
  • Fuel Type: Dual fuel
  • Part L Compliant

Dimensions and Clearances

Component Dimension (mm)
DIM A (Boiler) 760
DIM B 1455
DIM C 1315

Minimum Clearances

  • Front: Burner Length + 600mm (for access/maintenance), Boiler
    Length (for cleaning)

  • Rear: 1000mm (Min)

  • Top: 1000mm (Min)

  • Sides: 1000mm (Min)

Installation :

  1. Ensure the minimum clearances are maintained for proper operation and servicing.
  2. Follow the assembly instructions provided in the manual for proper boiler setup.

Maintenance :

  1. Regularly inspect and clean the boiler components as per the maintenance schedule.
  2. Refer to the exploded view diagram for identifying different parts for maintenance purposes.
Safety Precautions:
  • Always turn off the boiler and allow it to cool down before performing any maintenance tasks.
  • Do not operate the boiler with blocked flue or air inlet.

EVOJET

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
\(2\) Features and specification
The Evojet condensing range of pressure jet boilers are available in 14 models with outputs from 150-3000kW. Floor standing boilers for applications in either single or multiple configurations.

  • Up to 109.3% part load efficiency
  • Designed to operate up to 40°C ΔT providing minimum flow rates are achieved
  • Dedicated low temp return
  • Stainless steel heat exchanger
  • Triple flue pass for high operating efficiencies
  • Multiple burner options available (see page 3 for details)
  • Modulation via 0-10 volt BMS, or RWF controller

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
\(3\)

DIMENSIONS AND CLEARANCES

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
\(4\)

BOILER ASSEMBLY

EXPLODED VIEW
KEY

  1. Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-product Boiler frame
  2. Side Panel
  3. Side Panel
  4. Rear Panel
  5. Rear Panel
  6. Central side panel
  7. Central side panel
  8. Top cross beams
  9. Top rear panel
  10. Bottom rear bracket
  11. Bottom rear panel
  12. Bottom rear panel
  13. Front top panel
  14. Top panel
  15. Top panel
  16. Top panel
  17. Top panel
  18. Front trim panel
  19. Front trim panel
  20. Control panel

EVOJET 210kW

TECHNICAL SPECIFICATIONS

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
\(6\)

Burner and Gas Train selections for Natural Gas applications are based on standard design requirements (as stated in IGE/UP/2) of 20mbar gas pressure available at the appliance under max flow conditions. If this pressure is not available, or the available gas pressure is higher, or for alternative fuel types – please consult your sales contact for alternative matching.

HYDRAULICS Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
\(7\)

BURNER (Low NOx)

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
11

ELECTRICAL (PRIMETECH CONTROL PANEL)

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
\(9\)

CONTROL/BOILER/BURNER OPERATION Ideal-Evojet-Condensing-0Pressure-Jet-
Boilers-210kW- \(10\)

BURNER MATCHING OPTIONS Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-
210kW- \(11\)

Modulating and Low NOx options available; please contact us for full details. Oil burners would be subject to confirmation that the fuel supply was a suitable type / grade.

  • Burner matching for LPG operation by special request.

SUGGESTED ENGINEERING SPECIFICATION

The Suggested Engineering Specification is wording designed for specifiers to copy and paste into their specifications to ensure inclusion of Ideal Heating commercial boilers.

OVERVIEW

  • The boiler must be a fully automatically controlled, floor standing condensing boiler with a triple flue pass stainless steel heat exchanger. While they are designed primarily for central heating purposes, in conjunction with a suitable storage cylinder they can also be used to produce domestic hot water on an indirect fully pumped sealed water system.

  • All parts that come into contact with the combustion
    gases are made from titanium stabilized stainless steel to ensure maximum resistance to the corrosive action of acid condensation.

  • boiler must incorporate two return water connections to facilitate multiple applications e.g. CH & DHW and enables the optimum operating efficiency to be achieved.

  • The boilers must be designed to operate with Natural Gas, LPG or Oil (delete as required) using pressure-jet or premixed burners. The burner specification will enable the choice of
    2-stage, Modulating, Low NOx and Ultra Low NOx operation.

CONTROLS
The boiler control options must be selected at the time of purchase:

  • Two stage burner
  • Modulating burner
  • BMS 0-10V
  • Oil & dual fuel

The boiler must include control features enabling set point adjustment, heating circuit control of one constant temperature, one variable temperature and one DHW circuit and safety lock out parameters including fault diagnosis for both boiler and external components such as sensors or pumps.
Boiler capabilities must include, with the use of external components, frost protection, weather or room compensation and system pump control.

FLUE
The condensing boilers must be suitable for use with an open flued application in B23 configuration. The B23P configuration can only be used with a premix gas burner.

HYDRAULIC
The condensing boiler must be suitable for connection to
a fully pumped sealed water system. All hydraulic connections including flow return and condensate drain must be located on the bottom or rear of the boiler. The boiler must have a maximum operating pressure of 6 bar and be suitable for heating and indirect hot water systems.

DIMENSIONS
The condensing boiler must fit within maximum permitted floor space of 0.97m² (150 and 210kW models)/1.23m² (270 and 350kW models)/1.47m² (450 and 900kW models)/2.03m² (800 and 1000kW models)/2.40m² (1250kW model)/2.67m² (1450kW model)/6.34m² (1750kW model)/7.04m² (2100kW model)/8.19m² (2700kW) model/9.00m² (3000kW model).

MOUNTING / POSITIONING
The condensing boilers will be floor standing.

EFFICIENCY
The condensing boilers are capable of high seasonal efficiencies with a minimum requirement of 95.8% (Part L Vol.2 2022) and low NOx emissions between 43 – 65mg/kWh (47 – 70mg/Nm³) depending on boiler model, using Low NOx Natural Gas burner.

APPROVALS
The manufacturer must be ISO 9001 accredited

SPECIFICATION

The boiler must be capable of the below flow rates:

Ideal-Evojet-Condensing-0Pressure-Jet-Boilers-210kW-
\(1\)

WARRANTY

The boiler must be available with a 2 year warranty.