DAIKIN EWYT-CZ Air Water Heat Pump Units with Scroll Compressors Instruction Manual
- June 17, 2024
- Daikin
Table of Contents
- EWYT-CZ Air Water Heat Pump Units with Scroll Compressors
- INTRODUCTION
- RECEIPT OF THE UNIT
- STORAGE
- MECHANICAL INSTALLATION
- ELECTRICAL INSTALLATION
- OPERATOR’S REPONSIBILITIES
- MAINTENANCE
- LIST OF THE LABELS APPLIED TO THE UNIT
- COMMISSIONING
- IMPORTANT INFORMATION ON THE REFRIGERANT USED
- PERIODIC CHECKS AND COMMISSIONING OF PRESSURE EQUIPMENT
- DISMISSION AND DISPOSAL
- Documents / Resources
Installation, Maintenance and Operation Manual
D-EIMHP01405-21_04EN
EWYT-CZ Air Water Heat Pump Units with Scroll Compressors
Installation, Operation and Maintenance Manual
Air to water heat pump units with scroll compressors
EWYT~CZ / EWAT~CZ
REV | 04 |
---|---|
Date | 10/2022 |
Supersedes | D-EIMHP01405-21_03EN |
INTRODUCTION
This appliance is intended to be used by expert or trained users in shops, in
light industry and on farms, or for commercial use by lay persons. The
appliance shall not be accessible to the general public: install it in a
secured area, protected from easy access.This manual provides information on
the standard functions and procedures of all units in the series and is an
important supporting document for qualified personnel but can never replace
it.
All units are delivered with wiring diagrams, certified drawings, nameplate,
and CE Declaration of Conformity. These documents show all technical data for
the unit you have bought. In case of any discrepancies between the contents of
the manual and the documentation provided with the unit, always rely on the
unit because it is an integral part of this manual.Read this manual carefully
before installing and starting up the unit.
Improper installation could result in electric shock, shortcircuits, leaks,
fire or other damage to the equipment or injure to people.
The unit must be installed by professional operators / technicians in
compliance with the laws in force in the country of installation.
The startup of the unit must also be performed by authorized and trained
personnel and all activities must be carried out in full compliance with local
laws and regulations.
Installation and start up are absolutely forbidden if all instructions
contained in this manual are not clear.
If you are unsure about assistance and for more information, contact an
authorized representative of the manufacturer.
1.1 Precautions against residual risks
- Install the unit according to the instructions set out in this manual.
- Regularly carry out all the maintenance operations foreseen in this manual.
- Wear protective equipment (gloves, goggles, helmet, etc.) suited to the work in hand; do not wear clothes or accessories that can get caught or sucked in by flows of air; tie back long hair before entering the unit.
- Before opening the machine panel, make sure that it is firmly hinged to the machine.
- The fins on heat exchangers and the edges of metal components and panels can cause cuts.
- Do not remove the guards from mobile components while the unit is operating.
- Make sure that mobile component guards are fitted correctly before restarting the unit.
- Fans, motors and belts drives might be running: before entering, always wait for these to stop and take appropriate measures to prevent them from starting up.
- The surfaces of the machine and pipes can get very hot or cold and cause the risk of scalding
- Exceed the maximum pressure limit (PS) of the water circuit of the unit.
- Before removing parts on the pressurized water circuits, close the section of the piping concerned and drain the fluid gradually to stabilize the pressure at the atmospheric level.
- Do not use your hands to check possible refrigerant leaks
- Disable the unit from the mains using the main switch before opening the control panel.
- Check that the unit has been grounded correctly before starting it.
- Install the machine in a suitable area; do not install it outdoors if it is intended for use indoors
- Do not use cables with inadequate sections nor extension cord connections, even for very short periods or emergencies.
- For units with VFD, wait 10 minutes after removing the electric power supply before accessing the inside of t he switch board.
- The unit contains pressurized refrigerant gas: the pressurized equipment must not be touched except during maintenance, which must be entrusted to qualified and authorized personnel.
- Connect the utilities to the unit following the indications set out in this manual and on the panels of the unit itself.
- To avoid an environmental risk, make sure that any leaking fluid is collected in suitable devices in accordance with local regulations.
- If a part needs to be dismantled, make sure it is correctly reassembled before starting the unit.
- When the rules in force require the installation of firefighting systems near the machine, check that these are suitable for extinguishing fires on electrical equipment and on the lubricating oil of the compressor and the refrigerant, as specified on the safety data sheets of these fluids.
- Keep all the safety devices in good working order and check them periodically according to the regulations in force.
- Keep all lubricants in suitably marked containers.
- Do not store inflammable liquids near the unit.
- Solder or braze only empty pipes after removing all traces of lubricant oil; do not use flames or other heat sources close to pipes containing refrigerant fluid.
- Do not use naked flames near the unit.
- The machinery must be installed in structures protected against atmospheric discharge according to the applicable laws and technical standards.
- Do not bend or hit pipes containing pressurized fluids.
- It is not permitted to walk or rest other objects on the machines
- The user is responsible for overall evaluation of the risk of fire in the place of installation (for example, calculation of the fire load).
- During transport, always secure the unit to the bed of the vehicle to prevent it from moving about and ove rturning.
- The machine must be transported according to the regulations in force considering the characteristics of the fluids in the machine and the description of these on the safety data sheet.
- Inappropriate transport can cause damage to the machine and even leaking of the refrigerant fluid. Before starting up, the machine must be checked for leaks and repaired accordingly.
- The accidental discharge of refrigerant in a closed area can cause a lack of oxygen and, therefore, the risk of asphyxiation: install the machinery in a well-ventilated environment according to EN 378-3 / ISO 5149-3 and the local regulations in force.
- The installation must comply with the requirements of EN 378-3 / ISO 5149-3 and the local regulations in force.
1.2 General description
All EWYT~CZ / EWAT~CZ machines are built in accordance with the main European
Directives (Machinery Directive, Low Voltage Directive, Electromagnetic
Compatibility Directive, Pressure Equipment Directive.
The unit purchased is a Heat Pump, that is a machine designed to cool/heat the
water (or a water -glycol mixture) within certain limits which will be listed
below. The unit operates based on the compression, condensation and
evaporation of the coolant gas as per the Carnot cycle and is composed mainly
of the following parts depending on the Mode of Operation.
Cooling or Conditioning Mode :
- One or more scroll compressors which increase the pressure of the refrigerant gas from evaporation pressure to condensation pressure.
- A condenser where the refrigerant gas condenses under high pressure and transfers heat to the air.
- An expansion valve which allows the pressure of condensed liquid refrigerant to be reduced from condensation pressure to evaporation pressure.
- An evaporator, where the low-pressure liquid refrigerant evaporates and chills the water.
Heating Mode or Heat Pump:
- One or more scroll compressors which increase the pressure of the refrigerant gas from evaporation pressure to condensation pressure.
- A condenser where the refrigerant gas condenses under high pressure and transfers heat to the water.
- An expansion valve which allows the pressure of condensed liquid refrigerant to be reduced from condensation pressure to evaporation pressure
- An evaporator, where the low-pressure liquid refrigerant evaporates.
- The operation of the heat exchangers can be inverted using the 4way valve, with which the use of the heating/cooling unit can be seasonally inverted.
All units are fully assembled in the factory and tested before shipping. The
EWYT~CZ / EWAT~CZ range consists of models with a single cooling circuit and
models with two cooling circuits.
The machine uses R32 refrigerant fluid suitable for the entire field of
application of the machine.
The controller is prewired, set up and tested at the factory. Only normal
field connections such as piping, electrical connections and pump interlocks
are required, simplifying installation and increasing reliability. All safety
and operation control systems are installed at the factory in the control
panel.
The instructions in this manual are applicable to all models in this series
unl ess otherwise specified.
1.3 Information about the refrigerant
This product contains R32 refrigerant that has a minimal environmental impact,
thanks to its low value of Global Warming Potential (GWP). According to ISO
817, R32 refrigerant is classified as A2L, which is slightly flammable, since
the flame propagation rate is low, and nontoxic.
R32 refrigerant can burn slowly when all the following conditions are present:
- The concentration is between the lower and upper flammability limit (LFL & UFL).
- Wind velocity<propagation of flame velocity
- Energy of the ignition source>Minimum ignition energy
But pose no risk under the normal usage conditions for air conditioning equipment and work environment.
Safety class (ISO 817) | A2L |
---|---|
PED Group | 1 |
Practical limit (kg/m3) | 0,061 |
ATEL/ ODL (kg/m3) | 0,30 |
LFL (kg/m3) @ 60°C | 0,307 |
Vapor density @25°C, 101.3 kPa (kg/m3) | 2,13 |
Molecular mass | 52,0 |
Boiling point (°C) | -52 |
GWP (100 yr ITH) | 675 |
GWP (ARS 100 yr ITH) | 677 |
Autoignition temperature (°C) | 648 |
Table 1- Physical properties of R32 refrigerant
1.4 Installation information
The heat pump must be installed in open air or machinery room (location
classification III).
To ensure location classification III a mechanical vent on the secondary
circuit(s) must be installed.
Local building codes and safety standards shall be followed; in absence of
local codes and standards refer to EN 378 3 / ISO 5149-3 as a guide.
In paragraph “Additional guidelines for safe use of R32” there are provided
additional information that should be added to the requirements of safety
standards and building codes.
Additional guidelines for safe use of R32 for equipment located in the open
air
Units sited in the open air shall be positioned to avoid leaked refrigerant
flowing into a building or otherwise endangering people and property.
The refrigerant shall not be able to flow into any ventilation fresh air
opening, doorway, trap door or similar opening in the event of a leak. Where a
shelter is provided for refrigerating equipment sited in the open air it shall
have natural or forced ventilation.
For units installed outside in a location where a release of refrigerant can
stagnate e.g. below ground, then the installation shall comply with the
requirements for gas detection and ventilation of machinery rooms.
Additional guidelines for safe use of R32 for equipment located in a machinery
room
When a machinery room is chosen for the location of the unit it shall be in
accordance with local and national regulat ions.
The following requirements (according to EN 378-3:2016) can be used for the
assessment.
- A risk analysis based on the safety principle for a refrigeration system (as determined by the manufacturer and including the charge and safety classification of the used refrigerant) should be conducted to determine if it is necessary to install the heat pump in a separate refrigeration machinery room.
- Machinery rooms should not be used as occupied spaces. The building owner or user shall ensure that access is permitted only by qualified and trained personnel doing the necessary maintenance to the machinery room or general plant.
- Machinery rooms shall not be used for storage except for tools, spare parts and compressor oil for the installed equipment. Any refrigerants, or flammable or toxic materials shall be stored as required by national regulations.
- Open (naked) flames shall not be permitted in machinery rooms, except for welding, brazing or similar activity and then only provided the refrigerant concentration is monitored and adequate ventilation is ensured. Such open flames shall not be left unattended.
- A remote switching (emergency type) for stopping the refrigerating system shall be provided outside the room (near the door). A similar acting switch shall be located at a suitable location inside the room.
- All piping and ducting passing through floors, ceiling and walls of machinery room shall be sealed.
- Hot surfaces shall not exceed a temperature of 80 % of the autoignition temperature (in °C) or 100 K less than the autoignition temperature of the refrigerant, whichever is lower.
Refrigerant| Self ignition temperature| Maximum surface
temperature
---|---|---
R32| 648 °C| 548
-
Machinery rooms shall have doors opening outward and sufficient in number to ensure freedom for persons to escape in an emergency; the doors shall be tight fitting, selfclosing and so designed that they can be opened from inside (antipanic system).
-
Special machinery rooms where the refrigerant charge is above the practical limit for the volume of the room shall have a door that either opens directly to the outside air or through a dedicated vestibule equipped with selfclosing, tightfitting doors.
-
The ventilation of machinery rooms shall be enough both for normal operating conditions and emergencies.
-
Ventilation for normal operating conditions shall be in accordance with national regulations.
-
The emergency mechanical ventilation system shall be activated by a detector(s), located in the machinery room.
-
This ventilation system must be:
– independent of any other ventilation system on the site.
– provided with two independent emergency controls one located outside the machinery room, and the other inside. -
The emergency exhaust ventilation fan shall:
– Be either in the air flow with the motor outside the airflow or rated for hazardous areas (according to the assessment).
– Be located to avoid pressurization of the exhaust ductwork in the machinery room.
– Not cause sparks to occur if it contacts the duct material. -
Airflow of the emergency mechanical ventilation shall be at least: V = 0,014 × m2/3
Where
V is air flow in m3/s;
m Is the amount of refrigerant present in the machine room, in kg;
0,014 Is a conversion factor.
- Mechanical ventilation shall be operated continuously or shall be switched on by the detector.
- Detector shall automatically activate an alarm, start mechanical ventilation and stop the system when it triggers
- The location of detectors shall be chosen in relation to the refrigerant and they shall be located where the refrigerant from the leak will concentrate
- The positioning of the detector shall be done with due consideration of local airflow patterns, accounting for location sources of ventilation and louvers. Consideration shall also be given to the possibility of mechanical damage or contamination.
- At least one detector shall be installed in each machinery room or the occupied space being considered and/or at the lowest underground room for refrigerants heavier than air and at the highest point for refrigerants lighter than air.
- Detectors shall be continuously monitored for functioning. In the case of a detector failure, the emergency sequence should be activated as if refrigerant had been detected.
- The preset value for the refrigerant detector at 30 °C or 0 °C, whichever is more critical, shall be set to 25 % of the LFL. The detector shall continue to activate at higher concentrations.
Refrigerant| LFL| Threshold level
---|---|---
R320| 0,307 kg/m³| kg/m³0,07675| kg/m³36000 ppm - All electrical equipment (not only the refrigerating system) shall be selected to be suitable for use in the zones identified in the risk assessment. Electrical equipment shall be deemed to comply with the requirements if the electrical supply is isolated when the refrigerant concentration reaches 25% of the lower flammable limit or less.
- Machinery rooms or special machinery rooms shall be clearly marked as such on the entrances to the room, together with warning notices indicating that unauthorized persons shall not enter and that smoking, naked light or flames are prohibited. The notices shall also state that, in the event of an emergency, only authorized persons conversant with emergency procedures shall decide whether to enter the machinery room. Additionally, warning notices shall be displayed prohibiting unauthorized peration of the system
- The owner / operator shall keep an updated logbook of the refrigerating system.
RECEIPT OF THE UNIT
Inspect the unit immediately after delivery. Make sure that the machine is
intact in all its parts and that there are no deformations due to impacts. All
components described in the delivery note must be inspected and checked.
Should any damage occur upon receipt of the machine, do not remove the damaged
material and immediately make a written complaint to the transport company,
requesting the inspection of the unit; do not repair until inspection by the
transport company representative is carried out.
Immediately report the damage to the manufacturer representative, a set of
photographs is helpful in recognizing responsibility. The restitution of the
machinery is intended as ex-factory Daikin Applied Europe S.p.A..
Daikin Applied Europe S.p.A. declines all responsibility for any damage that
the machinery may suffer during transport to the destination.
Use extreme caution when handling the unit to prevent damage to components.
Before installing the unit, check that the model and power supply voltage
shown on the nameplate are correct. Responsibility for any damage after
acceptance of the unit cannot be attributed to the manufacturer.
STORAGE
**** If it is necessary to store the unit before installation, it is necessary to observe some precautions:
- do not remove the protective plastic;
- protect the unit from dust, bad weather and any rodents;
- do not expose the unit to direct sunlight;
- . do not use heat sources and / or open flames near the machine.
Although the unit is covered with a heatshrink plastic sheet, it is not
intended for longterm storage and must be removed and replaced by tarpaulins
or the like, more suitable for a longer period.
Environmental conditions must be within the following limits:
- Minimum ambient temperature: -20 °C
- Maximum ambient temperature +48 °C
- Maximum H.: 95% not condensing
Storage at a temperature below the minimum or over the maximum values can cause damage to the components. Storage in a humid atmosphere may damage electrical components.
MECHANICAL INSTALLATION
4.1 Safety
Before installation and commissioning of the machinery, the people involved in
this activity must have acquired the information necessary to perform these
tasks, applying all the information gathered in this manual. In particular:
- the unit must be firmly anchored to the ground when it must not be moved
- the unit can only be lifted using the lifting points indicated by labels fixed to its base;
- always protect operating personnel with personal protective equipment appropriate to the activities to be performed. The individual devices commonly used are: helmet, glasses, gloves, headphones, safety shoes.
Further personal and collective protection devices must be adopted after
having carried out an adequate analysis of the specific risks in the relevant
area, according to the activities to be carried out.
4.2 Handling and lifting
Avoid bumping and/or jolting during loading/unloading unit from the truck and
moving it. Do not push or pull the unit from any part other than the base
frame. Secure the unit inside the truck to prevent it from moving and causing
damages. Do not allow any part of the unit to fall during transportation or
loading/unloading.
Lifting instructions:
Equipment, ropes, lifting accessories and handling procedures must comply with
local regulations and current legislation.
When lifting the machine, use only the holes in the frame identified in the
figure. Use lifting hooks with closing device exclusively. The hooks must be
safely fastened before performing the handling.
The ropes and hooks used must have an appropriate capacity for the load. Refer
to the plate on the unit for the weight of the specific machine.
Lifting ropes must have the minimum length shown in the diagram. All units of
the series are supplied with lifting points indicated by labels. Only these
points may be used for lifting the unit, as shown in the following figures.
The installer has the responsibility to ensure the selection and correct use
of the lifting equipment.
Alternatively, the machine may be moved with a forklift, as shown. When
lifting the machine, make sure it is levelled properly so it will not
overturn.
4.2.1 Lifting the MONO unit
The machine must be lifted slowly and well levelled. Always use protective
devices to prevent damage to the belt and note the position of the unit’s
centre of gravity. Adjust the lifting equipment if necessary to ensure that
the unit is levelled.
The unit(s)- both Mono and Dual- can be lifted, using the buttonholes in the
base, by:
- lifting straps
- forklift, where the dimensions of the forks permit.
N.B.: Follow the lifting instructions provided in the ID plate fastened
to the electrical panel. 4.2.2 Lifting the DUAL unit 4.3 Positioning and assembly
All units are designed for installation outdoors, either on balconies or on
the ground, provided that the installation area is free of obstacles that
could reduce air flow to the condensers coil.
The unit must be installed on a robust and perfectly level foundation; should
the unit be installed on balconies or roofs, it might be necessary to use
weight distribution beams.
For installation on the ground, a strong concrete base, at least 150 mm
thickness and wider than the unit must be provided.
This base must be able to support the weight of the unit. In heavy snowfall
areas, this thickness should be increased, The frame of the unit must be
levelled using metal plate spaces. The base can be installed both longitudinally or
transversely. In the following figures are illustrated the mounting holes
location: Before unit
commissioning, the flatness must be verified by using a laser levelling device
or other similar devices. The flatness shall not be over 5 mm for units within
7 m length.
To ensure best performance on the installation site, the fol lowing
precautions and instructions must be followed
- Avoid air flow recirculation;
- Make sure that there are no obstacles to hamper air flow;
- Make sure to provide a strong and solid foundation to reduce noise and vibrations;
- Avoid installation in particularly dusty environments, in order to reduce soiling of condensers coils.
4.3.1 Mounting the main switch handle
- Unpair the locknut from the handle of the main switch
- Place the handle in the hole dedicated
- Fix the main switch handle by tightening the locknut from the back of the panel
- Insert the rod of the main switch
- Fasten the rod of the main switch
- Mount the panel
With ?1 and ?1 the new
minimum distances.
NOTE: in case the calculated value of ?1 and/or ?1 is higher than 2000mm,
consider 2000mm as minimum distance
4.4 Minimum space requirements
It is fundamental to respect minimum distances on all units to ensure optimum
ventilation to the condenser coils.
When deciding where to position the unit and to ensure a proper air flow, the
following factors must be taken into consideration:
- avoid any warm air recirculation;
- avoid insufficient air supply to the aircooled condenser.
Both these conditions can cause an increase of condensing pressure, which
leads to a reduction in energy efficiency and refrigerating capacity.
Any side of the unit must be accessible for postinstallation maintenance
operations and vertical air discharge must not be obstructed. Figure below
shows the minimum space required. Where:
A : Electrical panel side
B/D : Side view of battery
C : Front view of battery
:Intake
If the unit is installed in a free field, the distances indicated are: A/B/C/D
≥ 500 mm
In the presence of obstacles or walls, the following minimum distances are
recommended: With A1 and C1 the new minimum distances,
NOTE: In case the calculated value of A1 and/or C1 is higher than 2000mm,
consider 2000mm as minimum distance.
If two units are installed in a free field side by side along their longer
sides, A and C, the minimum recommended distance between them is 1000 mm; if
two units are installed side by side along their shorter sides, sides B and D,
the minimum distance between them should be 500 mm. Should the unit be
installed without observing the recommended minimum distances from walls
and/or vertical obstacles, there could be a combination of warm air
recirculation and/or insufficient supply to the aircooled condenser which
could cause a reduction of capacity and efficiency.
In any case, the microprocessor will allow the unit to adapt itself to new
operating conditions and delive r the maximum available capacity under any
given circumstances, even if the lateral distance is lower than recommended,
unless the operating conditions should affect personnel safety or unit
reliability. The minimum distances, reported above, ensure functionality of
the unit in most applications
4.5 Additional installation site requirements
- When installing, take strong winds, typhoons or earthquakes into account, improper installation may result in the unit turning over.
- Take care that in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
- Be sure that the air inlet of the unit is not positioned towards the main wind direction. Frontal wind will disturb the operation of the unit. If necessary, use a screen to block the wind.
- Ensure that water cannot cause any damage to the location by adding water drains to the foundation and prevent water traps in the construction.
Seaside installation Make sure the outdoor unit is NOT directly exposed to sea
winds. This is to prevent corrosion caused by high levels of salt in the air,
which might shorten the life of the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building (case I).
If the outdoor unit is exposed to direct sea winds, install a Windbreaker
(case II).
- Height of windbreaker ≥1.5×height of outdoor unit
- Mind the service space requirements when installing the windbreaker
Legend:
a. Sea wind
b. Building
c. Outdoor unit
d. Windbreaker
When operating the unit in a low outdoor ambient temperature, be sure to
follow the instructions described below.
To prevent exposure to wind and snow, install a baffle plate on the air side
of the outdoor unit: In heavy snowfall areas it is very important to select an
installation site where the snow will NOT affect the unit. If lateral snowfall
is possible, make sure that the heat exchanger coil is NOT affected by the
snow. If necessary, install a snow cover or shed and a pedestal.
For instructions on how to install the snow cover, contact your dealer.
When installing the snow cover, do NOT obstruct the air flow of the unit.
4.6 Noise and acoustic protection
The unit is a source of noise mainly due to rotation of compressors and fans.
The noise level for each model size is listed in sales documentation. If the
unit is correctly installed, operated and maintained the noise emission level
do not require any special protection device to operate continuously close to
the unit without any risk.
4.7 Water circuit for connection with the unit
4.7.1 Water piping
Piping must be designed with the lowest number of elbows and the lowest number
of vertical changes of direction. In this way, installation costs are reduced
considerably, and system performance is improved.
The water system must have:
- Antivibration mountings to reduce transmission of vibrations to the structures.
- Isolating valves to isolate the unit from the water system during maintenance.
- To protect the unit, the BPHE must be protected against freezing by continuous monitoring of the water flow in the BPHE by a flow switch. In most cases, on site, the flow switch is set to generate an alarm only when the water pump turns off and the water flow drops to zero. It is recommended to adjust the flow switch to produce a “Water Leakage Alarm” when the water flow reaches the minimum value of the flow allowable (see table 1); in this case the BPHE is protected against freezing and the flow switch can detect the clogging of the water filter.
- Manual or automatic air venting device at the system highest point and drain device at the system lowest point.
- Neither the BPHE nor the heat recovery device must be positioned at the system’s highest point.
- A suitable device that can maintain the water system under pressure (expansion tank, etc.).
- Water temperature and pressure indicators to assist the operator during service and maintenance.
- Gebrauch: A filter or device that can remove particles from the fluid. The use of a filter extends the life of the BPHE and pump and helps to keep the water system in a better condition. The water filter must be installed as close as possible to the unit. If the water filter is installed in another part of the water system, the Installer must guarantee the cleaning of the water pipes between the water filter and the BPHE. Precautions for correct use:
• All water components and piping/hydraulic devices outside the unit must therefore be protected against freezing.
• All water components (eg.BPHE) and piping/hydraulic devices must be emptied of water during the winter season, unless an ethylene glycol mixture in appropriate percentage is added to the water circuit.
• In case of unit substitution, the entire water system must be emptied and cleaned before the new unit is installed.
Regular tests and proper chemical treatment of water are recommended before starting up the new unit.
• If glycol is added to the water system as antifreeze protection, pay attention to the fact that suction pressure will be lower, the unit performance will be lower and water pressure drops will be greater. All unit protection systems, such as antifreeze, and low-pressure protection will have to be readjusted.
• When fastening the plant piping to the unit water piping, it is recommended to hold the threaded counterpart tight while fastening, to avoid unintentional rotations.
The maximum glycol percentage is 40% for all the unit.
In the following table are illustrated the minimum glycol percentage for low ambient air temperature AMBIENT T [°C]| -3 -8| – 15 -20
---|---|---
ETHYLENE GLYCOL| 10%| 20%| 30%| 40%
PROPYLENE GLYCOL| 10%| 20%| 35%| 40%
Table 2 – Minimum glycol percentage for low ambient air temperature
Protection of the water circuit is necessary in the winter season, even with
the unit not in operation.
• Before insulating water piping, check that there are no leaks. The complete
hydraulic circuit must be insulated to prevent condensation and reduced
refrigeration capacity. Protect the water pipes from frost during winter
(using for example a glycol solution or a heating cable).
• Check that the water pressure does not exceed the design pressure of the
water side heat exchangers. Install a safety valve on the water pipe
downstream of the BPHE.
- Select the piping diameter in relation to the required water flow and available external static pressure of the pump.
See the following table for the recommended water piping diameter. Unit| Water piping diameter
---|---
EWAT/EWYT016~040CZ(N/P/H)-A1| 1 ¼”
EWAT/EWYT040~090CZ(N/P/H)-A2| 2”
4.7.2 Flow-switch
Flow switch is a standard component fitted to all units. To ensure sufficient
water flow through the plate exchanger, it is essential that a flow switch be
installed on the water circuit. It is already installed in the standard
supply. The purpose of the flow switch is to stop the unit in the event of
interrupted water fl ow, thus protecting the BPHE from freezing.
This is a palette flow switch appropriate for uninterrupted use outdoors
(IP65).
The flow switch is set up to intervene when the water flow of the BPHE reaches
the minimum value of the flow acceptable (see the table below).
Modell | Flow switch Setpoint [l/min] |
---|---|
EWAT/EWYT016CZ(N/P/H)-A1 | 22 |
EWAT/EWYT021CZ(N/P/H)-A1 | 22 |
EWAT/EWYT025CZ(N/P/H)-A1 | 22 |
EWAT/EWYT032CZ(N/P/H)-A1 | 31 |
EWAT/EWYT040CZ(N/P/H)-A1 | 31 |
EWAT/EWYT040CZ(N/P/H)-A2 | 57 |
EWAT/EWYT050CZ(N/P/H)-A2 | 57 |
EWAT/EWYT064CZ(N/P/H)-A2 | 57 |
EWAT/EWYT090CZ(N/P/H)-A2 | 57 |
Table 3 – Flow Switch Setpoint
To ensure correct operation of the unit, the value of the water flow in the
evaporator must be within the declared range for that unit. A water flow lower
than the minimum value shown in the following table (table 4) could cause
problems with freezing, fouling and poor control. A water flow rate higher
than the maximum value shown in table 4 will result in an unacceptable load
loss and excessive erosion of the pipes, with vibrations that can cause
breakage
N – Naked Version
MODEL| Min.Flow [l/s]| Max. Flow [l/s]
EWAT/EWYT016CZN-A1| 0.44| 2.34
EWAT/EWYT021CZN-A1| 0,84| 2,66
EWAT/EWYT025CZN-A1| 0,84| 2,66
EWAT/EWYT032CZN-A1| 1,01| 2,66
EWAT/EWYT040CZN-A1| 1,01| 2,66
EWAT/EWYT040CZN-A2| 1,41| 6,00
EWAT/EWYT050CZN-A2| 1,41| 6,00
EWAT/EWYT064CZN-A2| 1,41| 6,00
P – H.Pump-Version
MODEL | Min. Flow [l/s] | Max. Flow [l/s] |
---|---|---|
EWAT/EWYT021CZ(P/H)-A1 | 0,84 | 1,90 |
EWAT/EWYT025CZ(P/H)-A1 | 0,84 | 1,90 |
EWAT/EWYT032CZ(P/H)-A1 | 1,01 | 2,66 |
EWAT/EWYT040CZ(P/H)-A1 | 1,01 | 2,66 |
EWAT/EWYT040CZ(P/H)-A2 | 1,41 | 3,89 |
EWAT/EWYT050CZ(P/H)-A2 | 1,41 | 3,89 |
EWAT/EWYT064CZ(P/H)-A2 | 1,41 | 5,50 |
EWAT/EWYT090CZ(P/H)-A2 | 2,43 | 6,00 |
Table 4 –Operating limits
4.7.3 Heat recovery (optional)
Units may be optionally equipped with heat recovery system.
This system is made by a water cooled heat exchanger located on the
compressors discharge pipe.
To guarantee compressor operation within its envelope, units with heat
recovery cannot operate with water temperature of the heat recovery water
lower than 20°C.
It is a responsibility of plant designer and chiller installer to guarantee
the respect of this value (e.g. using recirculati ng bypass valve).
4.7.4 Preparing and checking the water circuit connection
The units have water inputs and outputs for connecting the heat pump to
water circuit of the system. This circuit must be connected to the unit by an
authorized technician and must comply with all regulations on the subject.
If dirt penetrates the water circuit, there could be
problems.
Therefore, always remember the following when connecting the
water circuit:
- Only use pipes that are clean inside
- Keep the end of the pipe facing downward when removing any burrs
- Cover the end of the pipe when inserting it through a wall to avoid dust and dirt getting in.
- Clean the pipes of the system located between the filter and the unit, with running water, before connecting it to the system.
4.7.5 Water pressure
Check whether the water pressure is above 1 bar. If it is lower, add water.
The maximum operating pressure is 3 bar for P and H versions.
For N version please take care that the components installed in the field
piping can withstand the water pressure “maximum 3 bar + static pressure of
the external pump” and not exceeding 10 bar.
4.7.6 Hydraulic diagram
The unit is supplied with the following hydraulic components:
WATER CIRCUIT
N.B. The Pump kit
is optional
WATER CIRCUIT EQUIPMENT
a.Pump | m.Expansion vessel |
---|---|
d.Drainf | y.Water filter |
e.Plugged fitting | TT Temperature sensor |
f.Safety valve 3 BAR ½” | PI Pressure gauge |
g.Shut off valve | FS Flowswitch |
h.Air vent |
If air, moisture or dust gets into the circuit problems may occur. To prevent this use shut-off valves, and water filter which are delivered with the unit.
Legend:
a. Shut-off valve
b. Water filter
c. Threaded connector
Note: The hydraulic elements are supplied together with the unit and are
located inside the cabinet.
4.8 Water treatment
Before putting the unit into operation, clean the water circuit.
The BPHE must not be exposed to flushing velocities or debris released during
flushing. It is recommended that a suitably sized bypass and valve arrangement
is installed to allow flushing of the piping system. The bypass can be used
during maintenance to isolate the heat exchanger without disrupting flow to
other units.
Any damage due to the presence of foreign bodies or debris in the BPHE will
not be covered by warranty. Dirt, scales, corrosion debris and other material
can accumulate inside the heat exchanger and reduce its heat exchanging
capacity.
Pressure drop can increase as well, thus reducing water flow. Proper water
treatment therefore reduces the ri sk of corrosion, erosion, scaling, etc. The
most appropriate water treatment must be determined locally, according to the
type of system and water characteristics.
The manufacturer is not responsible for damage to or malfunctioning of
equipment caused by f ailure to treat water or by improperly treated water. In
the following table are listed the acceptable water quality limits:
DAE Water quality requirements | BPHE |
---|---|
pH (25 °C) | 7,5– 9,0 |
Electrical conductivity [μS/cm] (25°C) | <500 |
Chloride ion [mg Cl / l] | < 70 (HP1); < 300 (CO2) |
Sulphate ion [mg SO42 / l] | <100 |
Alkalinity [mg CaCO3 / l] | <200 |
Total Hardness [mg CaCO3 / l] | 75– 150 |
Iron [mg Fe / l] | <0,2 |
Ammonium ion [mg NH4+ / l] | <0,5 |
Silica [mg SiO2 / l] | |
Chlorine molecular (mg Cl2/l) | <0,5 |
Table 5 – Acceptable water quality limits
4.9 Water pressure drops for filters
In the following figure the water filter pressure drops are
illustrated.![DAIKIN EWYT-CZ Air Water Heat Pump Units with Scroll Compressors
- Figure 12](https://manuals.plus/wp-content/uploads/2024/02/DAIKIN-EWYT-CZ-
Air-Water-Heat-Pump-Units-with-Scroll-Compressors-Figure-12.png) 4.10 Pump
kit mounted on board (Optional)
Before to starting up the pump, ensure that the hydraulic circuit is filled correctly with a minimum static pressure of 1 bar as protection from cavitation. Furthermore, to ensure correct venting of the piping system make sure the venting valve indicated on the hydraulic diagrams with the letter “h”, is open.
In the following figure are illustrated the External pressure head (KPa) in case of Low li ft and High lift pump.
EWA(Y)T-CZP – Pump low lift EWA(Y)T-CZH – Pump high-lift External static pressure refers to unit equipped with hydronic kit, defined as difference between pump external static pressure and evaporator and water filter pressure drop. Water flow range refer to pump only. For water flow limits of the unit refer to water flow section.
Pump low lift
Model| Pump curve
EWAT/EWYT016CZP-A1| A
EWAT/EWYT021CZP-A1| B
EWAT/EWYT025CZP-A1| B
EWAT/EWYT032CZP-A1| C
EWAT/EWYT040CZP-A1| C
EWAT/EWYT040CZP-A2| D
EWAT/EWYT050CZP-A2| D
EWAT/EWYT064CZP-A2| E
EWAT/EWYT090CZP-A2| F
Pump high lift
Model | Pump curve |
---|---|
EWAT/EWYT016CZHA1 | A |
EWAT/EWYT021CZHA1 | B |
EWAT/EWYT025CZHA1 | B |
EWAT/EWYT032CZHA1 | C |
EWAT/EWYT040CZHA1 | C |
EWAT/EWYT040CZHA2 | D |
EWAT/EWYT050CZHA2 | D |
EWAT/EWYT064CZHA2 | E |
EWAT/EWYT090CZHA2 | F |
Table 6 – Pump curve associated with each unit size
4.11 Operation limits
Operation out of the mentioned limits may damage the unit. In case of any
doubt contact the manufacturer representative. In the following figure are
illustrated the operation ranges both in cooling and heating mode, in terms of
Leaving water temperature (LWT) and Ambient temperature (OAT).
OPERATION RANGE COOLING – EWAT-CZ
OAT | Outside ambient temperature |
---|---|
ELWT | Evaporator Leaving water temperature |
Ref. 1 | Unit operations in this area require OP. 192 HIGH AMBIENT |
TEMPERATURE KIT.
Ref. 2| Unit operations in this area require the enabling of the Brine
version in the controller and the use of the proper amount of glycol.
OPERATION RANGE COOLING – EWYT-CZ OPERATION RANGE HEATING – EWYT-CZ
EWYT021~090-CZ
OAT | Outside ambient temperature |
---|---|
CLWT | Condenser Leaving water temperature |
Ref. 1 | Unit operations in this area require OP. 192 HIGH AMBIENT |
TEMPERATURE KIT.
Ref. 2| Unit operations in this area require the enabling of the Brine
version in the controller and the use of the proper amount of glycol.
Ref. 3| Certain unit sizes might work in part load in this area.
Ref. 4| Certain unit sizes might work in part load in this area.
Selecting the accessory EKDAGBL “Restricted Application Definer” the unit
can’t work in this specific area.
EWYT016-CZ The charts shown above constitute a guideline
on operating limits in the range.
Refer to the CSS selection software for the actual operating limits in the
working conditions for each model.
4.12 Operating stability and minimum water content in the system
For the correct functioning of the machines it is important to guarantee a
minimum water content inside the system, avoiding an excessive number of
compressor startups and stops. In fact, every time the compressor starts
working, an excessive amount of oil from the compressor enters the circulation
in the refrigerant circuit and at the same time there is an increase in the
temperature of the compressor stator, generated by the inrush current of the
starting. In order to prevent damage to the compressor, the control system
will therefore permit no more than 10 startups per hour. The plant where the
unit is installed must therefore ensure that the overall water content allows
constant operation of the unit and consequently also greater environmental
comfort.
As a general indication the water content should not be less than the values
in the following table:
Heat Pump | Suggested l/kW | Min. water content [l] |
---|---|---|
EWYT016CZ(N/P/H)-A1 | 5.7 | 90 |
EWYT021CZ(N/P/H)-A1 | 5.0 | 100 |
EWYT025CZ(N/P/H)-A1 | 4.4 | 110 |
EWYT032CZ(N/P/H)-A1 | 4.9 | 160 |
EWYT040CZ(N/P/H)-A1 | 4.6 | 180 |
EWYT040CZ(N/P/H)-A2 | 3.0 | 120 |
EWYT050CZ(N/P/H)-A2 | 2.6 | 130 |
EWYT064CZ(N/P/H)-A2 | 2.7 | 170 |
EWYT090CZ(N/P/H)-A2 | 2.7 | 230 |
Cooling only | Suggested L/kW | Min water content [l] |
EWYT016CZ(N/P/H)-A1 | 3.7 | 58 |
EWYT021CZ(N/P/H)-A1 | 2.8 | 58 |
EWYT025CZ(N/P/H)-A1 | 2.4 | 58 |
EWYT032CZ(N/P/H)-A1 | 2.8 | 90 |
EWYT040CZ(N/P/H)-A1 | 2.3 | 90 |
EWYT040CZ(N/P/H)-A2 | 1.5 | 60 |
EWYT050CZ(N/P/H)-A2 | 1.2 | 60 |
EWYT064CZ(N/P/H)-A2 | 1.1 | 73 |
EWYT090CZ(N/P/H)-A2 | 1.0 | 90 |
Table 7 – Minimum water content in the system
NOTE : Extra water may be required in critical processes or in spaces
with a high thermal load.
The difference in startup temperature may vary from 1 to 5 K. This has an
impact on the minimum water volume required when the unit is functioning in
cooling mode. The unit is preset for a startup temperature difference of 2.5
K.
The Thermo ON condition is shown below: EWT > Setpoint + #Start ∆T
Standard | Max | Min |
---|---|---|
Startup ∆T (K) | 2.5 | 5 |
By default, the unit is set to have a water temperature difference of 2.5 K
which allows it to operate with the minimum volume mentioned in the previous
table. However, if a smaller temperature differential is set, as in the case
of process cooling applications where temperature fluctuations must be
avoided, a larger minimum water volume will be required.
To ensure proper operation of the unit when changing the value of setting, the
minimum water volume has to be corrected. If this volume exceeds the range
allowed in the unit, an additional expansion vessel or a buffer tank must be
installed in the field piping.
Minimum water volume correction factor
A water volume correction factor “a” is introduced on the basis of the
difference in startup temperature “b”, the function of which is: a · b =
2,5
Example: To illustrate the impact on the system when modifying the setting, we
will consider a unit with a minimum allowable water volume of 58 L. Assuming
that the setting is changed from Delta T 2.5 K (default) to 1.5 K. The
correction factor to be applied is a=\frac{2,5}{1,5}=1,67, and so to calculate
the minimum water content in the system for a 25 kW unit, in cooling mode, all
we need to do is multiple the default minimum volume by this correction factor
to obtain the new minimum volume, 97l.
4.13 Calibrating the expansion vessel
expansion vessel’s starting pressure depends on the difference between the
level at which the unit is installed and the highest point in the water
circuit, and is calculated as follows:
Pi=0,3+(H/10) (bar)
- Pi Initial pressure
- H Difference between the level at which the unit is installed and the highest point in the circuit
A unit with an onboard pump has a 12 liters expansion vessel with an initial
pressure of 1 bar.
Maximum water volume
Refer to the graph below to determine the maximum water volume in order to
calibrate the expansion vessel:
a Initial pressure of the expansion vessel [bar] b Maximum water volume [L] A
Circuit without glycol
B Circuit with 30% ethylene glycol
C Circuit with 40% ethylene glycol
D Circuit with 30% propylene glycol
E Circuit with 40% propylene glycol
F Default
The default value for initial pressure, shown in the figure, refers to a
difference in H of 7 metres.
If the total water volume in the entire circuit exceeds the permitted maximum
volume, another expansion vessel must be installed. If the difference in
system H is less than 7 metres and the init ial pressure reading is lower than
the maximum permitted value (refer to the graph), no adjustment of initial
pressure is required.
If it is necessary to change the default initial pressure value (1 bar), take
the following recommendations into consideration:
- Use dry nitrogen only to set the initial pressure in the expansion vessel
- An inappropriate initial pressure setting in the expansion vessel will result in malfunctioning of the system.
Changes to the initial pressure of the expansion vessel must be made by
reducing or increasing nitrogen pressure using the Schrader valve on the
expansion vessel.
NOTICE Only an authorised installer can adjust the initial pressure of
the expansion vessel.
To check water volume: examples
Example 1
The unit is installed 5 m below the highest point in the water circuit. The
total water volume in the water circuit is 250 litres. No actions or changes
required.
Example 2
The unit is installed at the highest point in the water circuit. The total
water volume in the water circuit (without the glycol) is 420 l.
Actions:
As the total water volume (420 l) is higher than the preset water volume (340
l), prepressure must be reduced.
The required prepressure is: Pg = (0,3+ (H / 10)) bar = (0,3+ (0/10)) bar =
0,3 bar
The corresponding maximum water volume is about 490 l (see graph).
As 420 l is less than 490 l, the expansion vessel is appropriate for the
installation.
4.14 Antifreeze protection for BPHE and recovery exchangers
If the heat exchangers are completely empty and cleaned with antifreeze
solution, additional methods can be used against freezing.
The following protection methods must be considered when designing the system
as a whole:
-
Continuous water flow circulation inside piping and exchangers;
-
Addition of an appropriate amount of glycol inside the water circuit or, as alternative, an additional heat insulation and heating of exposed piping (internal and external to the unit);
-
If the unit does not work during the winter season, emptying and cl eaning of the heat exchanger.
It is the responsibility of the installer and/or of local maintenance personnel to ensure that described antifreeze methods are used. Make sure that appropriate antifreeze protection is always maintained. Failing to follow the instructions above could result in unit damage. -
ELECTRIC HEATER (Option on request). A heater tape is installed on the water side components (the plates heat exchanger and the expansion vessel) to protect vital parts of the hydraulic system i nside the unit. This heater tape will only protect internal parts of the unit. It cannot protect field installed parts outside the unit. Field heater tapes must be provided by the installer.(1)
Damage caused by freezing is excluded from the warranty, therefore Daikin
Applied Europe S.p.A. declines all responsibility.
(1) Heat recovery exchanger is not equipped with heater tape.
ELECTRICAL INSTALLATION
5.1 General specifications
Refer to the specific wiring diagram for the unit you have bought. Should the
wiring diagram not be on the unit, or should it have been lost, please contact
your manufacturer representative, who will send you a copy.
In case of discrepancies between wiring diagram and electrical panel/cables,
please contact t he manufacturer representative.
All electrical connections to the unit must be carried out in compliance with
laws and regulations in force.
All installation, management and maintenance activities must be carried out by
qualified personnel.
There is a risk of electric shock and burning.
Electrical equipment is capable of operating correctly in the intended ambient
air temperature. For very hot/cold environments (refer to 4.11, “Operation
limits”), additional measures are recommended (contact the manuf acturer
representative).
The electrical equipment is capable of operating correctly when the relative
humidity does not exceed 50% at a maximum temperature of +40 °C. Higher
relative humidities are permitted at lower temperatures (for example 90% at 20
°C).
The product meets the technical requirements of IEC 61000-3-11 and IEC
61000-3-12.
5.2 Electric connections
Provide an electrical circuit to connect the unit. It must be connected to the
copper cables with an adequate section relative to the absorption values and
according to the current electrical standards.
Daikin Applied Europe S.p.A. declines all responsibility for an inadequate
electrical connection.
The connections to the terminals must be made with copper terminals and
cables, otherwise overheating or corrosion may occur at the connection points
with the risk of damaging the unit. The electrical connection must be carried
out by qualified personnel, in compliance with the laws in force.
There is a risk of electric shock.
The power supply to the unit must be set up in such a way that it can be
switched on or off independently from that of other system components and
other equipment in general, by means of a general switch.
The electrical connection of the panel must be carried out maintaining the
correct sequence of the phases. All units require a number of 4 conductor
cables (3 phases + neutral) plus a ground conductor. Refer to the specific
wiring diagram for the unit you have bought. In case of discrepancy between
the wiring diagram and electrical panel/cables, please contact the
manufacturer representative.
Do not apply torque, tension or weight to the main switch terminals. Power
line cables must be supported by appropriate systems.
To avoid interference, all control wires must be connected separately from the
power cables. To do this, use several electrical passage ducts.
The protections for the power supply system must be designed according to the
values mentioned above. A fuse must be present on each phase and, where
provided for by the national laws of the country of installation, a leak
detector to earth.
Before any electrical connection work to the compressor motor and / or the
fans, make sure that the system is switched off and the main switch of the
unit is open. Failure to observe this rule could result in serious personal
injury.
5.3 Cable requirements
The cables connected to the circuit breaker must respect the insulation
distance in the air and the surface isolation distance between the active
conductors and the earth, according to IEC 614391 table 1 and 2, and to the
local national laws.
The cables connected to the main switch must be tightened using a pair of keys
and respecting the unified clamping values, relative to the quality of the
screws of the washers and nuts used.
Connect the earth conductor (yellow / green) to the PE ground terminal.
The equipotential protection conductor (earth conductor) must have a section
according to table 1 of EN 602041 Point 5.2, shown below.
In any case, the equipotential protection conductor (earth conductor) must
have a cross section of at least 10 mm2, in accordance with point 8.2.8 of the
same standard.
Section of the copper phase conductors feeding the equipment
S [mm2]| Minimum cross section of the external copper protection
conductor Sp [mm2]
---|---
S ≤ 16
16 < S ≤ 35
S > 35| S
16
S/2
Table 8 – Table 1 of EN602041 Point 5.2
5.3.1 Maximum cable dimension
Maximum cable dimension that can be physically connected to mainswitch of the
unit.
Modell| Max cable size (mm^2] Model (A] STD-
Configuration| Max cable size (mm^2] Model (A] High ambient
temperature kit op. 192
---|---|---
EWAT/EWYT016CZ(N/P/H)-A1| 16| 63| 16| 63
EWAT/EWYT021CZ(N/P/H)-A1| 16| 63| 16| 63
EWAT/EWYT025CZ(N/P/H)-A1| 16| 63| 16| 63
EWAT/EWYT032CZ(N/P/H)-A1| 16| 63| 50| 100
EWAT/EWYT040CZ(N/P/H)-A1| 16| 63| 50| 100
EWAT/EWYT040CZ(N/P/H)-A2| 50| 80| 50| 80
EWAT/EWYT050CZ(N/P/H)-A2| 50| 80| 50| 80
EWAT/EWYT064CZ(N/P/H)-A2| 50| 100| 70| 125
EWAT/EWYT090CZ(N/P/H)-A2| 70| 125| 70| 125
5.3.2 Safety device requirements
The power supply must be protected with a Residual current device, as
indicated in the table below.
Main switch and Fuses can be added in accordance with the applicable
legislation.
Selection and sizing of the wiring should be done in accordance with the
applicable legislation based and the maximum unit current.
Model| Customer Protection – Mandatory| Fuses-
Not Mandatory
---|---|---
EWAT/EWYT016CZ(N/P/H)-A1| Residual Current device Type A| 32 A| 40 A
EWAT/EWYT021CZ(N/P/H)-A1| 40 A| 40 A
EWAT/EWYT025CZ(N/P/H)-A1| 40 A| 50 A
EWAT/EWYT032CZ(N/P/H)-A1| 63 A| 63 A
EWAT/EWYT040CZ(N/P/H)-A1| 63 A| 80 A
EWAT/EWYT040CZ(N/P/H)-A2| 80 A| 80 A
EWAT/EWYT050CZ(N/P/H)-A2| 80 A| 80 A
EWAT/EWYT064CZ(N/P/H)-A2| 100 A| 100 A
EWAT/EWYT090CZ(N/P/H)-A2| 125 A| 160 A
When using residual current operated circuit brakers, be sure to use a high-
speed type 300 mA rated residual operating current.
5.4 Phase unbalance
In a three-phase system, the excessive unbalance between the phases is the
cause of the engine overheating. The maximum permitted voltage unbalance is
3%, calculated as follows:
Imbalance % = (Vx – Vm) 100 Vm
Where:
Vx = Phase with greatest imbalance
Vm = Average of the voltages
Example:
The three phases measure 383, 386 and 392 V respectively.
The average is: 383 + 386 + 392 3 = 387 V
The unbalance percentage is: (392 – 387) 100 387 = 1,29 %
Less than the maximum allowed (3%).
OPERATOR’S REPONSIBILITIES
It is essential that the operator is appropriately trained and becomes
familiar with the system before operating the unit. In addition to reading
this manual, the operator must study the microprocessor operating manual and
the wiring diagram to understand startup sequence, operation, shutdown
sequence and operation of all the safety devices.
During the unit initial startup phase, a technician authorized by the
manufacturer is available to answer any questions and to give instructions as
to the correct operating procedures.
The operator must keep a record of operating data for every installed unit.
Another registration must also be kept for all the periodic maintenance and
assistance activities.
If the operator notes abnormal or unusual operating conditions, he is advised
to consult the technical service authorized by the manufacturer.
If the unit is switched off, the compressor oil heater cannot be used. Once
the unit is reconnected to the mains, leave the compressor oil heater charged
for at least 6 hours before restarting the unit.
Failure to observe this rule may cause damage to the compressors due to
excessive accumulation of liquid inside them.
This unit represents a substantial investment and deserves the attention and
care to keep this equipment in good working order.
However, during operation and maintenance it is essential to observe the
following instructions:
- Do not allow unauthorized and / or unqualified personnel to access the unit;
- It is forbidden to access the electrical components without having opened the unit main switch and switched off the power supply;
- It is forbidden to access the electrical components without using an insula ting platform. Do not access the electrical components if water and/or moisture are present;
- Verify that all operations on the refrigerant circuit and on the components under pressure are carried out exclusively by qualified personnel;
- The replacement of the compressors must be carried out exclusively by qualified personnel;
- Sharp edges and the surface of the condenser section could cause injury. Avoid direct contact and use adequate protection device;
- Do not introduce solid objects into the water pipes while the unit is connected to the system;
- It is absolutely forbidden to remove all protections of moving parts.
In case of sudden stop of the unit, follow the instructions on the Control
Panel Operating Manual which is part of the on board documentation delivered
to the end user.
It is strongly recommended to perform installation and maintenance with other
people.
Avoid installing the unit in areas that could be dangerous during maintenance
operations, such as platforms without parapets or railings or areas not
complying with the clearance requirements around the unit.
MAINTENANCE
Personnel working on the electrical or the refrigeration components must be
authorized, trained and fully qualified.
Maintenance and repair requiring the assistance of other skilled personnel
should be carried out under the supervision of the person competent in the use
of flammable refrigerants. Any person conducting servicing or maintenance on a
system or associated parts of the equipment should be competent according to
EN 13313.
Persons working on refrigerating systems with flammable refrigerants should
have competence in safety aspects of flammable refrigerant handling supported
by evidence of appropriate training.
No person carrying out work in relation to a refrigerating system which
involves exposing any pipe work shall use any sources of ignition in such a
manner that it may lead to the risk of fire or explosion. All possible
ignition sources, includ ing cigarette smoking, should be kept sufficiently
far away from the site of installation, repairing, removing and disposal,
during which refrigerant can possibly be released to the surrounding space.
Prior to work taking place, the area around the equipment is to be surveyed to
make sure that there are no flammable hazards or ignition risks. “No Smoking”
signs shall be displayed.
Always protect the operating personnel with personal protective equipment
appropriate for the tasks to be performed.
Common individual devices are: Helmet, goggles, gloves, caps, safety shoes.
Additional individual and group protective equipment should be adopted after
an adequate analysis of the specific risks in the area of relevance, according
to the activities to be performed.
Electrical components| Never work on electrical components until the
machine’s main power supply has been cut off with the main switch on the
electrical panel. Wait 10 minutes after cutting off the machine’s power supply
before opening the electrical panel, to prevent the risk of high voltage due
to firing of the capacitors.
---|---
Refrigeranting system| The following precautions should be taken before
working on the refrigerant circuit:
· obtain permit for hot work (if required);
· ensure that no flammable materials are stored in the work area and that no
ignition sources are present anywhere in the work area;
· ensure that suitable fire extinguishing equipment is available;
· ensure that the work area is properly ventilated before working on the
refrigerant circuit or before welding, brazing or soldering work;
· ensure that the leak detection equipment being used is nonsparking,
adequately sealed or intrinsically safe;
· ensure that all maintenance staff have been instructed
· perform the following procedure before working on the refrigerant circuit:
· remove refrigerant (specifying residual pressure);
· purge circuit with inert gas (e.g. nitrogen);
· evacuate at a pressure of 0.3 bar (ass.) (or 0.03 MPa);
· purge circuit with inert gas (e.g. nitrogen) again;
· open the circuit.
If compressors or compressor oils are to be removed, it should be ensured that
it has been evacuated to an acceptable level to ensure that there is no
flammable refrigerant remaining within the lubricant. Only refrigerant
recovery equipment designed for use with flammable refrigerants should be
employed.
If the national rules or regulations permit the refrigerant to be drained,
this should be done safely, using a hose, for example, through which the
refrigerant is discharged into the outside atmosphere in a safe area. It
should be ensured that an inflammable explosive refrigerant concentration
cannot occur near an ignition source or penetrate into a building under any
circumstance.
In the case of refrigerating systems with an indirect system, the heat
transfer fluid should be checked for the possible presence of refrigerant.
After any repair work, the safety devices, for example refrigerant detectors
and mechanical ventilation systems, should be checked and the results
recorded.
It should be ensured that any missing or illegible label on components of the
refrigerant circuit is replaced.
Sources of ignition should not be used when searching for a refrigerant leak.
7.1 Pressure / temperature table 7.2 Routine maintenance
This unit must be maintained by qualified technicians. Before beginning any
work on the system, the personnel shall assure that all security precautions
have been taken.
Neglecting unit maintenance could degrade all parts of the units (coils,
compressors, frames, pipes, etc.) with negative effect on performances and
functionality.
There are two different levels of maintenance, which can be chosen according
to the type of application (critical/noncritical) or to the installation
environment (highly aggressive).
Examples of critical applications are process cooling, data centres, etc.
Highly Aggressive Environments can be defined as the follows:
- Industrial environment (with possible concentration of fumes result of combustion and chemical process);
- Coastal environment;
- Highly polluted urban environment;
- Rural environment close to of animal excrement and fertilizers, and high concentration of exhaust gas from diesel generators;
- Desert areas with risk of sandstorms;
- Combinations of the above.
Table 10 lists all Maintenance activities for standard applications and
standard environment. Table 11 lists all Maintenance activities for critical
applications or highly aggressive environment.
Unit exposed to a highly aggressive environment can face corrosion in a
shorter time than ones installed on a standard environment. Corrosion causes a
rapid rusting of the frame core, consequently, decreases unit structure life
time. To avoid that, it is necessary to wash periodically the frame surfaces
with water and suitable detergents.
In case of part of unit frame paint came off, it is important to stop its
progressive deterioration by repainting the exposed parts using proper
products. Please contact factory to get the required products specifications.
In case of just salt deposits are present, it is enough to rinse the parts
with fresh water.
7.2.1 Air Heat Exchanger Maintenance
Routine cleaning of air heat exchanger surfaces is essential to maintai n
proper operation of the unit, avoid corrosion and rusting. Elimination of
contamination and removal of harmful residues will greatly increase the life
of the coil and extend the life of the unit.
Remove surface dirt, leaves, fibers, etc. with a vacuum cleaner (preferably
with a brush or other soft attachment rather than a metal tube), compressed
air blown from the inside out, and/or a soft bristle (not wire!) brush. Do not
impact or scrape the coil with the vacuum tube, air nozzle, etc.
Use of a water stream, such as a garden hose, against a surface loaded coil
will drive the fibers and dirt into the coil.
This will make cleaning efforts more difficult. Surface loaded fibers must be
completely removed prior to using low velocity clean water rinse.
A monthly clean water rinse is recommended for coils that are applied in
coastal or industrial environments to help to remove chlorides, dirt and
debris. It is very important when rinsing that the water temperature is below
55 °C.
Galvanic corrosion of the connection Copper/Aluminum can occurre in corrosive
atmosphere under the plastic protection;
during the maintenance operations or periodic cleaning, check the aspect of
the plastic protection of the copper/aluminum connection. If it is inflated,
damaged or took off contact the manufacturer representative for advice and
information.
7.2.2 Electrical Installation
All electrical maintenance activities must be followed by qualified personnel.
Make sure the system is switched off and the main switch of the unit open.
Failure to observe this rule could result in serious personal injury. When the
unit is turned off but the disconnection switch is in the closed position, the
unused circuits will still be active.
The maintenance of the electrical system consists of the application of some
general rules as follows:
- the current absorbed by the compressor must be compared to the rated value. Normally the value of the absorbed current is lower than the rated value that corresponds to the absorption of the full load compressor at the maximum operating conditions;
- at least once every three months all the security checks must be made to verify their functionality. Each appliance, with aging, can change its point of operation and this must be monitored to adjust it or replace it. The pump interlocks and flow switches must be checked to make sure that they interrupt the control circuit if they intervene.
7.2.3 Service and limited warranty
All units are factorytested and guaranteed for 12 months as of the first
startup or 18 months as of delivery.
These units have been developed and constructed according to high quality
standards ensuring years of failurefree operation. However, the unit requires
maintenance even during the warranty period, from the time of installation and
not just from the commissioning date. We strongly advise stipulating a
maintenance contract with a service authorized by the manufacturer to ensure
efficient and problemfree service, thanks to the expertise and experience of
our personnel.
It must be borne in mind that operating the unit in an inappropriate manner,
beyond its operating limits or not performing proper maintenance according to
this manual can void the warranty.
Observe the following points, to conform to warranty limits:
- The unit cannot function beyond the specified limits;
- The electrical power supply must be within the voltage limits and without voltage harmonics or sudden changes;
- The threephase power supply must not have an unbalance between phases exceedi ng 3%. The unit must stay turned off until the electrical problem has been solved;
- No safety device, either mechanical, electrical or electronic must be disabled or overridden;
- The water used for filling the water circuit must be clean and suitably treated. A mechanical filter must be installed at the point closest to the BPHE inlet;
- The value of the BPHE water flow must be included in the declared range for the unit considered, refer to the CSS selection software.
List of activities| Weekly| Monthly (Note 1)| Yearly /
Seasonal (Note 2)
---|---|---|---
General
Reading of operating data (Note 3)| X| |
Visual inspection of unit for any damage and/or loosening| | X|
Verification of thermal insulation integrity| | X|
Cleaning| | X|
Paint where necessary| | | X
Analysis of water (4)| | | X
Check of flow switch operation| | X|
Electrical Installation:
Verification of control sequence| | | X
Verify contactor wear – Replace if necessary| | | X
Verify that all electrical terminals are tight – Tighten if necessary| |
X (Quarterly)|
Clean inside the electrical control board| | | X
Visual inspection of components for any signs of overheating| | X|
Verify operation of compressor and electrical resistance| | X|
Refrigeration circuit:
Check for any refrigerant leakage (leak test)| | X|
Analyze compressor vibrations| | | X
Hydraulic circuit:
Check for any water leakage| | X|
Check hydraulic connections| | X|
Check the pressure at the pump inlet| | X|
Clean the water filter| | | X
Check the glycol concentration| | | X
Check the water flow rate| | X|
Check the safety valve| | | X
Coil section:
Check the cleaning of coils and water heat exchangers (Note 5)| | | X
Verify that fans are well tightened| | | X
Verify the coil fins| | | X
BPHE:
Check the cleaning of the BPHE| | | X
Table 10 – Standard Routine Maintenance Plan
Notes:
-
Monthly activities include all the weekly ones.
-
The annual (or early season) activities include all weekly and monthly activities.
-
Daily reading of the operating values of the unit allows maintaining high observational standards.
-
Check for any dissolved metals
-
Clean condenser banks with clean water and water heat exchangers with appropriate chemicals. Particles and fibres could clog up the exchangers, especially for water exchangers pay attention if water rich in calcium carbonate is used. An increase in pressure drops or a decrease in thermal efficiency means that the heat exchangers are clogged.
In environments with a high concentration of airborne particles, it might be necessary to clean the condenser bank more often. -
Units placed or stored in a Highly Aggressive Environment for long time without operation are still subject to those routine maintenance steps.
List of activities (Note 8)| Weekly| Monthly (Note1)| Yearly / Seasonal (Note2)
---|---|---|---
General:
Reading of operating data (Note 3)| X| |
Visual inspection of unit for any damage and/or loosening| | X|
Verification of thermal insulation integrity| | X|
Cleaning| | X|
Paint where necessary| | | X
Analysis of water (4)| | | X
Check of flow switch operation| | X|
Electrical Installation:
Verification of control sequence| | | X
Verify contactor wear – Replace if necessary| | | X
Verify that all electrical terminals are tight – Tighten if necessary| | | X
Clean inside the electrical control board| | X|
Visual inspection of components for any signs of overheating| | X|
Verify operation of compressor and electrical resistance| | X|
Measure compressor motor insulation| | | X
Refrigeration circuit:
Check for any refrigerant leakage (leak test)| | X|
Analyze compressor vibrations| | | X
Hydraulic circuit:
Check for any water leakage| | X|
Check hydraulic connections| | X|
Check the pressure at the pump inlet| | X|
Clean the water filter| | | X
Check the glycol concentration| | | X
Check the water flow rate| | X|
Check the safety valve| | | X
Coil section:
Checking the cleaning of the air heat exchanger (Note 6)| | X|
Check the cleaning of water heat exchangers (Note 6)| | | X
Verify that fans are well tightened| | | X
Verify coil fins| | X|
BPHE:
Check the cleaning of the BPHE| | | X
Table 11 – Routine Maintenance Plan for Critical Application and/or Highly
Aggressive Environment
Notes:
-
Monthly activities include all the weekly ones.
-
The annual (or early season) activities include all weekly and monthly activities.
-
Daily reading of the operating values of the unit allows maintaining high observational standards.
-
Check for any dissolved metals
-
Clean condenser banks with clean water and water heat exchangers with appropriate chemicals. Particles and fibers could clog up the exchangers, especially for water exchangers pay attention if water rich in calcium carbonate is used. An increase in pressure drops or a decrease in thermal efficiency means that the heat exchangers are clogged.
In environments with a high concentration of airborne particles, it might be necessary to clean the condenser bank more often. -
Units placed or stored in a Highly Aggressive Environment for long time without operation are still subject to those routine maintenance steps
7.2.4 Refrigerant circuit scheme
REFRIGERAT| PED- GROUP| LINE| PS (bar)| Ts
(°C)
---|---|---|---|---
R32| 1| HIGH PRESSURE GAS| 42,9| +10/+120
HIGH PRESSURE LIQ| 42,9| -10/+65
LOW PRESSURE| 30| -30/+60
REFRIGERANT| PED- GROUP| LINE| PS (bar)| Ts
(°C)
---|---|---|---|---
R32| 1| HIGH PRESSURE GAS| 42,9| +10/+120
HIGH PRESSURE LIQ| 42,9| -10/+65
LOW PRESSURE| 30| -30/+60
REFRIGERANT| PED- GROUP| LINE| PS (bar)| Ts
(°C)
---|---|---|---|---
R32| 1| HIGH PRESSURE GAS| 42,9| +10/+120
HIGH PRESSURE LIQ| 42,9| -10/+65
LOW PRESSURE| 30| -30/+60
REFRIGERANT| PED- GROUP| LINE| PS (bar)| Ts
(°C)
---|---|---|---|---
R32| 1| HIGH PRESSURE GAS| 42,9| +10/+120
HIGH PRESSURE LIQ| 42,9| -10/+65
LOW PRESSURE| 30| -30/+60
Legend
Item | Description |
---|---|
1 | Scroll compressor |
2 | Four-way valve |
3 | Tube&fins heat-exchanger (coil) |
4 | Biflux-Filter |
5 | Mechanical Filter |
6 | Electronic expansion valve |
7 | Liquid receiver |
8 | Heat exchangerBPHE |
9 | Check valve |
11 | Access fitting |
13 | Receiver valve |
K | Cranckase heater |
Water inlet and outlet are indicative. Please refer to the machine dimensional diagrams for exact water connections. The series is composed by mono (one circuit) and dual (two circuits) reversible unit.
LIST OF THE LABELS APPLIED TO THE UNIT
Labels| Description|
Location
---|---|---
| Generical warning| On the electric panel (outside)
| Hazardous voltage warning| On the electric panel (outside)
| A2L-Symbol| On the electric panel (outside)
****| Manufacturer’s logo| On the electric panel (outside)
| Lifting instructions| **** On the unit frame and one on the packaging
| Lift point label| On the unit panel near the unit lifting holes
| Unit ID plate information| On the unit frame (outside)
| UN-3358-labels| On the packaging
| Water outlet| On the unit panel near the outlet connection
| Water inlet| On the unit panel near the inlet connection
Labels on the unit packaging
Table 12 – Labels applied to the Unit
With the exception of the unit’s identification plate, which is always in
the same position, the other plates may be located in different positions
depending on the model and the options present on the unit.
COMMISSIONING
Only authorized DAIKIN personnel should
conduct commissioning
This general commissioning checklist can be used as a guideline and
reporting template during the commissioning and hand-over to the user.
For more detailed commissioning instructions, please contact the local Daikin
Service department or authorized representative of the manufacturer
General | Yes | No | N/A |
---|---|---|---|
Check for external damage | |||
Open all isolation and / or shutoff valves |
Verify that the unit is pressurized with refrigerant in all of its parts
before making the connection to the hydraulic circuit| | |
Chilled Water| Yes| No| N/A
Piping complete| | |
Water System filled and vented| | |
Pumps installed & operational (rotation checked)| | |
Strainers installed and clean| | |
Controls (3way valves, bypass valves, etc.) operable| | |
Flow switch installed| | |
Water system operated and flow balanced to meet unit design requirements| | |
Proper glycol percentage for the application in accordance with Daikin
specifications| | |
Condenser Water| Yes| No| N/A
Cooling tower flushed, filled and piping vented| | |
Pumps installed & operational (rotation checked)| | |
Strainers installed and clean| | |
Controls (3way valves, bypass valves, etc.) operable| | |
Water system operated and flow balanced to meet unit design requirements| | |
Proper glycol percentage for the application in accordance with Daikin
specifications| | |
Electrical| Yes| No| N/A
Power leads connected to unit main terminal block| | |
Power leads have been checked for proper electrical phasing UVW for L1, L2, &
L3 respectively| | |
All interlock wiring complete and complies with Daikin specifications| | |
Pump starter and interlocks wired| | |
Cooling tower fans and controls wired| | |
Wiring complies with National Electrical Code and local codes| | |
Miscellaneous| Yes| No| N/A
Unit installed in accordance with Daikin IOM specifications (leveling, space
requirements, …)| | |
Thermometer wells, thermometers, gauges, control wells, controls, etc.,
installed| | |
A minimum system load of 60% of machine capacity is available for testing and
adjusting controls| | |
Table 13 – Checks before starting up the unit
This list must be completed and sent to the local Daikin Service department
at least two weeks before the startup date.
IMPORTANT INFORMATION ON THE REFRIGERANT USED
This product contains fluorinated greenhouse gases. Do not vent gases into the
atmosphere.
Refrigerant: R32
GWP Value (Global Warming Potential): 675
The refrigerant system is charged with fluorinated greenhouse gases and the
refrigerant charge is impressed on the plate.
In Europe, the greenhouse gas emissions of the total amount of refrigerant in
the system (expressed in equivalent tonnes of CO2) is used to determine the
frequency of maintenance. Follow the applicable legislation.
PERIODIC CHECKS AND COMMISSIONING OF PRESSURE EQUIPMENT
The units are included in category II and III of the classification
established by the European Directive 2014/68/EU (PED).
For units belonging to these categories, some local regulations require a
periodic inspection by an authorized person.
Please check with your local requirements.
DISMISSION AND DISPOSAL
The unit is made of metal, plastic and electronic parts. All these components
must be disposed of in accordance with local disposal laws and if in scope
with the national laws implementing the Directive 2012/19/EU (RAEE).
Lead batteries must be collected and sent to specific waste collection
centers.
**** Avoid the escape of refrigerant gases into the environment by using
suitable pressure vessels and tools for transferring the fluids under
pressure. This operation must be carried out by competent personnel in
refrigeration systems and in compliance with the laws in force in the country
of installation.
The present publication is drawn up only for technical support and it does not
constitute a binding commitment for Daikin Applied Europe S.p.A.. Its content
has been written by Daikin Applied Europe S.p.A. to the best of its knowledge.
No explicit or implied warranty is given for the completeness, accuracy,
reliability of its contents. All data and specification s contained therein
may be subject to change without notice. Refer to the data communicated at the
time of the order. Daikin Applied Europe S.p.A. explicitly rejects any
liability for any direct or indirect damage, in the broadest sense, arising
from or related to the use and/or interpretation of this publication. All
content is copyrighted by Daikin Applied Europe S.p.A..
DAIKIN APPLIED EUROPE S.p.A.
Via Piani di Santa Maria, 72 – 00072 Ariccia (Roma) – Italy
Tel: (+39) 06 93 73 11 – Fax: (+39) 06 93 74 014
http://www.daikinapplied.eu
D-EIMHP01405-21_04EN
Documents / Resources
|
DAIKIN EWYT-CZ Air Water Heat Pump Units with Scroll
Compressors
[pdf] Instruction Manual