Waterite VERSION III Advanced Reverse Osmosis System Instruction Manual
- June 17, 2024
- Waterite
Table of Contents
Waterite VERSION III Advanced Reverse Osmosis System
Congratulations!
You have purchased the finest commercial reverse osmosis water system available. It will provide years of reliable service if properly installed, operated and maintained. Please read this entire manual before attempting installation and operation.
THIS MANUAL IS TO BE LEFT WITH THE OWNER OF THE EQUIPMENT FOR REFERENCE PURPOSES AND TECHNICAL GUIDANCE. IT IS STRONGLY RECOMMENDED THAT QUALIFIED DEALER SERVICE PERSONNEL BE CONTACTED IN THE EVENT OF AN UNKNOWN INTERRUPTION OF SERVICE OR APPARENT PRODUCT MALFUNCTION. AN ANNUAL PREVENTATIVE MAINTENANCE INSPECTION BY A WATER PROFESSIONAL IS RECOMMENDED TO ENSURE TROUBLE-FREE AND CONTINUOUS OPERATION
Frequently Asked Questions
Before getting started, take the time to familiarize yourself with your new Waterite system by reading some FAQs listed below. Call us or ask your dealer if you have any other questions about your system’s operation.
Before getting started, take the time to familiarize yourself with your new Waterite system by reading some FAQs listed below. Call us or ask your dealer if you have any other questions about your system’s operation.
Q: How does the VectaMaxx™ RSL Reverse Osmosis System differ from an
ordinary water filter?
Ordinary water filters use a screen to separate only particles of dirt and
sediment from the raw water source. Reverse osmosis employs a semi-permeable
membrane that removes not only particles but also a very high percentage of
dissolved contaminants, molecule by molecule, from your raw water. Your system
will deliver pure, refined water consistently to the designated storage tank
or water distribution equipment.
Q: What is the membrane and how does it work?
The membrane element consists of several thin layers or sheets of film that
are bonded together and rolled in a spiral configuration around a plastic
tube. As the raw water passes across the surface of the membrane, only pure
water molecules are allowed to pass through and collect in the tube, while all
other mineral and contaminant molecules are rejected and washed from the
surface of the membrane to the drain.
Q: What processes does the VectaMaxx™ RSL RO system use?
VectaMaxx™ RSL systems use two stages of treatment to produce high-purity
product water.
The feed water first flows through a 5-micron polypropylene filter used to
reduce suspended particles. The second stage is the reverse osmosis
membrane(s) that separates most dissolved contaminants from the water
molecules. These standard processes will probably be augmented with additional
pre-treatment processes, depending on your raw water source.
Q: Will reverse osmosis remove sodium chloride and other salts from the
water?
Yes. Reverse osmosis was originally developed to make drinking water from
seawater. Your system is equipped with a membrane that will be very effective
in reducing sodium levels normally found in ground water or softened water.
VectaMaxx™ RSL and RSLHP systems are not designed for use on seawater.
Q: Does reverse osmosis remove bacteria? Cryptosporidium? Viruses?
Reverse osmosis membranes will virtually eliminate most chemicals, bacteria,
viruses and parasites such as Cryptosporidium from the water. Where these
conditions exist, pre-filters and other system components located before the
membrane will become contaminated from exposure to them. Cross contamination
of the entire system may occur when the membrane or filters are changed or
disturbed.
THIS REVERSE OSMOSIS WATER SYSTEM IS DESIGNED ONLY TO IMPROVE AESTHETIC PROPERTIES AND IS NOT DESIGNED TO ACT AS A PRIMARY BARRIER TO WATERBORNE MICROBIOLOGICAL OR TOXIC CHEMICAL CONTAMINATION. WHERE THESE CONDITIONS MAY EXIST CONSULT A WATER PROFESSIONAL TO ENSURE SUFFICIENT RAW WATER PRE- TREATMENT AND DISINFECTION.
Q: What other contaminants does reverse osmosis remove?
The combined filtering and RO processes in your system will remove more than
98% of many organic compounds, including THMs (chloroforms), DBCP, lindane,
TCE (trichloroethylene), PCE (tetrachloroethylene), carbon tetrachloride and
chlorine. Very conservatively, a TFC membrane will remove the following
percentages of contaminants:
Barium | 97% | Fluoride | 90% | Radium | 97% | Sulphates | 97% |
---|---|---|---|---|---|---|---|
Bicarbonate | 94% | Lead | 97% | Selenium | 97% | Total Dissolved |
Solids
| 97%
Cadmium| 97%| Magnesium| 97%| Silicates| 96%| PCBs| 97%
Calcium| 97%| Nickel| 97%| Silver| 85%| Insecticides| 97%
Chromium| 92%| Nitrates| 80%| Sodium| 92%| Herbicides| 97%
Copper| 97%| Potassium| 92%| Strontium| 97%| Detergents| 97%
Q: Where is the system installed?
Each application will require access to the feed water source, electrical
power, a storage vessel for the permeate and a drain for the wastewater to be
routed to. The system should be protected from the elements and at all times
protected from freezing. If the system is used to provide water to a critical
piece of equipment, you may consider protection from power surges and
lightning strikes.
Q: Can the VectaMaxx™ RSL system be connected multiple appliances?
Yes. Many installations will involve providing water to multiple appliances or
pieces of equipment simultaneously. Make sure that the peak usage of water for
the combined equipment does not exceed the output of your RO system or its
product water storage. See your dealer for advice and parts.
Q: What factors affect the quantity and the quality of the water
produced?
-
Pressure: The greater the RO system pressure, the greater the water quantity that will be produced by the membrane.
a. Your VectaMaxx™ RSL unit has been equipped with ultra- low energy membrane(s) that are designed to operate at a minimum system pressure of 100 psi. (7.0 kg/cm²) and a maximum of 135 psi (9.0 kg/cm²) for models 2400 and 4800, 140 psi (9.8 kg/cm²) for models 7200 and 9600. Do not attempt to operate your RSL system at pressures exceeding 150 psi, as damage to the membrane or premature fouling may result*.
b. The RSLHP units use a brackish water membrane that is rated for 225 psi. All units are designed to operate to a maximum pressure of 250 psi. -
Temperature:
a. Production increases with temperature, standard production ratings are established at 25°C. Never operate the system from the hot water line or with water exceeding 35°C, as this will damage the membrane and internal components. -
Membrane type: VectaMaxx™ RSL systems use premium quality TFC (Thin Film Composite) membranes, specially chosen for general commercial applications. Please contact your dealer or Waterite for information on special application or nanofiltration membranes.
-
TDS: The higher the Total Dissolved Solids in the raw water, the lower the rate of output of product water.
- Units equipped with an optional CIP are equipped to operate at a maximum of 160 psi (11.3 kg/cm²)
Q: How much water does the VectaMaxx™ RSL system produce?
-
The VectaMaxx™ RSL systems use membranes each nominally rated for 2400GPD.
Actual output will be dependent upon the factors explained previously. In optimal applications (low feed water TDS, feed water =25°C, you may expect 1600-2200 USG from each membrane to be available over 24 hours. -
The VectaMaxx™ RSLHP units use membranes each nominally rated for 2000GPD. Actual output will be dependent upon the factors explained previously. In optimal applications, feed water =25°C, you may expect 1300-1800 USG from each membrane to be available over 24 hours.
Q: Can the amount of total water produced be increased?
Once the system has been set for optimal operation, the overall water
available for consumption over a set period of time will be increased by
increasing the storage capacity. This will increase the time available for the
unit to produce water in off-peak hours (instead of standing idle), and more
storage capacity to be available in peak hours when water usage may exceed
production capacity, for short intervals.
Q: What is the standard warranty with the VectaMaxx™ RSL system?
Every VectaMaxx™ RSL and RSLHP system comes with a standard one-year limited
warranty on all parts and shop repair labour, freight excluded. See section 5
in this manual for details on components with limited warranty coverage.
Q: What is the maintenance schedule for the VectaMaxx™ RSL system?
A good rule of thumb is to replace the pre-filter every month in commercial
applications. Consider changing them biweekly when in continuous use or when
used with untreated water sources.
Dependent upon feed water quality, your membrane(s) should have a life
expectancy of 1-5 years.
More severe water conditions (iron, hardness) may shorten this significantly;
soft water sources may allow a membrane life of up to 8 years. See Section 5.5
Q: When should the membrane(s) be cleaned or changed?
If you notice gradually decreasing production from your system, differing
taste to your drinking water or water analyses indicate a rising TDS, it
probably means that your membrane(s) are deteriorating and losing
effectiveness. You may purchase a pocket or full-featured TDS meter from your
dealer – this is the best way to gauge your RO’s operation.
Where the RO is used as a pre-treatment for a process requiring water to exact
standards, you should adopt a regular ongoing sampling and testing procedure
to ensure compliance, as product water will vary with the quality of the RO
feed water.
Designing your Installation
Your reverse osmosis system is designed to operate with feed water quality parameters that fall in a specific range. The lifespan of the membranes and the ability of the system to produce water in the required volume will depend largely on the feed water that is delivered to the system.
Step 2.1. Start with a Thorough Water Analysis
Every successful installation begins with a full analysis of the raw water
source. Testing should measure the following:
✓ Total Hardness: This measures the calcium and magnesium hardness in the
water.
Hardness in excess of 6 grains/gallon (103 mg/l) must be pre-treated by
softening.
Failure to do so will cause premature failure of the membrane through lime
scaling.
✓ Total Iron: Iron is another common membrane foulant. Found in most
water supplies, it’s particularly prevalent in supplies drawn from wells. In
its ferrous state (Fe+2), it’s soluble. However, when it’s oxidized to its
ferric state (Fe+3), it’s insoluble and forms a precipitate. Concentrations in
excess of .05 ppm must be pre-treated with an iron remover (concentrations > 2
ppm) or combination softener* (for iron concentrations < 2 ppm); otherwise
premature membrane and system equipment failure through iron deposit fouling
will result.
✓ Manganese: Manganese is a commonly occurring mineral found in ground
water.
Manganese will leave black, scaly deposits and will eventually foul membranes
in concentrations greater than .05 ppm. Manganese must be treated with a
manganese greensand filter, regenerated with potassium permanganate.
✓ Hydrogen Sulphide: Most commonly, hydrogen sulphide is known for its
“rotten egg” odour. In addition to having a objectionable odour, it is highly
corrosive and will damage plumbing and equipment. At lower concentrations (< 1
ppm) it can be removed with a Paterson Iron Remover (air injection). At levels
exceeding 1 ppm it will need to be treated with a manganese greensand filter.
✓ Nitrates: The presence of nitrates in the water is usually an
indicator for other problems with the water source. Nitrates are a by-product
of the decomposition of organic material that may include sewage or run-off
from septic systems. Surface runoff containing fertilizers will also be high
in nitrates. The source of the nitrates should be found and eliminated – feed
water should be treated with nitrate-selective ion exchange resins to reduce
nitrates to < 5 mg/l.
✓ Tannins and Lignin: These are organic materials that are often
contained in surface water and shallow well water. Their origin is the natural
decomposition of plant matter and tree barks, leaving a brown colour ranging
from a pale yellow to dark amber. Feed water tannins must be pre-treated to
levels < .5 mg/l to avoid membrane fouling. This is usually achieved through
the use of organic scavenging ion exchange resin (polystyrene or polyacrylic),
regenerated with salt.
✓ Chlorine: Feed water should be free of chlorine (< .1 ppm), as TFC
membranes are easily damaged by chronic chlorine exposure. This is an
important consideration when.
When softeners are used for iron reduction, be sure to fit your softener with a resin bed cleaner to assist in the flushing of iron deposits from the resin bed during backwashing and regeneration. municipal water is used as the feed water source. Pre-treatment by carbon filtration is very effective for chlorine reduction – carbon eventually becomes exhausted and must be replaced to ensure continuous filtration. If stabilized chlorine is present, size your carbon filter 2 to 3 times larger than for unstabilized chlorine to ensure removal. Consider installing a post-carbon filter test port for ease of sampling.
✓ Organic and Microbiological Activity: Raw water sources, particularly
surface water, often contain algae and naturally occurring bacteria. Ground
water may contain sulphur or iron reducing bacteria or may be contaminated
with other more dangerous strains of coliforms or E. coli. These must be
treated to avoid contamination or fouling of the pre-treatment systems or
membrane element(s).
✓ pH: Most membrane manufacturers recommend a pH range between 3.0 and
11.0 for the membrane element. We recommend that the system operate at between
5.5 and 9.5, to minimize the effects of extremely acidic or scale-forming
water at either ends of the range. Extremes in pH will be harder on your
system, either causing premature corrosion on metallic parts or scaling
internal components upstream from the membrane, and likely the membrane
itself. Keep in mind that reverse osmosis lowers the pH of the feed water, by
up to 1.0, depending on the water chemistry. This will be a consideration for
the end use of product water and for the vessels and plumbing system that will
be used to store and control it.
✓ Turbidity: This is the term to describe suspended particulate in the
raw water.
Turbidity is treated by the sediment cartridges that your RO system has been
equipped with. Reduction of turbidity is necessary to avoid fouling your
membrane and damaging your drive pump. Make sure that your prefilters are
changed regularly and that quality Excelpure 5-micron cartridges are used as
replacements. The SDI (silt density index) on feed water reaching the membrane
must be kept < 5 to assure long membrane life.
Step 2.2. Plan Your Pre-treatment Strategy
Pre-treating feed water can lengthen the life of membrane elements, improve
the quality of the water produced and reduce the amount of maintenance and
cleaning a system requires.
The importance of feed water conditions is evident when you examine how
crossflow membranes work. In simple terms, a crossflow filtration system
separates an influent stream into two effluent streams – the permeate and the
concentrate. The permeate is the portion of the fluid that has passed through
the semi-permeable membrane. The concentrate stream, on the other hand,
contains constituents that have been rejected by the membrane.
An inherent advantage of crossflow filtration is its ability to continuously
operate in a self-cleaning mode. It’s self-cleaning because suspended solids
and rejected solutes are constantly swept away from the membrane surface.
Membrane fouling occurs when materials from the feed stream collect on or near
the membrane surface and restrict water permeation. Fouling may occur as
layers of deposition on the surface of the membrane (cake fouling), a hardened
layer on the membrane surface (scale), particle insertion into the pore
channel or entrance (pore blockage), or chemical attachment of particles to
the membrane (adsorption).
You will note that many of the prescribed treatments for various raw water
conditions will be effective in treating more than one problem. Where multiple
pre-treatment requirements are necessary, consult with a water treatment
professional to design a pre-treatment system that meets the necessary needs
most economically.
Use the pre-treatment summary below to prescribe the necessary pre-treatment where your water analysis indicates parameters outside of the recommended range:
Pre-Treatment Summary Chart
Recommended Feed Water Range| Potential Effect| Pre-Treatment
Solution| Waterite Models
---|---|---|---
TDS
< 2000 ppm
| Reduced production rate Increased salt passage| Contact Waterite/ Replace
water source| RSL HP
T. Hardness
< 6 grains/gal
(103 mg/l)
| Scaling of membrane surface Reduced production rate| Automatic Softener|
Fusion² series Gem series
Total Iron
< .05 ppm
| Reduced production rate Fouling of membrane surface Iron deposits in
equipment| Iron Remover (> 5 ppm) Softener (levels < 5 ppm)| FOB series
Tannins
< .5 ppm
| Reduced production rate Fouling of membrane surface| Softener with organic
scavenger resin| Gem series
Chlorine
< .1 ppm
| Permanent membrane damage Increased salt passage| Carbon Filter| Fusion² CF
series
pH
5.5 – 9.5
| Internal corrosion Lime scaling in equipment
Plumbing damage
| Replace water source Adjust pH| Call your dealer
Organic or Microbiological Activity
0
| Reduced production rate Fouling of membrane surface Sliming of pre-treatment
equipment, odour| UV Disinfection followed by 1 micron filtration Well
chlorination| Excelite UV Excelpure WellPro
Manganese
<. 05 ppm
| Reduced production rate Fouling of membrane surface| Manganese Greensand
Filter| Greensand Catalox
Hydrogen Sulphide 0| “Rotten egg” odour Internal corrosion| Iron Remover
(<1 ppm) Manganese Greensand Filter (> 1 ppm)| Greensand Catalox
Turbidity
SDI < 5.0
| Reduced production rate Plugging of membrane Rotary vane pump damage| Multimedia Filter Pre-treatment cartridges| Nextsand Excelpure
TEST THAT THE PRE-TREATMENT SYSTEM IS DELIVERING RO FEED WATER TO NECESSARY SPECIFICATIONS BEFORE PLUMBING THE RO SYSTEM ONLINE.
ALWAYS ALLOW A NEW SOFTENER INSTALLED TO PRE-TREAT AN RO SYSTEM TO START ON
THE BACKWASH/REGENERATION/RINSE CYCLE. OPERATE THE SOFTENER OFF-LINE UNTIL
WATER RUNS CLEAR BEFORE USING IT TO PROVIDE RO FEED WATER.
THIS PROCEDURE ALSO APPLIES TO NEW RESIN BED INSTALLATIONS. COLOUR THROW FROM
NEW RESIN BEDS MAY DAMAGE OR FOUL RO MEMBRANES.
WATERITE DOES NOT RECOMMEND THE USE OF A GRANULAR CARBON CARTRIDGE IN THE PRE-TREATMENT FILTER HOUSINGS SUPPLIED, FOR THE PRIMARY REDUCTION OF CHLORINE. IT WILL REQUIRE REPLACEMENT TOO OFTEN, LIMIT FLOW RATES AND LIKELY LEAD TO CHLORINE BREAKTHROUGH TO THE MEMBRANE ELEMENT. WE RECOMMEND THAT THIS HOUSING BE RESERVED FOR 5-MICRON OR 1-MICRON SEDIMENT CARTRIDGES, FOR THE REDUCTION OF SUSPENDED PARTICULATE.
Step 2.3. Plan Your Water System
Using a Pressure Storage Tank and Pressure Switch
Your RO system will produce permeate (product water) at a pressure capable of
pressurizing a bladder tank, though tank recovery time will be limited by the
production rate of the membrane(s).
Rates of maximum production water for Vectapure™ RSL systems are, (feed water
@<1000 TDS):
RSL2400| 1.6 USG/min. (6 litres/min.)| RSLHP2400| 1.4 USG/min.
(5.3 litres/min.)
---|---|---|---
RSL4800| 3.2 USG/min. (12.1 litres/min.)| RSLHP4800| 2.8 USG/min.
(10.6 litres/min.)
RSL7200| 4.8 USG/min. (18.1 litres/min.)| RSLHP7200| 4.2 USG/min.
(15.9 litres/min.)
RSL9600| 6.6 USG/min. (24.2 litres/min.)| RSLHP9600| 5.6 USG/min.
(21.2 litres/min.)
For many systems, this rate of recovery will be insufficient in periods of peak usage. It will be necessary for you to provide product water storage in a non-pressurized tank from which you may re-pressurize the water for delivery to your appliances or plumbing system.
IF THE SYSTEM IS CONNECTED DIRECTLY TO A PRESSURE TANK, MAKE SURE THAT A CHECK VALVE IS INSTALLED ON THE PRODUCT WATER LINE BETWEEN THE MACHINE OUTLET AND THE PLUMBING SYSTEM PRESSURE SWITCH, TO ELIMINATE BACKPRESSURE ON THE MEMBRANE(S). FAILURE TO DO SO WILL CAUSE PERMANENT DAMAGE TO THE RO MEMBRANE(S).
If a pressure tank and pressure switch are used for storage, be sure that the pressure switch is capable of carrying the full load amperage of the system. For reference, the motor full load amperages are.
| 230/208VAC 1 PH| | 230/208VAC 1 PH
---|---|---|---
RSL2400| 8.7/9.4 A| RSLHP2400| 15.0/16.5 A
RSL4800| 8.7/9.4 A| RSLHP4800| 15.0/16.5 A
RSL7200| 10.4/11.5 A| RSLHP7200| 15.0/16.5 A
RSL9600| 10.4/11.5 A| RSLHP9600| 15.0/16.5 A
Consult your electrician to determine the proper sized breaker for your
installation. Other motor voltages are available as a factory option. Consult
with your dealer for availability and pricing.
The pressure switch will be used to turn off the RO unit at the cut-off
pressure and turn it on at the cut-in pressure, in the same way one is used to
control a water well pump. Set the pressure switch to a maximum shut-off
pressure of 50 psi.
Using an Atmospheric Pressure (non-pressurized) Storage Tank and Float
Switch
Your VectaMaxx™ RSL RO may be wired to a float control shut-off switch that
shuts the system down when a non-pressurized storage tank is filled. Make sure
that the tank size is selected to provide adequate water storage for your peak
demand period. Keep in mind that atmospheric water storage vessels are subject
to contamination by airborne bacteria – they should include alid, be sanitized
before use and periodically disinfected. RO product water will have no
chlorine residual and will be subject to contamination at all stages in the
plumbing system. Consider UV disinfection as an inline option for all water
being pumped from the storage tank into the plumbing system. An overflow
bulkhead with a drain line should be installed in the tank above the float
switch water line, and be connected to a floor drain to protect against a
failed level control switch.
If the inlet bulkhead fitting to the non-pressurized tank is below the maximum
water level in the tank, make sure that a check valve is installed in the
product water line between the RO unit’s outlet and the tank inlet. This will
ensure that backpressure from the tank will not damage the membrane(s). To
eliminate this problem, install the bulkhead fitting above the level switch.
Consult your Waterite Commercial RO Systems Price List for information and
availability on a wide variety of water system components including storage
tanks, re-pressurization pumps, bulkheads, tube, pipe, pressure switches,
fittings, UV disinfection systems and float valves.
Installation
Your system includes:
✓ The main RO/filter assembly frame with one assembled pre-filter, booster
pump, membrane housing(s), flow controls, pressure gauges and flow meters.
✓ One, two, three or four membrane(s) (in a sealed plastic bag and one
5-micron polypropylene sediment cartridge);
✓ One sediment filter housing wrench;
✓ One Owner’s package including owner’s manual and warranty certificate.
Step 3.1. Selecting the System Location
- The filter housing will need periodic maintenance – easy access must be maintained. Do not install in a location with high humidity, direct sun or a direct source of heat. Typically, a commercial mechanical room is ideal. Never expose the RO unit to freezing temperatures.
- Use the threaded feet at the base of the RO stand to level the unit.
- The unit will need to be installed in a location that has ready access to 230/208VAC power, the feed water line, and near a drain capable of handling the waste flow from the machine.
Your RO system has been equipped with quality compression and push on fittings
throughout.
All compression fittings should be hand-tightened and then tightened ¼ turn
further with a wrench.
Check that all fittings are snug, as they may have loosened in transit. Do not
over-tighten as damage may occur to the internal gasket on the sst threaded
hose assemblies.
Completing and securing a push-on connection is simple. First, the tubing
should be cut square and any burrs or rough edges removed. Insert the tube
firmly and push until the tube end contacts the stop. Gently tug the tube
backwards to assure a secure connection. To disconnect, pull the tube while
pushing in the collet ring. Fittings may be reconnected over and over again,
if necessary.
Figure 2.
Step 3.2. Install the Feed Water Supply Connection
-
Inspect the cold water supply line and the condition of the pipe. Ensure that the supply pipe is in good overall condition and can deliver the system’s necessary feed water flow rate. See Section 8 for specified feed water flow rate requirements.
-
Turn the water supply line to your plumbing OFF.
-
Plumb a connection from the COLD water supply line, ensuring that the feed line is at least ¾” in diameter (1” for RSL 9600 and RSLHP9600). Install a shut off valve on the connection, so that the RO system can by isolated from the main water supply. Note that the inlet connection to your RO system is 1”. We recommend that you also install a pipe union near the RO to allow easy disconnection should it be required for maintenance.
-
Make sure the feed water source is a reliable one and will constantly deliver feed water between 40 psi and 60 psi maximum. Your RO system has been equipped with an emergency low pressure shut-off, if the line pressure to your RO inlet falls below 20 psi. This will keep the drive pump from running dry and damage occurring to its internal components.
The RO Controller will wait 60 seconds and try to restart the system. Should it fail to restart- the controller will try again in 60 seconds, to a maximum of 5 times in 10 minutes. If the unit has failed to continue to run then it will go into alarm and will require a power re-set.
Step 3.3. Installing the Drain Line
-
A 1/2” poly tube (minimum) should be used for the drain line. Attach the drain line to the ½” fitting on top of the Reject Flow Meter. Position the drain line over the drain and secure it in place. Do not elevate the drain line over 10 feet above the unit. If connection to a sewer line is necessary, check the local code or a plumbing professional for guidance and the required parts. Usually a trap with a 2” air gap will suffice. For systems equipped with the fast flush option a ¾” drain line should be installed.
ALWAYS MAINTAIN OR INSTALL A 2” AIR GAP ON ALL DRAIN LINES TO PREVENT SEWAGE BACK SIPHONAGE. -
DO NOT use a residential septic field for receiving the RO waste from VectaMaxx™ RSL systems. If used to capacity, these systems (depending on the model and settings) will produce between 1670 to 9820 USG (6,336 to 37,440 litres) per day of wastewater and will waterlog septic beds.
-
RSL24-9600 Only
3. Set-up of your RO system will be dependent upon the TDS of your feed water. Make sure that you specify the TDS of your feed water at the time the unit is ordered.
The system has been shipped with a Drain Line Flow Control (DLFC) that is intended for feed water of less than 1000 TDS. For TDS above 1000 please consult the parts list at end of this booklet. -
Make sure that you have the DLFC installed in your system. These orifices have been selected to operate at the correct waste flow rate for your system, at an optimum pressure of 130psi. For systems configured for <1000 TDS, the recovery rate will be a maximum of 60%. For systems configured for >1000 TDS, the recovery rate will be a maximum of 40%.
-
The DLFC (Figure 4) is mounted internally in the coupling on the lower connection of the Reject Flow Meter, and has been designed to give a constant system recovery rate at 130 psi operation pressure, @ 15 C water temperature.
-
If requiring replacement of the orifice plate, the installation is quick and simple:
-
Use Table 1 to find and order the right orifice assembly for the system.
-
DISCONNECT THE POWER TO THE SYSTEM, TURN OFF THE WATER SUPPLY AND ENSURE THE SYSTEM PRESURE HAS BEEN RELEASED.
-
Remove the assembly from the flow meter
-
Remove the locking ring from the collet and retract tubing
-
Remove the fitting attached to the Assembly by pushing the collet towards the assembly while pulling the fitting away from the assembly. (Figure a).
-
Disassemble the fitting by pulling the collet out, removing the o ring, and DLFC. (Figures b and c).
-
Insert the new DLFC so that it faces towards you. Replace the o-ring and the collet back into the fitting.
-
Re-attach the fitting to the flow meter and re-insert the tubing. Re-Install locking clips
Table 1
RSL MODEL # | Raw Water TDS | Color | Part # |
---|---|---|---|
RSL-2400 | < 1000 TDS | Lime/White | 5878301 |
> 1000 TDS | Pink | 5861041 | |
RSL4800 | < 1000 TDS | Pink | 5861041 |
> 1000 TDS | Dark Green/White | 5878321 | |
RSL7200 | < 1000 TDS | Dark Green/White | 5878321 |
> 1000 TDS | Lilac/White | 5878361 | |
RSL9600 | < 1000 TDS | Lilac/White | 5878361 |
> 1000 TDS | Grey/White | 5878351 |
Your VectaMaxx™ RSL is designed to operate at a recovery rate (percentage of product water to total water used) at maximum of 60% for feed water of <1000 TDS and 40% for feed water with TDS ranging from 1000 to 2000.
DO NOT ATTEMPT TO OPERATE THE SYSTEM AT HIGHER RECOVERY RATES, AS THIS WILL CAUSE PREMATURE MEMBRANE FAILURE OR INTERNAL SCALING AND EQUIPMENT FAILURE.
You may wish to operate your system at lower recovery rates where your dealer has identified water conditions that may stress your membrane or where recommended pre-treatment feed water conditions are not met. You may do so, though this must be accomplished by a combination of increasing the flow of concentrate to waste and reducing the recycle valve flow. This, done in
balance, will maintain the overall system pressure at previously stated normal
operating pressures.
Where your system is equipped with flow meters, simply change the DLFC to the
desired flow rate (See Step 6-Table 1) and close the recycle valve until the
pressure registers normal operating pressure. Using the formula:
% Recovery Rate = Flow rate of Permeate (Product Flow)
Flow rate of Permeate + Flow rate of Waste
Once the new balance has been established at normal operating pressure, you may wish to lock the valve in position by removing the handles by loosening the setscrews located on the valve handle.
Step 3.4. Installing the Filter Cartridge and Membrane (s)
-
Remove the filter housing by turning counter-clockwise with the housing wrench supplied. Remove all protective wrapping from the 5-micron filter cartridge. Insert the 5-micron white sediment filter in the housing and reassemble. The housing is seated with o-rings
- DO NOT OVERTIGHTEN – 1/4 turn after hand tight is usually sufficient.
Skip (2.) below if the factory has pre-loaded your membrane elements.
- DO NOT OVERTIGHTEN – 1/4 turn after hand tight is usually sufficient.
-
Remove the wrapping from the membrane element(s). Lightly lubricate the membrane brine seal and all o-rings located in the membrane housing caps with a good quality, silicone o-ring lubricant (do not use petroleum-based lubricants). Disconnect the connections on the membrane housing’s top end cap. Remove the end cap from the membrane housing by loosening the band clamp nuts and bolts. The membrane housing is mounted vertically on the system’s stand. See Figure 1. Insert the membrane element into the housing, so that the brine seal of the membrane will seat at the inlet side of the membrane housing (this is indicated by the direction of flow label on the housing). See Figure 3. Gently push and slowly twist until the membrane product adapter seats snugly inside the housing cap still in place at the bottom of the housing. Re-install the disassembled housing cap – be sure that o-rings do not roll out of their grooves, get pinched or cut. Re-install the band clamp snugly and reconnect the connections to the cap.
-
To remove the membrane from the housing, remove the top housing end cap and gently pull the membrane out of the housing body. You may need to lightly grip the membrane cage with needle-nose pliers to free it from the housing, after extended use. With each disassembly, always check the end cap o-rings and the membrane brine seal to make sure that they are in good condition and are secure in their seating grooves. While the housing is disassembled, clean all components thoroughly to remove any debris or scaling. When reassembling, make sure that that membrane element is installed with the brine seal facing in the same direction as it was previously. See direction of flow label on each membrane housing.
Step 3.5. Complete the Electrical Connection
- Connect the 14ga. 3 wire cable on the back of the control box to an approved electrical breaker or a disconnect switch.(See Step 4.4 – Figure 5 for main power location)
NOTE: Local electrical codes vary. Check with an electrician for appropriate device connection in accordance with local codes. Assure that the power source is rated to the necessary amperage (see page 8) and that the connection meets the local electrical code.
See the electrical diagram on page 20.
DO NOT START THE SYSTEM UNTIL STEP 4.5.1 IS COMPLETE.
System Controller
Step 4.1. RO Controller Set-Up
System Controller Specifications
_ _Inputs__|
---|---
Tank level switch| (1) Normally-Closed. RO runs on switch closure.
Inlet pressure switch | Normally-Open. Switch opens on low pressure.
Pre-treat lockout switch | Normally-Open. Pretreat lockout active
with switch closure.
NOTE: All switch inputs are dry contacts. Voltage applied to the switch inputs will damage the controller
Controller Power| 120/240 VAC, 60/50Hz (Range: 96-264 VAC)
The switching power supply automatically adjusts to supply voltage.Voltage
applied to the input is the same voltage the motor and valves will operate on.
_ _Relay Output Ratings__|
Feed Solenoid| 12A. Output Voltage is the same as motor/supply voltage.
Flush Solenoid| 12A. Output Voltage is the same as motor/supply voltage.
The solenoid relay ratings above reflect the capacity of the relays only.
The current capacity of each circuit is 2A.
Motor| 1.0 HP @ 120V, 2.0 HP @ 240V.
Circuit Protection|
Controller Power Fuse| F1 5x20mm 1/4(0.25)Amp Little Fuse
0218.250MXP Branch circuit protection, motor and valve protection must be
provided externally.
_ _Other__|
Dimensions| 7” tall, 5” wide, 2.375” deep. Nema 4X Polycarbonate
Enclosure.
Weight| 1.1 lb.
Environment| 0-50˚C, 10-90%RH (non-condensing)
- Flush solenoid and pre-treat lockout are optional equipment.
Step 4.2. RO Controller Interface
Standby/ON Switch
Capacitive touch switch. Tank Full LED turns Red to confirm button contact. To
use switch to switch states, hold for 1-2 seconds.
Step 4.3. RO Controller Programming
The controller has 3 separate user-selectable sets of settings for configuring
the RO. The factory default settings are shown below. The settings are
identical except for variations in the flush behavior.
Program 1, No Flush (Standard)
Program 2, High Pressure Flush (Optional)
Parameter | Value | Program 1 | Program 2 |
---|---|---|---|
Tank Level Switch delay (actuation and de- actuation) | Seconds | 2 | 2 |
Pressure Switch delay (actuation and de-actuation) | Seconds | 2 | 2 |
Pretreat Switch delay (actuation and de-actuation) | Seconds | 2 | 2 |
Pump start delay | Seconds | 10 | 10 |
--- | --- | --- | --- |
Inlet Solenoid stop delay | Seconds | 1 | 1 |
Pump start retry interval (restart delay after LP fault) | Seconds | 60 | 60 |
Low pressure fault shutdown, # of faults | Faults | 5 | 5 |
--- | --- | --- | --- |
Low pressure fault shutdown, time period to count | Minutes | 10 | 10 |
Low pressure fault shutdown, reset after shutdown | Minutes | 60 | 60 |
Low pressure timeout fault | Seconds | 60 | 60 |
Flush Behavior | No Flush | High Pressure | |
--- | --- | --- | --- |
Startup Flush: Minutes from last flush | Minutes | 0 | 0 |
Startup Flush: Duration | Seconds | 0 | 0 |
Periodic Flush: Interval | Minutes | 0 | 60 |
Periodic Flush: Duration | Seconds | 0 | 60 |
Shutdown Flush: Time from last flush | Minutes | 0 | 10 |
Shutdown Flush: Minimum operation | Minutes | 0 | 30 |
Shutdown Flush: Duration | Seconds | 0 | 60 |
Timed Manual Run | Minutes | 5 | 5 |
--- | --- | --- | --- |
Timed Manual Flush | Minutes | 0 | 5 |
Step 4.4. DIP Switch Settings
RO Program Settings
Switch 1| Switch 2| Program
ON| OFF| 1
OFF| OFF| 2
Step 4.5. Starting Up and Flushing the System
- Turn on the feed water valve to the system and check all connections for leaks. Do not proceed further until any leaks are fixed. Water will flow to the pre-treatment housings but will not pass the inlet solenoid (see Figure 3.) until the system has been started. The available line pressure should now register on the line pressure gauge. Purge any air from the pre-filter housing by depressing the red button located on top of the housing.
- Open the recycle valve to the fully open position. For RSLHP models open the Concentrate Reject valve fully open.
- Turn on system breaker/Disconnect switch. Press the ON button.
RSL units: Let the system operate for about 5 minutes with recycle valve
fully open
RSLHP units once the pump is running and all air is purged from the
system, close the reject valve until you have a flow rate of 5 gpm. Let the
system operate for about 5 minutes with recycle valve fully open.
The system is now flushing and clearing any dust or debris from the lines. There should be little or no water production from the machine during this flush.
Step 4.6 Operating Pressures
RSL Units
The RSL systems are designed to normally operate at 130 psi (140 psi for RSL
7200/9600).
At this pressure, the proper waste/production ratio is established. Begin to
close the recirculation valve slowly until the operating pressure gauge
registers 130 psi (9.1 bar) on 2400 and 4800 models, 140 psi for 7200 and 9600
models. DO NOT ALLOW THE SYSTEM TO OPERATE IN EXCESS OF 150 PSI AS MEMBRANE
AND SYSTEM DAMAGE MAY RESULT.
You may wish to lock the valves in the proper position by removing the handles
to discourage tampering.
Your system is now set up to operate at its design settings.
RSLHP Units
The RSLHP systems are designed to normally operate at 220 psi. At this
pressure, the proper waste/production ratio is established. Begin by closing
the reject valve slowly until the Reject flow is about 3 gpm. Now close the
recycle valve slowly until the pressure is at 210 psi. The nominal
reject/production flow for these models is 2/3. Adjust both valves until the
pressure is stabilized at 230 psi with a 2:3 ratio for flow. DO NOT ALLOW THE
SYSTEM TO OPERATE IN EXCESS OF 250 PSI AS MEMBRANE AND SYSTEM DAMAGE MAY
RESULT.
You may wish to lock the valves in the proper position by removing the handles
to discourage tampering.
Your system is now set up to operate at its design settings
****YOUR MEMBRANES HAVE BEEN SHIPPED WITH AN ANTI-BACTERIAL PRESERVATIVE. OPERATE THE SYSTEM FOR 1 HOUR AT DESIGN SETTINGS BEFORE BRINGING THE SYSTEM ONLINE TO ASSURE MEMBRANE HAS BEEN COMPLETELY FLUSHED. DO NOT USE WATER PRODUCED DURING THIS RUN-IN PERIOD.
System Maintenance
Changing Pre-filter Cartridges
The pre-filter cartridge should be changed, as a rule of thumb, every month,
biweekly in heavy use applications. It is critical that this be done to ensure
that pre-treatment cartridge allow necessary flow and that suspended
particulate is removed from the feed water.
To change the cartridge, turn off the system’s power and as a safety
precaution, close the water supply to the unit. Repeat Step 3:4 from the
installation instructions above. Thoroughly flush and clean the filter
housings while they are disassembled. Always use Waterite factory cartridges
as replacements.
Monitoring your System Performance
Your system will be operating at its peak performance after about 24 hours of operation. You should develop a daily log to track line pressure, system pressure, feed water TDS, permeate TDS, permeate flow rate and waste flow rate. This will allow you to see any developing performance trends or alert you to system changes that will require you to intervene. It will also be helpful for your dealer or Waterite technical personnel to have this information available to help troubleshoot your system, should it become necessary. The table provided in the last few pagesof this manual (Section 9) will help you get started.
Auto Flushing your VectaMaxx™ RSL (Optional)
For TDS above 1000ppm, it is strongly recommended that periodic fast flushing
be done to remove sediments and mineral build-ups from the membrane surface.
An Auto flush system purges high concentrates of dissolved solids out of the
system on a time basis. This helps to keep scale and fouling to a minimum.
An Auto-flush system is a factory installed option, but can be installed by a
qualified field technician. (Waterite P/N RSLAFSH)
Cleaning your Membrane Element
As your membrane begins to age, it will gradually lose some output performance. This is normal and may result in an overall permeate flow loss of 5% after about 1 year. Your membrane(s) may eventually begin to lose production due to fouling or scaling in its interior. Symptoms of this may be continuously falling production rates or elevated TDS levels in the product water. Do not attempt to operate the system above specified pressures to compensate for output loss.
Total Dissolved Solids may be measured by a professional or by use of a simple hand-held TDS monitor. These are available from your dealer.
The membrane element life will range from 1 to 5 years, depending on the
quality of the raw water. See 3.4 Figure 3 for membrane removal and
installation instructions.
If you suspect your membrane element requires cleaning or replacement, contact
Waterite or your dealer. Do not attempt to clean the element yourself, as it
requires specialized chemicals, procedures and equipment. If you remove your
membrane from the housing, make sure that you keep it wet, preferably in a
sealed plastic sleeve.
It is a good idea to always keep an extra membrane(s) on hand to avoid
system downtime when cleaning is necessary. Never allow a membrane to dry
out (if wet variety) or freeze while in storage.
A Word on your Warranty
Keep your bill of sale and your warranty certificate, included in this kit.
This is needed to claim any parts or repair service during the warranty
period. Read the document completely for warranty claim instructions.
Your VectaMaxx™ RSL system comes with a limited one-year warranty covering
materials and workmanship for one year from date of installation, subject to
user’s compliance with these maintenance and operating instructions. Membranes
are excluded by the warranty and the seller’s responsibility is limited to any
warranty carried by the manufacturer. It is the purchaser’s responsibility to
immediately notify Waterite if defects are detected. Seller shall not be
liable for any special, incidental or consequential damages and will at its
option repair or replace any defective components. Warranty excludes o-rings,
membranes, pre-filter cartridges, freight charges, labour to remove or re-
install equipment, use with feed water in excess of 2000 TDS for RSL standard
units/or in excess of 4000 ppm TDS for RSLHP units, use of feed water that
does not meet recommended conditions and with system alterations made, without
a written approval from Waterite.
Trouble Shooting Guide
Problem | Possible Cause | Solution |
---|---|---|
Low or Declining | Water supply valve closed. | Open valve. |
Permeate Production | Crimped poly product line Raw water TDS too high |
Membranes fouled.
Membrane installed upside down. Low operating pressure. Brine seal rolled out of groove.
Feed water content has changed. Membrane permeate o rings not sealing or damaged Pre-treatment cartridges plugged.
| Repair or replace tube Consult dealer – may need pre-treatment.
Clean or replace membrane. Fast flush system Install element correctly See “Low System Pressure”. Re-install membrane using lubricant. Check brine seal for damage. Review pre-treatment. Reseat membrane or replace orings Replace cartridges.
Leaking Joints| Fittings not seated. Filter housing leaking.| Disconnect
fitting and reseat tube. Tighten with housing wrench. Inspect o-rings for cuts
or crimps.
Low System Pressure| Clogged pre-filter or fouled pre-treatment. Low
feed water pressure. Inlet solenoid closed.Booster pump malfunctioning.|
Replace pre-filter cartridges.
Check feed water source for restrictions. Check solenoid circuit- replace if necessary. Call dealer.
| Malfunctioning pressure gauge.| Replace gauge.
High System Pressure| Plugged or restricted recycle valves. Crimped
product line tube. Malfunctioning pressure gauge. Membranes fouled| Clean or
replace Repair or replace Replace gauge. Clean or replace Membranes
Permeate TDS Rising| Scaled, perforated or fouled membrane(s).Pre-
treatment system failure. O-rings on product adapters| Clean or replace
membranes.
Fast flush membrane. Check feed water quality. Check and replace
| cut or damaged.| damaged o-rings.
Common Replacement Parts
Part Description | Part Number | Models |
---|---|---|
Excelpure 20” 5 Micron PP Spun Cartridge | PP20B05 | ALL |
Excelpure 20” 1 Micron PP Spun Cartridge | PP20B01 | ALL |
¾” Inlet Solenoid | ROSD220 | ALL |
Low Pressure Cut-off Switch N.O. | FRG22 | ALL |
2 ½” Pressure Gauge, 0-100 psi | LDU10025 | ALL |
2 ½” Pressure Gauge, 0-200 psi | LDU20025 | RSL |
2 ½” Pressure Gauge, 0-300 psi | LDU30025 | RSLHP |
Pre-filter Housing Wrench | HAN13W | ALL |
Recirculation Valve | IVISBFF10 | ALL |
Concentrate Reject Valve | IVISBFF8 | RSLHP |
RSL Drain Line Flow Control – DLFC (see Sec 3.3 Table 1 for sizing) | RSL | |
Product Adapter O-ring | N70210 | ALL |
Membrane Housing End Cap O-ring | N70342 | ALL |
Pre-Filter Housing O-ring | RKE0013HLB | ALL |
Black Max 4040 Membrane, TFC, XLP | BME4040SXL | RSL |
Black Max 4040 Membrane, TFC, S | BME4040S | RSLHP |
Feed Water Flow Requirements
RSL2400:
RSL4800:
| 4.0 USGPM minimum 8.0 USGPM minimum| includes 20% safety factor
---|---|---
RSL7200: RSL9600:| 12.0 USGPM minimum 16.0 USGPM minimum| on 1000 TDS
feed water.
RSLHP2400 RSLHP4800| 3.1 USGPM minimum 6.2 USGPM minimum| includes 20%
safety factor
RSLHP7200 RSLHP9600| 9.3 USGPM minimum 12.4 USGPM minimum| on 3000 TDS
feed water.
Installations that have purchased the flush option require a flow of a minimum 10 gpm at 30 psl
VectaMaxx RSL Performance Log
Date| Line| System| Permeate| Feed Water| Pre-
Filter| Fast| Permeate| Waste
---|---|---|---|---|---|---|---|---
| Pressure| Pressure| TDS| TDS| Change| Flush|
Flow Meter| Flow Meter
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
| | | | | | | |
VectaMaxx RSL Electrical Wiring Diagram
Pump Motor | RSL2400 | RSL4800 | RSL7200 | RSL9600 |
---|
1HP
230VAC
| 1HP
230VAC
| 1.5HP
230VAC
| 1.5HP
230VAC
1PH 6.4A| 1PH 6.4A| 1ph 8.6A| 1ph 8.6A
Pump Motor| RSLHP2400| RSLHP4800| RSLHP7200|
RSLHP9600
2 HP
230VAC
| **** 2 HP
230VAC
| 2 HP
230VAC
| 2 HP
230VAC
1ph 10.4A| 1ph 10.4A| 1ph 10.4A| 1ph 10.4A
Motor Service factor all units: Amps x 1.30
ALL RSL AND RSLHP UNITS ARE WIRED 230/208VAC 1 PH 60HZ, UNLESS OTHERWISE
SPECIFIED
Customer Support
www.waterite.com
Waterite, Inc.
■ Winnipeg, MB Canada
https://manual-hub.com/
WATERITE, INC.
Winnipeg, Manitoba
Canada
204.786.1604
fax: 204.7863.1599
www.waterite.com
Documents / Resources
|
Waterite VERSION III Advanced Reverse Osmosis
System
[pdf] Instruction Manual
VERSION III Advanced Reverse Osmosis System, VERSION III, Advanced Reverse
Osmosis System, Reverse Osmosis System, Osmosis System, System
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>