Lumin Smart LSP Gen 7.0 Smart Panel Instruction Manual
- June 16, 2024
- Lumin Smart
Table of Contents
LSP Gen 7.0 Smart Panel
Product Information: Lumin Smart Panel
Specifications:
-
Product Name: Lumin Smart Panel (LSP)
-
Model Number: LS-100374 Rev. 9
-
Function: Extends the capability of an existing circuit breaker
panel by providing measurement and remote control of up to twelve
(12) circuits in a home or building -
Data Transmission: Securely and safely transmits real-time
consumption information to the cloud via Ethernet connection
(preferred) or customer Wi-Fi -
Access: Can be accessed through the Lumin mobile app or the
web-based Lumin dashboard (app.luminsmart.com)
Introduction:
Welcome! The Lumin Smart Panel (LSP) is a standalone product
that extends the capability of an existing circuit breaker panel
(or electrical panel) by providing measurement and remote control
of up to twelve (12) circuits in a home or building. The LSP does
not impact the function of the circuit breaker panel itself. It
securely and safely transmits real-time consumption information to
the cloud via Ethernet connection (preferred) or customer
Wi-Fi.
Data and system controls can be accessed via the Lumin mobile
app or the web-based Lumin dashboard. The Lumin app allows
customers to monitor their energy consumption, track energy costs,
and control or automate their energy use remotely.
Before using the Lumin Smart Panel, it needs to be fully
commissioned. The installer is responsible for both the physical
installation and the online setup/commissioning process. Refer to
page 32 of the manual for the setup process. Installers should
complete Lumin Certified Installer Training before installing the
product.
If you need assistance with installation, please contact Lumin
support by email at support@luminsmart.com or by phone at
1-888-421-0616 (North America).
Read Before Use:
NOTE: The LSP Circuit Label & CT Table
(provided with the LSP) must be completed and delivered to the
home/building owner upon the successful installation of the LSP. A
completed LSP Circuit Label & CT Table is required to complete
LSP setup.
Warnings:
LSP installation and servicing involve dangerous voltages that
can cause injury or death. In addition to specific instructions
accompanied by the symbol throughout this booklet and product
labeling, observe the following safety precautions:
-
* Use a whole-house surge protector to prevent product damage due
to lightning strike
System Design Considerations:
Installation:
To install the Lumin Smart Panel, follow these steps:
-
Ensure you have completed the necessary training and
certification as a Lumin Certified Installer. -
Choose a suitable location for the LSP installation near the
existing circuit breaker panel. -
Turn off the power supply to the circuit breaker panel.
-
Mount the LSP securely on the wall or other suitable surface
using the provided mounting bracket and screws. -
Connect the LSP to the existing circuit breaker panel using
appropriate electrical wiring. -
If using an Ethernet connection, connect the LSP to the
Ethernet network using an Ethernet cable. -
If using Wi-Fi, connect the LSP to the customer Wi-Fi network
following the provided instructions. -
Turn on the power supply to the circuit breaker panel.
-
Verify the proper functioning of the Lumin Smart Panel by
checking the LED indicators and ensuring data transmission to the
cloud. -
Complete the LSP setup process as described on page 32 of the
manual.
Frequently Asked Questions (FAQ):
Q: How many circuits can the Lumin Smart Panel control?
A: The Lumin Smart Panel can control up to twelve (12) circuits
in a home or building.
Q: How can I access the data and system controls of the Lumin
Smart Panel?
A: You can access the data and system controls through the Lumin
mobile app or the web-based Lumin dashboard
(app.luminsmart.com).
Q: What should I do if I encounter hazardous voltages during
installation or servicing?
A: Follow the safety precautions mentioned in the manual and
seek professional assistance if needed. Ensure you are a certified
installer and have completed the necessary training.
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
WWW.LUMINSMART.COM
LS-100374 Rev. 9
U.S. Patent No. 10,109,987 U.S. Patent No. 10,467,712 Canadian Patent No. 3,050,702 U.S. and International Patent Applications Pending. ® U.S. Registered Trademark. Copyright © 2022 Coulomb, Inc. (DBA Lumin). All rights reserved.
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
TABLE OF CONTENTS
INTRODUCTION……………………………………………………………………………………………………………………………….. 1 READ BEFORE
USE …………………………………………………………………………………………………………………………… 2
Warnings ……………………………………………………………………………………………………………………………………. 2 SYSTEM DESIGN
CONSIDERATIONS ………………………………………………………………………………………………….. 3 INSTALLATION
…………………………………………………………………………………………………………………………………. 4
Items in the Box………………………………………………………………………………………………………………………….. 4 Required
Materials (Not Included) ……………………………………………………………………………………………….. 5 Required
Tools ……………………………………………………………………………………………………………………………. 6 Hardware Installation
Overview…………………………………………………………………………………………………… 7 Hardware Installation Steps
………………………………………………………………………………………………………… 8 Configuration and Account Setup
………………………………………………………………………………………………. 32 TROUBLESHOOTING AND REPAIRS
…………………………………………………………………………………………………. 33 End User
…………………………………………………………………………………………………………………………………… 33 Qualified Installer
……………………………………………………………………………………………………………………… 33 OPERATIONAL INFORMATION
………………………………………………………………………………………………………… 34 PRODUCT SPECIFICATIONS
…………………………………………………………………………………………………………….. 35 LIMITED WARRANTY FOR LUMIN
SMART PANEL………………………………………………………………………………. 36 RADIO FREQUENCY STATEMENT
…………………………………………………………………………………………………….. 37
This page intentionally left blank
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
INTRODUCTION
Welcome! The Lumin Smart Panel (LSP) is a standalone product that extends the
capability of an existing circuit breaker panel (or “electrical panel”) by
providing measurement and remote control of up to twelve (12) circuits in a
home or building. The function of the circuit breaker panel remains the same
and is not impacted. The LSP securely and safely transmits real-time
consumption information to the cloud via Ethernet connection (preferred) or
customer Wi-Fi.
Data and system controls can be accessed via the Lumin mobile app or the web-
based Lumin dashboard (app.luminsmart.com). The Lumin app gives customers
insights into their energy consumption and energy costs, as well as providing
the user with the ability to control or automate their energy use remotely.
NOTE: A Lumin Smart Panel will not function as designed until it is fully
commissioned. It is generally the responsibility of the installer to perform
both the physical installation and the online setup/commissioning process.
Refer to pg. 32 to begin the setup process. All personnel installing this
product should complete Lumin Certified Installer Training prior to
installation. Scan below to register for training.
Need help? For installation assistance please contact Lumin by e-mail at
support@luminsmart.com or by phone at
1-888-421-0616 (North America).
DANGER: HAZARDOUS VOLTAGES PRESENT DURING INSTALLATION AND SERVICING.
PRECAUTIONS AND QUALIFICATIONS REQUIRED. REFER TO THE FOLLOWING PAGE.
DANGER: TENSIONS DANGEREUSES PRÉSENTES LORS L’INSTALLATION ET L’ENTRETIEN.
PRÉCAUTIONS ET QUALIFICATIONS REQUISES. REPORTEZ-VOUS À LA PAGE SUIVANTE.
1
READ BEFORE USE
The LSP is compatible with both flush-mounted (i.e., set within drywall)
existing electrical panels and surface-mounted electrical panels. Please
determine which electrical panel type the LSP will be connecting to and follow
the corresponding installation steps outlined in this manual. Devices with
LSP-12-IR and TPU-IR model numbers must be installed indoors. Please review
the product’s technical ratings and specifications (pg. 35) to confirm it is
suitable for your application prior to installation.
NOTE: The LSP Circuit Label & CT Table (provided with the LSP) must be
completed and delivered to the home/building owner upon the successful
installation of the LSP. A completed LSP Circuit Label & CT Table is required
in order to complete LSP setup.
Warnings
LSP installation and servicing involves dangerous voltages that can cause
injury or death. In addition to specific instructions accompanied by the
symbol throughout this booklet and product labeling, observe the following
safety precautions:
· Installation and servicing must be conducted by a qualified professional,
according to local and national electrical codes
· Lumin Certified Installer training is required for installation and
servicing · Review entire manual before starting the installation or servicing
· Personal protective equipment should be worn when installing or servicing
the product · Do not install or operate the LSP other than intended or outside
the conditions specified on pg. 35 · Do not open, attempt to access, or touch
any internal product parts — dangerous voltages would
be exposed even if main service feed is disconnected · Do not use the product
if it is damaged or appears to be damaged · Use only the wires and cables
supplied with the product · Power relays are evaluated for 100,000 cycles at a
1.5 HP inductive load (e.g., motors) — larger
loads of this type may result in premature relay failure · The product
warranty does not cover damage due to lightning. Lumin recommends the
installation
of a whole-house surge protector to prevent product damage due to lightning
strike
2
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
SYSTEM DESIGN CONSIDERATIONS
· The LSP should be mounted so that the connected electrical panel is within
reach of the LSP’s flexible conduit nipple. Depending on orientation, the
nipple extends between 7″ and 17″ beyond the edge of the LSP enclosure. Ensure
that the load center has adequate wiring space for LSP conductors and
connections. Suitable junction boxes and conduit may be used to route and/or
extend LSP conductors if needed. For voltage drop calculations, assume LSP
conductors add 15 one-way-feet to the circuit.
· An LSP requires an always-on internet connection, either via Ethernet
(preferred if available) or 2.4 GHz Wi-Fi.
· When used for energy management, the LSP will be most effective when used to
shed heavy discretionary loads. These are loads greater than 15 amps that may
be desired during grid outages or other energy-constrained situations. Lumin
can shed such loads automatically while permitting a user to manually re-
enable them at their discretion. More information about circuit selection is
provided in the required Lumin Certified Installer Training. In order to shed
discretionary loads in response to grid conditions, a connection to non-
backed-up utility grid power is required for the LSP grid detection circuit.
See pg. 28. This will require wiring beyond the LSP’s connected electrical
panel.
· The LSP does not replace the need for standard circuit breakers. Lumin does
not provide overcurrent protection, ground fault protection, arc fault
detection, or other safety functionality that circuit breakers provide.
· The LSP uses current transformers (CTs) to measure overall power flows.
Correct placement of these CTs may require wiring beyond the LSP’s connected
electrical panel/s. See pg. 23.
· If the LSP is configured to automatically shed loads exceeding backup
capacity following a grid outage, a Temporary Power Unit (TPU) accessory
device may be required if the transfer to backup power takes more than 70 ms.
Without the TPU, the LSP could lose power before backup transfer completes,
and circuit disconnection would be delayed until after the LSP powers on with
the backup source. If unsure about transfer times, contact Lumin to determine
if a given system requires a TPU. The TPU is surface-mounted near the LSP and
connected with an included cable.
Need help? For system design and installation assistance please contact Lumin
by e-mail at support@luminsmart.com or by phone at
1-888-421-0616 (North America).
3
INSTALLATION
Items in the Box
1 LSP with Conduit, Conduit Bushings & Wire Whips Attached
2 Mounting Brackets (Surface-mounted installation)
1 Pair of 200A Current Transformers (A second pair is optional)
1 Temporary Power Unit (TPU) & LSPTPU Connection Cable
(Optional equipment; see pg. 3)
NOTE: Additional items include an antenna, installation hardware, Lumin Identifier Sticker Sheet, and an LSP Circuit Label & CT Table.
4
Required Materials (Not Included)
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
Wire splice connectors
Pen or marker
Supply-side/line-side tap (Optional)
Cable ties (Optional)
Electrical tape (Optional)
Dual-pole breaker: 15 to 20 amps (Optional)
NOTE: Additional supplies may be required depending on the existing electrical panel installation. A NON-GFCI dual-pole breaker of 15 to 20 amps may be required to power the LSP. Appropriately rated, NON-GFCI breakers may be double-tapped depending on local electrical codes. See pg. 17 for more details. A supply-side connection (line-side tap) and/or wire extension may be required for the LSP’s Grid Detection Circuit (see pg. 28). Specific wire extension supplies may be required for current transformers (see pg. 26).
5
Required Tools
Drill
Utility knife
2″ Knockout punch (2-3/8″ hole size)
Drywall saw (optional)
Tape measure
Wire stripper
Pliers
Stud-finder (optional)
Fish tape (optional)
Phillips screwdriver
Flathead screwdriver
Level (optional)
NOTE: A multimeter may be required for determining current transformer placement (see pg. 25).
6
Hardware Installation Overview
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 1. Turn Off Main Feed and Remove Electrical Panel Cover
STEP 2. (Flush-Mount Only) Cut and Remove Drywall
STEP 3. Knock Out or Punch One Hole for 2″ Conduit Fitting
STEP 4. Measure and Mark Hole Locations for Mounting
STEP 5. (Surface-mount Only) Secure Mounting Brackets to Wall
STEP 6. Attach LSP Antenna and Guide LSP Wire Whip into Electrical Panel
STEP 7. Secure LSP to Wall/Bracket and Electrical Panel
STEP 8. Connect LSP Equipment Grounding Conductor (EGC) to Ground Bar
STEP 9. Identify A-Row and B-Row Breakers
STEP 10. Connect LSP Power Circuit and Label Breaker
STEP 11. Select Circuit Breaker to Connect to LSP, Turn Off, and Disconnect
Load
STEP 12. Connect One LSP Wire Labeled “Line # Breaker” to Circuit Breaker
STEP 13. Connect Corresponding LSP Wire Labeled “Line # Load” to Load and Turn
Circuit Breaker Back On
STEP 14. Record Circuit Label/Name and Breaker Row (A/B) With Corresponding
LSP Wire Number
STEP 15. Repeat Steps 11-14 Until All LSP Line # Wires Are Connected
STEP 16. Determine Placement of Current Transformers (CTs)
STEP 17. Phase Conductors Monitored by Current Transformers
STEP 18. Testing for Crossover before Current Transformer Placement
STEP 19. Connecting Current Transformers
STEP 20. Record Line Name(s) of Corresponding Current Transformers
STEP 21. Connect the LSP’s Grid Detection Circuit (GDC) Wires to the Grid Side
of an Automatic Transfer Switch (ATS) or Microgrid Interconnect Device (MID)
STEP 22. Connect TPU to LSP (Optional)
STEP 23. Replace Electrical Panel Cover and Turn On Main Feed
STEP 24. Circuit Labeling (Optional)
7
Hardware Installation Steps STEP 1. Turn Off Main Feed and Remove Electrical
Panel Cover
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Screwdriver
8
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 2. (Flush-Mount Only) Cut and Remove Drywall
Drywall Cutout Option A
Drywall Cutout Option B
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. ENSURE CUTTING PATH IS FREE
OF ELECTRICAL CONDUCTORS. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE
DISJONCTEUR PRINCIPAL EST ÉTEINT. ASSUREZ-VOUS QUE LE CHEMIN DE COUPE EST
EXEMPT DE CONDUCTEURS ÉLECTRIQUES.
Tools: Tape measure, level (optional), stud finder (optional), and drywall saw
or suitable alternative
NOTE: Cut and remove enough wall material to accommodate the LSP’s wire whips.
Consider drywall cutout “Option B” if additional space is required to
accommodate the LSP’s wire whips and properly access the electrical panel for
Step 3.
9
STEP 3. Knock Out or Punch One Hole for 2″ Conduit Fitting
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Screwdriver, pliers, drill (optional), and knockout punch (optional)
NOTE: Hole location in electrical panel may vary depending on spacing
constraints. The installer should choose a location that avoids existing
obstructions and provides adequate clearance for routing of the LSP wire
whips. The hole location can be below as shown, above, or to either side of
the electrical panel as appropriate. Use of existing pre-stamped 2″ knockouts
are acceptable provided there is sufficient clearance. Otherwise, a 2″
knockout punch (2-3/8″ hole) will be required to attach the LSP conduit.
10
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 4. Measure and Mark Hole Locations for Mounting
TPU Mount (Optional)
TPU Mount (Optional)
Surface-mounted installation
Flush-mounted installation
Tools: Tape measure, marker, stud-finder (optional), and level (optional)
NOTE: Mark the applicable hole locations for the installation type (flush- mount vs. surface-mount with mounting brackets). Exact hole locations may vary depending on existing conditions. Qty 4 holes are required for the LSP. Qty 2 additional holes are required if the optional TPU was purchased (see pg. 3).
NOTE: Alternative Installation Method: Installers may find it easier to route the wire whip into the electrical panel and attach the conduit to the electrical panel before determining the mounting hole locations. See Steps 6 and 7 for more details.
11
STEP 5. (Surface-mount Only) Secure Mounting Brackets to Wall
Tools: Drill, stud-finder (optional), screws (x4), and washers (x4) NOTE:
Ensure all screws are securely threaded into studs or suitable anchor systems.
12
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 6. Attach LSP Antenna and Guide LSP Wire Whip into Electrical Panel
Conduit Bushing
Conduit Bushing
Attach Antenna
Attach Antenna
Surface-mounted installation
Flush-mounted installation
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
NOTE: Attach the antenna provided with the LSP and then guide the wire whip
through the hole in the electrical panel. Remove the conduit bushing before
guiding the wire whip through the hole.
13
STEP 7. Secure LSP to Wall/Bracket and Electrical Panel
Conduit Bushing
TPU (Optional)
Conduit Bushing
TPU (Optional)
Surface-mounted installation
Flush-mounted installation
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Tools: LSP: Drill, screws (x4), washers (x4), and nuts (x4; surface-mount only) TPU: Drill and screws (x2) (optional)
NOTE: Lift the LSP to align with the mounting holes and secure it directly to the wall (flush-mount installation — ensure all screws are securely threaded into studs or suitable anchor systems) or mounting brackets (surface-mount installation) utilizing the hardware provided. Secure the LSP to the electrical panel with the 2″ conduit bushing provided. For the optional TPU (see pg. 3), align with the mounting holes and secure it directly to the wall (ensuring both screws are securely threaded into studs or suitable anchor systems) utilizing the hardware provided.
14
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 8. Connect LSP Equipment Grounding Conductor (EGC) to Ground Bar
EGC to Ground Bar
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. GROUND WIRE MUST BE INSTALLED FOR SAFETY. AVERTISSEMENT: HAUTE
TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES CONDUCTEURS
DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. UN FIL DE TERRE DOIT ÊTRE
INSTALLÉ POUR LA SÉCURITÉ.
Tools: Screwdriver and pliers (optional) NOTE: Connect the EGC (bare copper
wire) from the LSP to the existing ground bar in the electrical panel (exact
location of ground bar may vary).
15
STEP 9. Identify A-Row and B-Row Breakers
A B A B A B
NOTE: For purposes of Lumin installation, the top row of breakers will always
be classified as “A”. The second row of standard breakers will be “B”. The
alternating A-B-A-B pattern continues down the rows of breakers. Exception:
All breaker rows are designated “A” in panels with two-wire single-phase power
rather than three-wire single-phase (split phase). NOTE: If the load center
contains tandem or “skinny” breakers, there will be two breakers in a standard
breaker space. Thus, the top-to-bottom breaker panel will be A-A-B-B-A-A-B-B.
16
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 10. Connect LSP Power Circuit and Label Breaker
“Line A” (Black) to A-Row Breaker
“Neutral” (White)
“Line B” (Red)
to B-Row Breaker
A
B
A
B
A
B
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Screwdriver, pliers, and wire stripper
NOTE: Connect the LSP wires as pictured to the existing neutral bar and a
double-pole 15- to 20-amp breaker, landing Line A on an A-row breaker terminal
and Line B on a B-row breaker terminal. Exception: Use a single-pole breaker
for “Line A” and securely cap “Line B” in panels with two-wire single-phase
power rather than three-wire single-phase (split phase). Mark the breaker with
a clearly identifying label (ex. “Lumin Smart Panel Power”). DO NOT CONNECT
THESE CONDUCTORS TO GFCI BREAKERS. Do not double-tap breakers unless they are
appropriately rated.
17
STEP 11. Select Circuit Breaker to Connect to LSP, Turn Off, and Disconnect Load
Turn Off Circuit
Disconnect Load Wire
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Screwdriver NOTE: Breaker labels should be marked to indicate that the
load connects to the LSP. In typical applications, do not connect breakers
that power the router(s)/modem(s) that provide the LSP internet connection.
18
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 12. Connect One LSP Wire Labeled “Line # Breaker” to Circuit Breaker
“Line # Breaker”
Load Wire
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Screwdriver and wire stripper NOTE: All LSP wires labeled “Line #
Breaker” must connect to a breaker or be safely terminated with a wire
connector/cap. Lines 1-6 (6 AWG wire) can connect to circuit breakers rated up
to 60 amps and lines 7-12 (10 AWG wire) can connect to circuit breakers rated
up to 30 amps (see pg. 35).
19
STEP 13. Connect Corresponding LSP Wire Labeled “Line # Load” to Load and Turn
Circuit Breaker Back On
Load Wire
“Line # Load”
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Wire stripper and wire splice connector NOTE: All LSP wires labeled
“Line # Load” must connect to a load wire via a wire splice connector
(ensuring a tight connection) or be safely terminated with a Wire Connector.
The LSP wire line number must match the line number used in the previous step
(ex. “Line 3 Breaker” connects to a breaker and “Line 3 Load” connects to that
breaker’s load).
20
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 14. Record Circuit Label/Name and Breaker Row (A/B) With Corresponding
LSP Wire Number
Refrigerator
Single-pole circuit
Range
Double-pole circuit
Range
NOTE: Record the circuit label/name and breaker row (A or B) with the
corresponding LSP line number in the LSP Circuit Label & CT Table provided
with the LSP (ex. record “Refrigerator” next to LSP Line 1 and circle Breaker
Row “B” if the circuit labeled “Refrigerator” is connected to a B-row breaker
and is connected to LSP Line 1). Double-pole circuit breakers will require two
LSP wiresets, and thus two LSP line numbers.
21
STEP 15. Repeat Steps 11-14 Until All LSP Line # Wires Are Connected
x 12
WARNING: HIGH VOLTAGE. AVERTISSEMENT: HAUTE TENSION.
Tools: Screwdriver, wire stripper, and wire splice connectors NOTE: All LSP
wires labeled “Breaker” must connect to a breaker. Lines 1-6 (6 AWG wire) can
connect to circuit breakers rated up to 60 amps and lines 7-12 (10 AWG wire)
can connect to circuit breakers rated up to 30 amps (see pg. 35). NOTE: The
LSP can connect to up to 12 single-pole (or six double-pole) circuit breakers.
Each hot leg of a double-pole circuit must be connected to its own numbered
Lumin wireset (ex. LSP controls a clothes dryer. Dryer Leg “A” is connected to
LSP Line 3. Dryer Leg “B” is connected to LSP Line 4).
22
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 16. Determine Placement of Current Transformers (CTs)
DO NOT INSTALL CTS UNTIL PROPER LOCATION AND PHASING HAVE BEEN DETERMINED.
Each LSP is supplied with one set of two (2) 200-amp current transformers
(CTs). The LSP is equipped with leads for these main CTs as well as leads for
an optional set of auxiliary CTs which is available for purchase from Lumin.
Most LSP installations do not utilize auxiliary CTs and use the main CTs to
measure the total consumption of the electrical panel(s) backed up by a
battery. In this typical installation, the CTs are placed on the feeders from
the Microgrid Interconnect Device (MID) or Automatic Transfer Switch (ATS) to
the electrical panel, as shown in Figure A.
If your installation is configured differently than shown in Figure A or if
your installation will utilize auxiliary CTs, consult the Lumin CT
configuration guide for CT placement information.
Figure A Typical CT Configuration
23
STEP 17. Phase Conductors Monitored by Current Transformers
REMINDER: For the purpose of a Lumin installation, the top* row of breakers in
an electrical panel is always designated “A”. Whichever feeder leg supplies
breaker Row A will be designated “A.”
NOTE: Lumin CTs are designated either “A” or “B”. Placing them on the
incorrect leg of a circuit will result in erroneous consumption data.
If the panel is a main-lug-only type as shown in Figure B (no main circuit
breaker) then the feeder on the left will be Lumin Leg “A”. If the panel
includes a main circuit breaker, note that the main breaker may contain
crossover busing, with the result that the feeder on the left feeds the
rightside bus bar and the feeder on the right feeds the leftside bus bar. To
identify A/B feeders when a main breaker is present, consult the following
page.
Figure B Typical Main-Lug-Only Electrical Panel Busing
- All descriptions assume a top-fed electrical panel.
24
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 18. Testing for Crossover before Current Transformer Placement
To determine A and B feeders when a main circuit breaker is present, test for AC voltage between the left lug and the left bus bar*. If the bus bar is not accessible, test between the left lug and the terminal on the top left circuit breaker. See Figure C.
Left Lug
If V between these points 240, the main breaker is a crossover type. Place CT – A on the right and CT – B on the left.
Left Bus
If V between these points 0, the main breaker is a standard type. Place CT – A on the left and CT – B on the right.
WARNING: HIGH VOLTAGE. AVERTISSEMENT: HAUTE TENSION.
Tools: Multimeter
- All descriptions assume a top-fed electrical panel.
Figure C Typical Main Breaker Electrical Panel
25
STEP 19. Connecting Current Transformers
Prior to installation, measure the CT leads’ routing path(s) in the electrical
panel. If the provided leads are not long enough, fashion CT wire extensions
in the field. Refer to the following documentation for proper extension
procedures:
When installing CTs, connect CTs labeled “Line A/B CT” to the 2-pin connector
on the corresponding LSP lead first. Then clamp the CT around the
corresponding feeder leg as determined in the previous steps. The CT marked
with “A” should attach to Leg A and the CT marked with “B” should attach to
Leg B. Ensure the sticker on the CT reading “This side toward grid” is facing
toward the grid/utility meter.
WARNING: HIGH VOLTAGE. MAIN SERVICE LINES ARE ALWAYS LIVE. AVERTISSEMENT:
HAUTE TENSION. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION. CAUTION: A CT SHOULD NEVER BE LEFT CLAMPED ON A CONDUCTOR WHEN THE CT
WIRING IS DISCONNECTED. SATURATION AND DESTRUCTION OF THE CT CORE MAY RESULT.
CONNECT CT WIRING BEFORE CLAMPING. UNCLAMP BEFORE DISCONNECTING CT WIRING.
ATTENTION: UN TRANSFORMATEUR DE COURANT NE DOIT JAMAIS ÊTRE LAISSÉ SERRÉ SUR
UN CONDUCTEUR LORSQUE LES FILS DU TRANSFORMATEUR DE COURANT SONT DÉCONNECTES.
LA SATURATION ET LA DESTRUCTION DU NOYAU PEUVENT EN RÉSULTER. CONNECTER LES
CÂBLES DU TRANSFORMATEUR DE COURANT AU LSP AVANT L’INSTALLATION. DÉSINSTALLEZ
LE TRANSFORMATEUR DE COURANT AVANT DE DÉBRANCHER SON CÂBLE. 26
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 20. Record Line Name(s) of Corresponding Current Transformers
LSP LINE
BREAKER ROW (circle one)
A 1
B
CIRCUIT BREAKER LABEL/NAME
LSP LINE
BREAKER ROW (circle one)
A 7
B
CIRCUIT BREAKER LABEL/NAME
A 2
B
A 8
B
A 3
B
A 9
B
A 4
B
A 10
B
A 5
B
A 11
B
A 6
B
Line A/B CTs
CURRENT TRANSFORMER (CT)
Ex. Main Service Lines
A 12
B
Aux. A/B CTs (Optional)
CURRENT TRANSFORMER (CT)
Ex. Solar Output
NOTE: Record the line name of the corresponding attached CTs in the LSP Circuit Label & CT Table. For example, record “Main Service Lines” next to “Line A/B CTs” if the CTs were attached to main feeders.
27
STEP 21. Connect the LSP’s Grid Detection Circuit (GDC) Wires to the Grid Side of an Automatic Transfer Switch (ATS) or Microgrid Interconnect Device (MID)
“Grid Neutral” (White)
Connect black wire to a portion of the electrical system that will lose power
in a grid outage
“Grid Line” (black)
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Wire stripper and wire splice connectors NOTE: The GDC monitors the
presence of grid voltage. The GDC must be installed so that it is not backed
up by storage. Land the “Grid Neutral” wire at the most upstream neutral bar
or terminal possible. Extend the “Grid Line” wire via suitable wire splice
connector and land it on non-backed-up circuit breaker or perform a supply-
side connection (or “line-side tap”) on a wire that will lose power in a grid
outage. The 12 AWG wires in this circuit must have overcurrent protection per
local code.
28
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
STEP 22. Connect TPU to LSP (Optional)
Tools: Cable ties (optional) NOTE: Connect the TPU to the LSP using the LSP-
TPU Connection Cable provided in the TPU kit. Plug the male connector into the
TPU and then connect the female connector to the LSP. Tighten the retaining
collar on each connector to secure in place. Optional: Coil excess cable and
secure with cable ties. After completing the remainder of the installation
process, wait until the indicator on the TPU labeled “Charged” is lit before
testing system functionality. Charging time is approximately 10 minutes.
29
STEP 23. Replace Electrical Panel Cover and Turn On Main Feed
Surface-mounted installation
Flush-mounted installation
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE
ALWAYS LIVE. AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR
PRINCIPAL EST ÉTEINT. LES CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS
TENSION.
Tools: Screwdriver
NOTE: Please make any necessary drywall repairs (if applicable) and clean up
the area around the circuit breaker panel once the LSP installation is
completed. Make sure the LSP’s antenna is securely attached prior to powering
on the device.
30
STEP 24. Circuit Labeling (Optional)
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
Surface-mounted installation
Flush-mounted installation
WARNING: ELECTRICAL CODES MAY REQUIRE ADDITIONAL LABELING. AVERTISSEMENT: LES
CODES ELECTRIQUES PEUVENT NECESSITER UN ETIQUETAGE SUPPLEMENTAIRE.
Tools: Screwdriver
NOTE: Electrical codes (depending on the installation location) may require
additional labeling for energy management systems such as the LSP. The
provided installation materials include labels to identify the LSP-managed
circuits in the electrical panel, LSP electrical conduit/raceway, and
informational QR code labels.
31
Configuration and Account Setup
1. After completing the hardware installation, flip the LSP power switch to
the “on” position (“I”). The blue and green indicator lights will begin
blinking in unison, indicating that the LSP is ready for commissioning.
2. If feasible, make an Ethernet connection between the Lumin Smart Panel’s
Ethernet port and a LAN port on the location’s router. This Ethernet
connection is more reliable than a Wi-Fi connection and is not affected by
replacing the router or resetting the Wi-Fi network password.
3. Download the Lumin mobile app. In the Apple App Store or Google Play
Store, search for “Lumin Smart”.
4. Log in with an existing account or create a new account. 5. Expand the
menu (upper left of screen) and select “Set up a new Lumin Smart Panel”. 6.
Follow the in-app instructions to set up your Lumin Smart Panel (completed LSP
Circuit Label &
CT Table required). Invite users to grant access to the commissioned LSP.
Need help? For account setup assistance or troubleshooting, please call
1-888-421-0616 (North America) or
e-mail support@luminsmart.com.
32
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
TROUBLESHOOTING AND REPAIRS
End User
If the LSP is not functioning as expected, ensure that the power switch is on,
Internet service is available, antenna/ethernet connection is secure, and
breakers are switched on. See Operational Information (pg. 34) on how to read
the LSP indicators for internet connectively status. It is best to obtain
assistance from a qualified installer for further troubleshooting of hardware
issues. The installer’s familiarity with Lumin products and ability to perform
electrical work will help resolve issues effectively. Alternatively, contact
Lumin directly for assistance.
Qualified Installer
Observe all safety precautions listed on page 2. Never use the LSP to de-
energize circuits to perform electrical work. The LSP is not designed for
safety disconnecting means; lock-out/tag-out is not possible. Additionally,
when not properly connected, the app may incorrectly indicate that a circuit
is de-energized, so always assume that the LSP circuits are enabled, and
conductors are live. Ensure that the power switch is on, Internet service is
available, antenna/ethernet connection is secure, and breakers are switched
on. Inspect the system for installation and wiring faults (e.g., loose wire
connections). If the issue is not resolved, contact Lumin.
Lumin Certified Installer training is required before Lumin will authorize
work on an existing LSP. Casespecific authorization and instruction will be
provided by Lumin if applicable. Do not open cover or attempt repairs
otherwise — even with the LSP power switch and main feed breakers off, the
Grid Detection Circuit (GDC) is connected to hazardous voltages. The LSP power
switch does not deenergize the internal product components. Fuses: LSP Power
non-replaceable 2.5 A; GDC 1 A, slow blow; TPU 5 A, slow blow.
DANGER: HAZARDOUS VOLTAGES PRESENT DURING INSTALLATION AND SERVICING. DO NOT
OPEN LSP COVER, INSPECT INSTALLATION WIRING, OR ATTEMPT REPAIRS WITHOUT
REQUIRED
QUALIFICATIONS AND LUMIN AUTHORIZATON. ALWAYS DISCONNECT ELECTRICAL SUPPLY
BEFORE PERFORMING REPAIRS.
DANGER: TENSIONS DANGEREUSES PRÉSENTES LORS L’INSTALLATION ET L’ENTRETIEN. NE
PAS OUVRIR LE COUVERCLE DU LSP, INSPECTER LE CÂBLAGE D’INSTALLATION OU ESSAYER
DE RÉPARER SANS
QUALIFICATIONS REQUISES ET AUTORISATION DE LUMIN. TOUJOURS DÉBRANCHER
L’ALIMENTATION ÉLECTRIQUE AVANT D’EFFECTUER DES RÉPARATIONS.
33
OPERATIONAL INFORMATION
LED Indicator Green
Blue
Off Lumin Server Disconnected
No Internet Connection
via Wi-Fi
Both Blinking
Setup Mode. Wi-Fi connectivity
is disabled. Press and release “Setup”
button to exit
Just One Blinking
(When blue is solid) Lumin server error
Attempting to connect to the
internet
Both Solid
Fully connected via Wi-Fi
NOTE: Simultaneous blue and green blinking lights indicate that the LSP is in
Setup Mode. This is the required mode for initial setup and commissioning,
however the LSP does not connect to the internet via Wi-Fi in this mode. If
both lights are seen blinking during normal operation, it is likely that the
“Setup” button was pressed, taking the LSP offline. In most instances, an
additional press-and-release of the “Setup” button will bring the LSP back
online. Note that it may take about 45 seconds to restore the connection and
display two solid unblinking indicator lights.
NOTE: During an internet outage local connection can be made between an LSP
and user’s mobile device as long as the device and the LSP are connected to
the same network. Ensure that the LSP is not in Setup Mode and that Wi-Fi
connectivity is enabled on the mobile device.
NOTE: In the unlikely event that the LSP cannot be controlled via the mobile
app or web interface, all Lumin-controlled circuits can be enabled by toggling
the Lumin power rocker switch in a particular sequence. To bypass the system,
turn LSP power off (“O”), then on (“I”), then off again (“O”). Please contact
Lumin support as soon as possible so we can help resolve your issue.
Need help? For additional support documentation, visit
http://luminsmart.freshdesk.com/support/solutions or scan the code at right:
34
PRODUCT SPECIFICATIONS
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
INSTALLATION
Type
Wall-Mount; Indoor Only
Installer Qualification Local Electrical Codes and
Lumin Certified Installer
Typical Time Required 1.54 Hours
Temperature
0°C to 60°C (32°F to 140°F)
Humidity
< 80% RH (Non-Condensing)
Altitude
< 3000 m
Pollution Level
Degree 2
Dimensions
44.6 cm × 44.6 cm × 10.1 cm
(17.5 in × 17.5 in × 4.0 in)
Weight
12 kg (27 lb)
Conductor Length
All Extend 76 cm (30 in) Beyond
Conduit End
Additional Units
Use of Multiple Lumin Smart Panels
Supported
CONNECTIVITY & SECURITY
Connection Options
Wi-Fi or Ethernet
Internet Bandwidth
Approx. 0.02 Mbps
Wi-Fi Protocols
802.11 b/g/n, 2.4 GHz
Wi-Fi Encryption
WPA and WPA2 Methods
Ethernet Port
1×RJ-45 (10/100/1000 Mbps)
IP Addressing
Dynamic (DHCP)
Cryptographic System TLS 1.2 (Minimum)
Firewall Outbound
Ports 53, 123, 443444, and 50050
Access Required
50059
USER ACCESS
Local Network
Live Data and Controls
Applications
iOS, Android, and Web
Data
1-Second Granularity (Averaged
from 16 kHz)
Load Controls
Manually/Directly, Automated
Schedules, and Automated Modes
ELECTRICAL SYSTEM
AC Voltage
120/240 VAC Split-Phase, 5060Hz
Supply Breaker Rating
1520 A (non-GFCI)
Supply Amperage
0.4 A (Maximum)
Standby Power
6 W
Voltage Fluctuations
±10% from Nominal
Overvoltage
Category III (Building Wiring)
TPU (Optional)
Load Shedding: Supports Toggling
All Lines a Minimum of Once
During a Power Outage
MANAGED LOADS
Max. Load Breaker
60 A per Line × 6 Lines and
Ratings up to 50 °C
30 A per Line × 6 Lines
Load Breaker Ratings
50 A per Line × 6 Lines and
at 50-60 °C
20 A per Line × 6 Lines
Breaker Types
Single Pole (1 Line) and Dual Pole
(2 Lines)
MEASUREMENT
Accuracy
±0.5% of Load
Monitoring Type
Separate Measurement of Lines
(Including Dual-Pole)
Split-Phase Voltage
Separate Line-to-Neutral Potential
Measurement
Current Transformers
2 Split-Core 200 A Included;
Up to 2 Additional Available
Measurement Category Loads: CAT III (Mains Distr.)
GDC: CAT IV (Mains Source)
SUPPORT & COMPLIANCE
Warranty
10-Year Limited
Compatible Equipment All Makes/Models/Brands of
Electrical Panels and Breakers
Safety Compliance
Listed to UL and CSA C22.2: 61010-1 & 61010-2-030
Radiofrequency
47 CFR 15 (FCC)
Compliance
RSS-Gen and RSP-100 (ISED)
35
LIMITED WARRANTY FOR LUMIN SMART PANEL
This Limited Warranty gives you specific legal rights and you may also have
other rights, which vary from state to state. We warrant that during the
warranty period, the product will be free from defects in materials and
workmanship. We limit the duration and remedies of all implied warranties,
including without limitation the warranties of merchantability and fitness for
a particular purpose to the duration of this express limited warranty. Some
states do not allow limitations on how long an implied warranty lasts, so the
above limitations may not apply to you. Our responsibility for defective goods
is limited to repair, replacement, or refund as described below in this
warranty statement.
Who May Use This Warranty? Coulomb Inc. (d/b/a Lumin), a Delaware corporation
located at address 501 Locust Ave, Suite 2, Charlottesville, VA 22902 (“we”)
extends this limited warranty only to the consumer who originally activated
the product and connected it to a Lumin Account (through
https://www.luminsmart.com/) and to any subsequent owner or other transferee
of the product (“you”).
What Does This Warranty Cover? This limited warranty covers defects in
materials and workmanship of the Lumin Smart Panel (the “product”) for the
Warranty Period as defined below.
What Does This Warranty Not Cover? This limited warranty does not cover any
damage due to: (a) transportation; (b) storage; (c) improper installation; (d)
improper use; (e) failure to follow the product instructions; (f) failure to
adhere to the product’s technical specifications, including the product’s
environmental and electrical ratings; (g) modifications; (h) unauthorized
opening of the product’s cover; (i) tampering with the product’s internal
components; (j) unauthorized repair; (k) normal wear and tear; or (l) external
causes such as accidents, abuse, flooding, lightning strikes, storms, or other
actions or events beyond our reasonable control. This limited warranty also
does not apply to the software, mobile applications, technology and services
provided by Lumin which enable you to remotely access and view data that is
collected, stored and transmitted by the product concerning electricity
consumption and/or to remotely control electrical circuits which the product
is connected to (the “Lumin Service”). Use of the Lumin Service is subject to
and governed by the terms of the Lumin Service User Agreement, a copy of which
can be accessed at https://www.luminsmart.com/consentdocumentation/. Any
warranties provided by Lumin with respect to the Lumin Service are only those
warranties expressly set forth in the Lumin Service User Agreement.
What Is the Period Of Coverage? The “Warranty Period” for this limited
warranty starts on the date the product is first activated and connected to a
Lumin Account through https://www.luminsmart.com/) and lasts (a) for two years
for the product’s sensor boards and the processor board, including the
individual components that makeup the sensor boards and processor board, and
(b) for ten years for all other components of the product. The Warranty Period
is not extended if we repair or replace the product. We may change the
availability of this limited warranty at our discretion, but any changes will
not be retroactive.
What Are Your Remedies Under This Warranty? With respect to any defective
product during the applicable Warranty Period, we will, in our sole
discretion, either: (a) repair or replace such product (or the defective part)
free of charge or (b) refund the purchase price of such product. We will also
pay for shipping and handling fees to return the repaired or replacement
product to you if we elect to repair or replace the defective product.
How Do You Obtain Warranty Service? To obtain warranty service, you must call
1-888-421-0616 or e-mail
support@luminsmart.com during the Warranty Period to obtain a Defective
Merchandise Authorization (“DMA”) number. No warranty service will be provided
without a DMA number.
Limitation of Liability. The remedies descried above are your sole and
exclusive remedies and our entire liability for any breach of this limited
warranty. Our liability shall under no circumstances exceed the actual amount
paid by you for the defective product, nor shall we under any circumstances be
liable for any consequential, incidental, special or punitive damages or
losses, whether direct or indirect. Some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you.
36
RADIO FREQUENCY STATEMENT
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
This device complies with Part 15 of the FCC rules and with Innovation,
Science and Economic Development Canada’s licence-exempt RSS(s). Operation is
subject to the following two conditions:
1. This device may not cause interference. 2. This device must accept any
interference, including interference that may cause undesired
operation of the device.
L’émetteur/récepteur exempt de licence contenu dans le présent appareil est
conforme à la partie 15 des règles de la FCC et aux CNR d’Innovation, Sciences
et Développement économique Canada applicables aux appareils radio exempts de
licence. L’exploitation est autorisée aux deux conditions suivantes:
1. L’appareil ne doit pas produire de brouillage; 2. L’appareil doit accepter
tout brouillage radioélectrique subi, même si le brouillage est
susceptible d’en compromettre le fonctionnement.
There is no guarantee that interference will not occur in a particular
installation. If it does cause interference, we recommend reorienting the
receiving antenna, increasing the separation between the device and the
receiver, or consulting an experienced radio/TV technician for help.
37
NOTES
38
NOTES
Lumin Smart Panel
DOCUMENTATION AND INSTALLATION MANUAL
39
501 Locust Ave, Floor 1, Suite 2 Charlottesville, VA 22902
SUPPORT@LUMINSMART.COM 1-888-421-0616
WWW.LUMINSMART.COM
U.S. Patent No. 10,109,987 U.S. Patent No. 10,467,712 Canadian Patent No.
3,050,702 U.S. and International Patent Applications Pending. ® U.S.
Registered Trademark. Copyright © 2022 Coulomb, Inc. (DBA Lumin). All rights
reserved.