neptronic SKG4 Gas Fired Humidifier User Guide
- June 4, 2024
- neptronic
Table of Contents
neptronic SKG4 Gas Fired Humidifier
Introduction
The SKG4 Modbus Communication Module User Guide provides information for using
Neptronic® communication feature. The controller uses Modbus communication
protocol over serial line in the RTU mode and provides a Modbus network
interface between client devices and Neptronic SKG4 devices.
The SKG4 Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus:
-
Data Model. The SKG4 Gas Fired Humidifier Modbus server data model uses only the Modbus Registers table.
-
Register Address:
- As per protocol base (base 0); for PLC add 1 to protocol base.
- As per holding register (base 400001).
Note: Ensure that the Modbus communication software used does not have a limit on the range of the register addresses that can be viewed and supports 6-digit holding registers.
-
Function Codes. The SKG4 Gas Fired Humidifier Modbus server supports a limited function codes subset comprising:
- Read Holding Registers (0x03)
- Write Single Register (0x06)
- Write Multiple Registers (0x10)
-
Exception Responses. The SKG4 Gas Fired Humidifier Modbus server supports the following exception codes:
- Illegal data address
- Illegal data value
- Slave device busy
-
Serial Line. The SKG4 Gas Fired Humidifier Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
- The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
- The supported baud rates are 9600, 19200, 38400, and 57600.
- The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2.
- In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
-
Addressing. The SKG4 Gas Fired Humidifier device only answers at the following address:
- The device’s unique address (1 to 246) that can be set through the device menu or through holding register index 0.
Modbus Registers
Table Glossary
Name | Description | Name | Description |
---|---|---|---|
W | Writable Register | ASCII | For registers containing ASCII (8-bit) characters |
RO | Read Only Register | MSB | Most Significant Byte |
Unsigned | For range of values from 0 to 65,535, unless otherwise specified | ||
LSB | Least Significant Byte | ||
Signed | For range of values from -32,768 to 32,767, unless otherwise | ||
specified | MSW | Most Significant Word | |
Bit String | For registers with multiple values using bit mask (example, | ||
flags) | LSW | Least Significant Word |
Modbus Registers Table
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
0
| ****
40000 1
| ****
Modbus Address and Product Type
| ****
Unsigned
| MSB = Product type, not writable
LSB = Modbus Address (1 to 247), writable
| ****
W
|
1| 40000 2| Device Baud Rate| Unsigned
Scale 100
| 0, 9600, 19200, 38400, and 57600, 0 = Auto Baud
Rate Detection Value/100 (e.g. 38400 baud = 384)
| W| 19200
2
| ****
40000 3
| ****
Modbus Slave Communication Port Configuration
| ****
Unsigned
| 0 = No parity, 2 Stop bits 1 = Even parity, 1 Stop bit 2 = Odd parity, 1 Stop bit| ****
W
| ****
No parity, 2 Stops bits
3| 40000 4| Product Name (characters 8 & 7)| ASCII| MSB = char 6, LSB =
char 7| W|
4| 40000 5| Product Name (characters 6 & 5)| ASCII| MSB = char 4, LSB =
char 5| W|
5| 40000 6| Product Name (characters 4 & 3)| ASCII| MSB = char 2, LSB =
char 3| W|
6| 40000 7| Product Name (characters 2 & 1)| ASCII| MSB = char 0, LSB =
char 1| W|
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
7| 40000 8| Product Actual Firmware Version (in Integer x100)| Unsigned
Scale 100
| 1 to 65535 (e.g. 100)| RO|
8| 40000 9| Product Actual EEPROM Version (in Integer x100)| Unsigned
Scale 100
| 1 to 65535 (e.g. 100)| RO|
2000
| ****
40 2001
| ****
Supply RH Signal (0)
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 1V = 1000)
| ****
RO
| ****
0V
2001| 40 2002| Supply RH Signal (1)| | Units: Volt (V), Range: 0V to 15V| |
2002
| ****
40 2003
| ****
Room RH Signal (0)
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 1V = 1000)
| ****
RO
| ****
0V
2003| 40 2004| Room RH Signal (1)| | Units: Volt (V), Range: 0V to 15V| |
2004
| ****
40 2005
| ****
Control Signal (0)
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 1V = 1000)
| ****
RO
| ****
0V
2005| 40 2006| Control Signal (1)| | Units: Volt (V), Range: 0V to 15V| |
2006
| ****
40 2007
| ****
Cabinet Temperature Signal
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
RO
| ****
0V
2007
| ****
40 2008
| ****
Main Power Supply (0)
| Unsigned
Scale 10
| Unit: Volt (V), Range: 0V to 40V
Value x 10 (e.g. 1V = 10)
| ****
RO
| ****
0V
2008| 40 2009| Main Power Supply (1)| | Unit: Volt (V), Range: 0V to
40V| |
4000| 40 4001| Power Output Feedback Signal| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| RO| 0V
6000
| ****
40 6001
| ****
Supply High Limit RH
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
6001
| ****
40 6002
| ****
Supply High Limit RH Min
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6002
| ****
40 6003
| ****
Supply High Limit RH Max
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
100% RH
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6003
| ****
40 6004
| ****
Supply High Limit RH Bias
| Signed
Scale 100
| Unit: % RH, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6004
| ****
40 6005
| ****
Room RH
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
6005
| ****
40 6006
| ****
Room RH Min
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
100% RH
6006
| ****
40 6007
| ****
Room RH Max
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
100% RH
6007
| ****
40 6008
| ****
Room RH Bias
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
100% RH
6008
| ****
40 6009
| ****
Control Input
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6009
| ****
40 6010
| ****
Control Min
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6010
| ****
40 6011
| ****
Control Max
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6011
| ****
40 6012
| ****
Control Bias
| Signed
Scale 100
| Unit: % RH, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6012
| ****
40 6013
| ****
Board Temperature
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F
Value x 100 (e.g. 5°C = 500 or 32ºF = 3200)
| ****
RO
| ****
0°C or 32°F
6013
| ****
40 6014
| ****
Power Output Feedback Bias
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
0V
6014
| ****
40 6015
| ****
Power Output Feedback Min
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
0V
6015
| ****
40 6016
| ****
Power Output Feedback Max
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
10V
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6016
| ****
40 6017
| ****
Power Output Feedback
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6017| 40 6018| Module 1 Water Level| Unsigned
Scale 10
| Unit: %, Range: 0% to 120%
Value x 100 (e.g. 10% = 1000)
| RO| 78%
6018| 40 6019| Module 1 Water Probe Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6019| 40 6020| Module 1 Water Probe High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6020| 40 6021| Module 1 Water Probe Abs Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6021| 40 6022| Module 1 Water Probe Abs High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6022| 40 6023| Module 2 Water Level| Unsigned
Scale 10
| Unit: %, Range: 0% to 120%
Value x 100 (e.g. 10% = 1000)
| RO| 78%
6023| 40 6024| Module 2 Water Probe Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6024| 40 6025| Module 2 Water Probe High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6025| 40 6026| Module 2 Water Probe Abs Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6026| 40 6027| Module 2 Water Probe Abs High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6027| 40 6028| Module 3 Water Level| Unsigned
Scale 10
| Unit: %, Range: 0% to 120%
Value x 100 (e.g. 10% = 1000)
| RO| 78%
6028| 40 6029| Module 3 Water Probe Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6029| 40 6030| Module 3 Water Probe High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6030| 40 6031| Module 3 Water Probe Abs Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6031| 40 6032| Module 3 Water Probe Abs High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6032| 40 6033| Module 4 Water Level| Unsigned
Scale 10
| Unit: %, Range: 0% to 120%
Value x 100 (e.g. 10% = 1000)
| RO| 78%
6033| 40 6034| Module 4 Water Probe Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6034| 40 6035| Module 4 Water Probe High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6035| 40 6036| Module 4 Water Probe Abs Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6036| 40 6037| Module 4 Water Probe Abs High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000HZ
6037| 40 6038| Room RH Network Reading| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 0% RH
6038| 40 6039| Room RH Setpoint| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 40% RH
6039| 40 6040| Room RH Unoccupied Setpoint| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 30% RH
6040| 40 6041| Room RH Vacant Setpoint| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 20% RH
6041| 40 6042| Room Demand Proportional Gain| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 1 = 10)
| W| 20
6042
| ****
40 6043
| ****
Room Demand Integral Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10sec = 100)
| ****
W
| ****
0 sec
6043
| ****
40 6044
| ****
Room Demand Derivative Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10sec = 100)
| ****
W
| ****
0 sec
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6044| 40 6045| Room Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| RO| 0% RH
6045
| ****
40 6046
| ****
Room Demand Proportional Band
| Unsigned
Scale 10
| Unit: %, Range: 0% to 100%
Value x 10 (e.g. 10% = 100)
| ****
W
| ****
5%
6046| 40 6047| Supply High Limit Network Reading| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 0% RH
6047| 40 6048| Supply High Limit Setpoint| Unsigned
Scale 100
| Unit: %, RH Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 80% RH
6048| 40 6049| Supply High Limit Proportional Gain| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)
| W| 10
6049| 40 6050| Supply High Limit Integral Time| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10sec = 100)
| W| 0 sec
6050
| ****
40 6051
| ****
Supply High Limit Derivative Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10sec = 100)
| ****
W
| ****
0 sec
6051| 40 6052| Supply High Limit Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| RO| 0% RH
6052| 40 6053| Humidity Control Network Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 0% RH
6053| 40 6054| Humidity Control Network High Limit| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 100% RH
6054| 40 6055| Humidity Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 1% RH = 100)
| RO| 0% RH
6055
| ****
40 6056
| ****
Network Timeout (0)
| Unsigned
Scale 1
| Unit: Seconds (sec), Range: 1 to 900 sec
Value x 1 (e.g. 10sec = 10)
| ****
W
| ****
900 sec
6056| 40 6057| Network Timeout (1)| | Unit: Seconds (sec), Range: 1 to
900 sec| |
6057| 40 6058| Humidity Demand Low Dead Band (0)| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| W| 1%
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6058| 40 6059| Humidity Demand Low Dead Band (1)| | Unit: %, Range: 0%
to 100%
Value x 100 (e.g. 10% = 1000)
| |
6059| 40 6060| System Power Output| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| RO| 0%
6060
| ****
40 6061
| ****
System Steam Capacity
| Unsigned
Scale 10
| Unit: kg/hr or lb/hr, Range: 0 to 3000 kg/hr or 0 to 6614 lb/hr
Value x 10 (e.g. 10 kg/hr = 100 or 10 lb/hr = 100)
| ****
RO
| 0 kg/hr or
0 lb/hr
6061| 40 6062| Module 1 Manual Calibration Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6062| 40 6063| Module 1 Manual Calibration Time (1)| | Units: Hours (h),
Range: 0 to 2147483647 h| RO| 0h
6063| 40 6064| Module 1 Manual Calibration Time (2)| | Units: Hours (h),
Range: 0 to 2147483647 h| RO| 0h
6064| 40 6065| Module 1 Manual Calibration Time (3)| | Units: Hours (h),
Range: 0 to 2147483647 h| RO| 0h
6065| 40 6066| Module 1 Chimney Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 260°C or 32°F to 500°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6066| 40 6067| Module 1 Chimney Temp (1)| | Unit: ºC/ºF, Range: 0°C to
260°C or 32°F to 500°F| |
6067| 40 6068| Module 1 Water Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6068| 40 6069| Module 1 Water Temp (1)| | Unit: ºC/ºF, Range: 0°C to
125°C or 32°F to 257°F| |
6069| 40 6070| Module 1 Water Frequency (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
6070| 40 6071| Module 1 Water Frequency (1)| | Unit: Hz, Range: 0 to
30000 Hz| |
6071| 40 6072| Module 1 Ambient Temp (0)| Signed
Scale 100
| Unit: ºC/ºF, Range: -40°C to 100°C or -40°F to 212°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6072| 40 6073| Module 1 Ambient Temp (1)| | Unit: ºC/ºF, Range: -40°C to
100°C or -40°F to 212°F| |
6073| 40 6074| Module 1 Fan Feedback (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 2000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6074| 40 6075| Module 1 Fan Feedback (1)| | Unit: Hz, Range: 0 to 2000
Hz| |
6075
| ****
40 6076
| ****
Module 1 Fan PWM (0)
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| ****
RO
| ****
0%
6076| 40 6077| Module 1 Fan PWM (1)| | Unit: %, Range: 0% to 100%| |
6077| 40 6078| Module 1 Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6078| 40 6079| Module 1 Run Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6079| 40 6080| Module 1 Run Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6080| 40 6081| Module 1 Run Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6081| 40 6082| Module 1 Service On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6082| 40 6083| Module 1 Service On Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6083| 40 6084| Module 1 Service On Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6084| 40 6085| Module 1 Service On Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6085| 40 6086| Module 1 Service Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6086| 40 6087| Module 1 Service Run Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6087| 40 6088| Module 1 Service Run Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6088| 40 6089| Module 1 Service Run Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6089| 40 6090| Module 1 On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6090| 40 6091| Module 1 On Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6091| 40 6092| Module 1 On Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6092| 40 6093| Module 1 On Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6093| 40 6094| Module 1 Demand| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 0%
6094| 40 6095| Module 1 Max Steam Output| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 100%
6095
| ****
40 6096
| ****
Module 1 Ignition Count (0)
| Unsigned
Scale 1
| No unit, 0 to 214748364
Value x 1 (e.g. 1 = 1)
| ****
RO
| ****
0
6096| 40 6097| Module 1 Ignition Count (1)| | No unit, 0 to 214748364|
|
6097| 40 6098| Module 1 Ignition Count (2)| | No unit, 0 to 214748364|
|
6098| 40 6099| Module 1 Ignition Count (3)| | No unit, 0 to 214748364|
|
6099| 40 6100| Module 2 Chimney Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 260°C or 32°F to 500°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6100| 40 6101| Module 2 Chimney Temp (1)| | Unit: ºC/ºF, Range: 0°C to
260°C or 32°F to 500°F| |
6101| 40 6102| Module 2 Water Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6102| 40 6103| Module 2 Water Temp (1)| | Unit: ºC/ºF, Range: 0°C to
125°C or 32°F to 257°F| |
6103| 40 6104| Module 2 Water Frequency (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
6104| 40 6105| Module 2 Water Frequency (1)| | Unit: Hz, Range: 0 to
30000 Hz| |
6105| 40 6106| Module 2 Ambient Temp (0)| Signed
Scale 100
| Unit: ºC/ºF, Range: -40°C to 100°C or -40°F to 212°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6106| 40 6107| Module 2 Ambient Temp (1)| | Unit: ºC/ºF, Range: -40°C to
100°C or -40°F to 212°F| |
6107| 40 6108| Module 2 Fan Feedback (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 2000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
6108| 40 6109| Module 2 Fan Feedback (1)| | Unit: Hz, Range: 0 to 2000
Hz| |
6109
| ****
40 6110
| ****
Module 2 Fan PWM (0)
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| ****
RO
| ****
0%
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6110| 40 6111| Module 2 Fan PWM (1)| | Unit: %, Range: 0% to 100%| |
6111| 40 6112| Module 2 Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6112| 40 6113| Module 2 Run Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6113| 40 6114| Module 2 Run Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6114| 40 6115| Module 2 Run Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6115| 40 6116| Module 2 Service On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6116| 40 6117| Module 2 Service On Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6117| 40 6118| Module 2 Service On Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6118| 40 6119| Module 2 Service On Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6119| 40 6120| Module 2 Service Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6120| 40 6121| Module 2 Service Run Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6121| 40 6122| Module 2 Service Run Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6122| 40 6123| Module 2 Service Run Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6123| 40 6124| Module 2 On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6124| 40 6125| Module 2 On Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6125| 40 6126| Module 2 On Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6126| 40 6127| Module 2 On Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6127| 40 6128| Module 2 Demand| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 0%
6128| 40 6129| Module 2 Max Steam Output| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 100%
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6129| 40 6130| Module 2 Ignition Count (0)| Unsigned
Scale 1
| No unit, 0 to 214748364
Value x 1 (e.g. 1 = 1)
| RO| 0
6130| 40 6131| Module 2 Ignition Count (1)| | No unit, 0 to 214748364|
|
6131| 40 6132| Module 2 Ignition Count (2)| | No unit, 0 to 214748364|
|
6132| 40 6133| Module 2 Ignition Count (3)| | No unit, 0 to 214748364|
|
6133| 40 6134| Module 2 Manual Calibration Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| W| 0h
6134| 40 6135| Module 2 Manual Calibration Time (1)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6135| 40 6136| Module 2 Manual Calibration Time (2)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6136| 40 6137| Module 2 Manual Calibration Time (3)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6137| 40 6138| Module 3 Chimney Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 260°C or 32°F to 500°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6138| 40 6139| Module 3 Chimney Temp (1)| | Unit: ºC/ºF, Range: 0°C to
260°C or 32°F to 500°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| |
6139| 40 6140| Module 3 Water Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6140| 40 6141| Module 3 Water Temp (1)| | Unit: ºC/ºF, Range: 0°C to
125°C or 32°F to 257°F| |
6141| 40 6142| Module 3 Water Frequency (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
6142| 40 6143| Module 3 Water Frequency (1)| | Unit: Hz, Range: 0 to
30000 Hz| |
6143| 40 6144| Module 3 Ambient Temp (0)| Signed
Scale 100
| Unit: ºC/ºF, Range: -40°C to 100°C or -40°F to 212°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6144| 40 6145| Module 3 Ambient Temp (1)| | Unit: ºC/ºF, Range: -40°C to
100°C or -40°F to 212°F| |
6145| 40 6146| Module 3 Fan Feedback (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 2000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
6146| 40 6147| 6Module 3 Fan Feedback (1)| | Unit: Hz, Range: 0 to 2000
Hz| |
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6147
| ****
40 6148
| ****
Module 3 Fan PWM (0)
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| ****
RO
| ****
0%
6148| 40 6149| Module 3 Fan PWM (1)| | Unit: %, Range: 0% to 100%| |
6149| 40 6150| Module 3 Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6150| 40 6151| Module 3 Run Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6151| 40 6152| Module 3 Run Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6152| 40 6153| Module 3 Run Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6153| 40 6154| Module 3 Service On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6154| 40 6155| Module 3 Service On Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6155| 40 6156| Module 3 Service On Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6156| 40 6157| Module 3 Service On Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6157| 40 6158| Module 3 Service Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6158| 40 6159| Module 3 Service Run Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6159| 40 6160| Module 3 Service Run Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6160| 40 6161| Module 3 Service Run Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6161| 40 6162| Module 3 On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6162| 40 6163| Module 3 On Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6163| 40 6164| Module 3 On Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6164| 40 6165| Module 3 On Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6165| 40 6166| Module 3 Demand| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 0%
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6166| 40 6167| Module 3 Max Steam Output| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 100%
6167| 40 6168| Module 3 Ignition Count (0)| Unsigned
Scale 1
| No unit, 0 to 214748364
Value x 1 (e.g. 1 = 1)
| RO| 0
6168| 40 6169| Module 3 Ignition Count (1)| | No unit, 0 to 214748364|
|
6169| 40 6170| Module 3 Ignition Count (2)| | No unit, 0 to 214748364|
|
6170| 40 6171| Module 3 Ignition Count (3)| | No unit, 0 to 214748364|
|
6171| 40 6172| Module 3 Manual Calibration Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| W| 0h
6172| 40 6173| Module 3 Manual Calibration Time (1)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6173| 40 6174| Module 3 Manual Calibration Time (2)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6174| 40 6175| Module 3 Manual Calibration Time (3)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6175| 40 6176| Module 4 Chimney Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 260°C or 32°F to 500°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6176| 40 6177| Module 4 Chimney Temp (1)| | Unit: ºC/ºF, Range: 0°C to
260°C or 32°F to 500°F| |
6177| 40 6178| Module 4 Water Temp (0)| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6178| 40 6179| Module 4 Water Temp (1)| | Unit: ºC/ºF, Range: 0°C to
125°C or 32°F to 257°F| |
6179| 40 6180| Module 4 Water Frequency (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
6180| 40 6181| Module 4 Water Frequency (1)| | Unit: Hz, Range: 0 to
30000 Hz| |
6181| 40 6182| Module 4 Ambient Temp (0)| Signed
Scale 100
| Unit: ºC/ºF, Range: -40°C to 100°C or -40°F to 212°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6182| 40 6183| Module 4 Ambient Temp (1)| | Unit: ºC/ºF, Range: -40°C to
100°C or -40°F to 212°F| |
6183| 40 6184| Module 4 Fan Feedback (0)| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 2000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 0Hz
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6184| 40 6185| Module 4 Fan Feedback (1)| | Unit: Hz, Range: 0 to 2000
Hz| |
6185
| ****
40 6186
| ****
Module 4 Fan PWM (0)
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| ****
RO
| ****
0%
6186| 40 6187| Module 4 Fan PWM (1)| | Unit: %, Range: 0% to 100%| |
6187| 40 6188| Module 4 Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6188| 40 6189| Module 4 Run Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6189| 40 6190| Module 4 Run Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6190| 40 6191| Module 4 Run Time (4)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6191| 40 6192| Module 4 Service On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6192| 40 6193| Module 4 Service On Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6193| 40 6194| Module 4 Service On Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6194| 40 6195| Module 4 Service On Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6195| 40 6196| Module 4 Service Run Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6196| 40 6197| Module 4 Service Run Time (1)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6197| 40 6198| Module 4 Service Run Time (2)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6198| 40 6199| Module 4 Service Run Time (3)| | Units: Hours (h), Range:
0 to 2147483647 h| |
6199| 40 6200| Module 4 On Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| RO| 0h
6200| 40 6201| Module 4 On Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6201| 40 6202| Module 4 On Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6202| 40 6203| Module 4 On Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6203| 40 6204| Module 4 Demand| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 0%
6204| 40 6205| Module 4 Max Steam Output| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| W| 100%
6205| 40 6206| Module 4 Ignition Count (0)| Unsigned
Scale 1
| No unit, 0 to 214748364
Value x 1 (e.g. 1 = 1)
| RO| 0
6206| 40 6207| Module 4 Ignition Count (1)| | No unit, 0 to 214748364|
|
6207| 40 6208| Module 4 Ignition Count (2)| | No unit, 0 to 214748364|
|
6208| 40 6209| Module 4 Ignition Count (3)| | No unit, 0 to 214748364|
|
6209| 40 6210| Module 4 Manual Calibration Time (0)| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 1h = 100)
| W| 0h
6210| 40 6211| Module 4 Manual Calibration Time (1)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6211| 40 6212| Module 4 Manual Calibration Time (2)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6212| 40 6213| Module 4 Manual Calibration Time (3)| | Units: Hours (h),
Range: 0 to 2147483647 h| |
6213| 40 6214| Water Level Replace Interval (0)| Unsigned Scale 1|
Unit: Days, Range: 0 day to 7 days
Value x 1 (e.g. 1 day = 1)
| W| 7 days
6214| 40 6215| Water Level Replace Interval (1)| | Unit: Days, Range: 0
day to 7 days| |
6215| 40 6216| Boiler Blowdown Rate| Unsigned
Scale 1
| Unit: %, Range: 0% to 100%
Value x 1 (e.g.1% = 1)
| W| 0%
6216| 40 6217| Boiler Drain Interval| Unsigned
Scale 1
| Units: Hours (h), Range: 0 to 24 h
Value x 1 (e.g. 1 h = 1)
| W| 6h
6217| 40 6218| Boiler Idle Temperature Setpoint (0)| Unsigned
Scale 1
| Unit: ºC/ºF, Range: 0°C to 60°C or 32°F or 140°F
Value x 1 (e.g. 5°C = 500 or 32ºF = 3200)
| W| 0°C or 32°F
6218| 40 6219| Boiler Idle Temperature Setpoint (1)| | Unit: ºC/ºF,
Range: 0°C to 60°C or 32°F or 140°F| |
6219| 40 6220| Boiler Idle Time Drain| Unsigned
Scale 1
| Unit: Hours (h), Range: 0 to 72 h
Value x 1 (e.g. 1 h = 1)
| W| 24h
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
6220| 40 6221| Boiler Service Interval| Unsigned
Scale 1
| Unit: Hours (h), Range: 1000 to 3000 h
Value x 1 (e.g. 1500 h = 1500)
| W| 1000h
6221| 40 6222| Boiler Idle Tank Rinse Interval| Unsigned
Scale 1
| Unit: Days, Range: 1 to 7 days
Value x 1 (e.g. 1 day = 1)
| W| 3 day
6222| 40 6223| Boiler Minimum Steam Output| Unsigned
Scale 1
| Unit: %, Range: 0 to 25%
Value x 1 (e.g. 1% = 1)
| W| 0%
6223| 40 6224| Boiler Drain Volume| Unsigned
Scale 1
| Unit: %, Range: 25 to 100%
Value x 1 (e.g. 30% = 30)
| W| 100%
6224| 40 6225| HRL Temperature| Signed
Scale 100
| Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to 500°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6225| 40 6226| HRL Humidity| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 1% RH = 100)
| RO| 0% RH
6226
| ****
40 6227
| ****
Modbus TCP IP Keep Alive Time Out (0)
| Unsigned
Scale 1
| Unit: Minutes (min), Range: 1 to 1440 mins
Value x 1 (e.g. 5 mins = 5)
| ****
W
| ****
5 min
6227| 40 6228| Modbus TCP IP Keep Alive Time Out (1)| | Unit: Minutes (min), Range: 1 to 1440 mins| |
10000
| ****
4 10001
| ****
Water Leak Detection
| Unsigned
Scale 1
| 0 = Ok
1 = Leak
| ****
RO
| ****
Ok
10001
| ****
4 10002
| ****
Binary External Demand
| Unsigned
Scale 1
| 0 = 0%
1 = 100%
| ****
RO
| ****
0%
10002
| ****
4 10003
| ****
Interlock
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10003
| ****
4 10004
| ****
Supply High Limit
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10004
| ****
4 10005
| ****
Air Flow
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10005
| ****
4 10006
| ****
RS485 Interface
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
RO
| ****
No
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
10006
| ****
4 10007
| ****
Ethernet Interface
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
RO
| ****
No
11000| 4 11001| Service Warning Relay| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11001| 4 11002| Alarm Warning Relay| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11002
| ****
4 11003
| ****
Alarm LED
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11003
| ****
4 11004
| ****
Power LED
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11004
| ****
4 11005
| ****
Buzzer
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
12000
| ****
4 12001
| ****
Network Control State
| Unsigned
Scale 1
| 0 = Normal
1 = Fault
| ****
W
| ****
Normal
12001
| ****
4 12002
| ****
Inhibit Resistive Probe
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
W
| ****
No
12002
| ****
4 12003
| ****
Inhibit Resistive Probe
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
W
| ****
No
12003
| ****
4 12004
| ****
Inhibit Resistive Probe
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
W
| ****
No
12004
| ****
4 12005
| ****
Inhibit Resistive Probe
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
W
| ****
No
12005| 4 12006| Module 1 Burner Inlet Pressure| Unsigned
Scale 1
| 0 = Normal
1 = Blocked
| RO| Normal
12006| 4 12007| Module 1 Water Level Low| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
12007| 4 12008| Module 1 Water Level High| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
12008| 4 12009| Module 1 Foam Sensor| Unsigned
Scale 1
| 0 = NoFoam
1 = Foam
| RO| NoFoam
12009| 4 12010| Module 1 Gas Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12010| 4 12011| Module 1 Tank Water Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12011| 4 12012| Module 1 Water Level Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12012
| ****
4 12013
| ****
Module 1 Drain Cooler Valve
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
12013| 4 12014| Module 1 Drain Pump| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12014| 4 12015| Module 1 Ignition Control| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12015| 4 12016| Module 1 AlarmLED| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12016| 4 12017| Module 1 Foam State| Unsigned
Scale 1
| 0 = Ok
1 = Detected
| RO| Ok
12017| 4 12018| Module 1 Service Due| Unsigned
Scale 1
| 0 = No
1 = Yes
| RO| No
12018| 4 12019| Module 1 Drain Valve| Unsigned
Scale 1
| 0 = On
1 = Off
| RO| On
12019
| ****
4 12020
| ****
Module 1 Water Level Probe Alarm
| Unsigned
Scale 1
| 0= Ok
1= Defect
| ****
RO
| ****
Ok
12020| 4 12021| Module 2 Burner Inlet Pressure| Unsigned
Scale 1
| 0 = Normal
1 = Blocked
| RO| Normal
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
12021| 4 12022| Module 2 Water Level Low| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
12022| 4 12023| Module 2 Water Level High| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
12023| 4 12024| Module 2 Foam Sensor| Unsigned
Scale 1
| 0 = NoFoam
1 = Foam
| RO| NoFoam
12024| 4 12025| Module 2 Gas Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12025| 4 12026| Module 2 Tank Water Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12026| 4 12027| Module 2 Water Level Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12027
| ****
4 12028
| ****
Module 2 Drain Cooler Valve
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
12028| 4 12029| Module 2 Drain Pump| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12029| 4 12030| Module 2 Ignition Control| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12030| 4 12031| Module 2 AlarmLED| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12031| 4 12032| Module 2 Service Due| Unsigned
Scale 1
| 0 = No
1 = Yes
| RO| No
12032| 4 12033| Module 2 Foam State| Unsigned
Scale 1
| 0 = Ok
1 = Detected
| RO| Ok
12033| 4 12034| Module 2 Drain Valve| Unsigned
Scale 1
| 0 = On
1 = Off
| RO| On
12034
| ****
4 12035
| ****
Module 2 Water Level Probe Alarm
| Unsigned
Scale 1
| 0= Ok
1= Defect
| ****
RO
| ****
Ok
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
12035| 4 12036| Module 3 Burner Inlet Pressure| Unsigned
Scale 1
| 0 = Normal
1 = Blocked
| RO| Normal
12036| 4 12037| Module 3 Water Level Low| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
12037| 4 12038| Module 3 Water Level High| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
12038| 4 12039| Module 3 Foam Sensor| Unsigned
Scale 1
| 0 = NoFoam
1 = Foam
| RO| NoFoam
12039| 4 12040| Module 3 Gas Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12040| 4 12041| Module 3 Tank Water Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12041| 4 12042| Module 3 Water Level Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12042
| ****
4 12043
| ****
Module 3 Drain Cooler Valve
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
12043| 4 12044| Module 3 Drain Pump| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12044| 4 12045| Module 3 Ignition Control| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12045| 4 12046| Module 3 AlarmLED| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12046| 4 12047| Module 3 Service Due| Unsigned
Scale 1
| 0 = No
1 = Yes
| RO| No
12047| 4 12048| Module 3 Foam State| Unsigned
Scale 1
| 0 = Ok
1 = Detected
| RO| Ok
12048| 4 12049| Module 3 Drain Valve| Unsigned
Scale 1
| 0 = On
1 = Off
| RO| On
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
12049
| ****
4 12050
| ****
Module 3 Water Level Probe Alarm
| Unsigned
Scale 1
| 0= Ok
1= Defect
| ****
RO
| ****
Ok
12050| 4 12051| Module 4 Burner Inlet Pressure| Unsigned
Scale 1
| 0 = Normal
1 = Blocked
| RO| Normal
12051| 4 12052| Module 4 Water Level Low| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
12052| 4 12053| Module 4 Water Level High| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| RO| Inactive
12053| 4 12054| Module 4 Foam Sensor| Unsigned
Scale 1
| 0 = NoFoam
1 = Foam
| RO| NoFoam
12054| 4 12055| Module 4 Gas Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12055| 4 12056| Module 4 Tank Water Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12056| 4 12057| Module 4 Water Level Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12057
| ****
4 12058
| ****
Module 4 Drain Cooler Valve
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
12058| 4 12059| Module 4 Drain Pump| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12059| 4 12060| Module 4 Ignition Control| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12060| 4 12061| Module 4 AlarmLED| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12061| 4 12062| Module 4 Service Due| Unsigned
Scale 1
| 0 = No
1 = Yes
| RO| No
12062| 4 12063| Module 4 Foam State| Unsigned
Scale 1
| 0 = Ok
1 = Detected
| RO| Ok
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
12063| 4 12064| Module 4 Drain Valve| Unsigned
Scale 1
| 0 = On
1 = Off
| RO| On
12064
| ****
4 12065
| ****
Module 4 Water Level Probe Alarm
| Unsigned
Scale 1
| 0= Ok
1= Defect
| ****
RO
| ****
Ok
12065
| ****
4 12066
| ****
Boiler Line Rinse
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
On
12066| 4 12067| Boiler Service Operation| Unsigned
Scale 1
| 0 = NotAllowed
1 = Allowed
| W| Allowed
12067| 4 12068| HRL Lock Setpoint| Unsigned
Scale 1
| 0 = Unlock
1 = Lock
| W| Unlock
12068| 4 12069| Notify Alarm| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
12069| 4 12070| Notify Warning| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
12070| 4 12071| Notify App Msg| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
15000| 4 15001| System Power State| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
15001| 4 15002| Modbus Server Units| Unsigned
Scale 1
| 0 = Metric| 1 = Imperial| W| Metric
15002
| ****
4 15003
| ****
Supply RH Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15003
| ****
4 15004
| ****
Room RH Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15004
| ****
4 15005
| ****
Control Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
15005
| ****
4 15006
| ****
Control Profile
| Unsigned
Scale 1
| 0 = ExternAnalog
1 = ExternNetwork
2 = InternAnalog
| 3 = InternNetwork
4 = HRL
5 = Custom
| ****
W
| ****
ExternAnalog
15006
| ****
4 15007
| ****
Modulating High Limit Profile
| Unsigned
Scale 1
| 0 = Disabled
1 = ExternAnalog
2 = ExternNetwork
| 3 = InternAnalog
4 = InternNetwork
5 = Custom
| ****
W
| ****
Disabled
15007| 4 15008| Occupancy State| Unsigned
Scale 1
| 0 = Occupied
1 = Unoccupied
| 2 = Vacant
3 = Off
| RO| Occupied
15008| 4 15009| Room RH Source| Unsigned
Scale 1
| 0 = None
1 = RoomRH
| 2 = Network
3 = HRL
| W| None
15009| 4 15010| Room RH Setpoint Source| Unsigned
Scale 1
| 0 = None
1 = Internal
| 2 = ControlInput| W| None
15010| 4 15011| Supply High Limit Reading Source| Unsigned
Scale 1
| 0 = None
1 = Supply HLRH
| 2 = Network| W| None
15011| 4 15012| Supply High Limit Setpoint Source| Unsigned
Scale 1
| 0 = None
1 = Internal
| 2 = ControlInput| W| None
15012| 4 15013| Humidity Control Demand Source| Unsigned
Scale 1
| 0 = None
1 = ControlInput
| 2 = RoomDemand
3 = Network
| W| ControlInput
15013| 4 15014| Humidity Control High Limit Source| Unsigned
Scale 1
| 0 = None
1 = ControlInput
| 2 = SupplyHLDemand
3 = Network
| W| None
15014
| ****
4 15015
| ****
Humidity Control Cutout State
| Unsigned
Scale 1
| 0 = Off
1 = Normal
2 = LowLimit
| 3 = HighLimit
4 = AirFlow
5 = Interlock
| ****
RO
| ****
Off
15015
| ****
4 15016
| ****
Module 1 State
| ****
Unsigned
Scale 1
| 0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
| 5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
9 = PurgeAir
| ****
RO
| ****
Off
15016
| ****
4 15017
| ****
Module 1 Request
| ****
Unsigned
Scale 1
| 0 = None
1 = Reset Alarms 2 = Drain
| 3 = Reset Counters 4 = Filling
5 = WaterCalib
6 = PurgeAir
| ****
W
| ****
None
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
15017
| ****
4 15018
| ****
Module 1 Alarm
| ****
Unsigned
Scale 1
| 0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = OverHeat
6 = WaterLeak
7 = Service
8 is Reserved
| 9 = BurnerLocked
10 = FanDefect
11= FailedComm
12 = ChimTempHi
13 = RefillTimeout
14 = FanBlocked
15 = SystBlck
16 = TankBlocked
17 = RefillDelay
| ****
RO
| ****
Normal
15018| 4 15019| Water Probe 1 Auto Calib| Unsigned
Scale 1
| 0 = Off| 1 = On| W| On
15019
| ****
4 15020
| ****
Module 1 Water Level Probe Warning
| Unsigned
Scale 1
| 0= Ok
1= Replace
| ****
RO
| ****
Ok
15020
| ****
4 15021
| ****
Water Level 1 Probe Failure
| Unsigned
Scale 1
| 0 = None
1 = Capacitive
| 2 = Resistive
3 = Both
| ****
RO
| ****
None
15021
| ****
4 15022
| ****
Module 1 Water Level Probe Alarm
| Unsigned
Scale 1
| 0 = Ok
1 = Defect
| ****
2 = NoCalib
| ****
RO
| ****
Ok
15022
| ****
4 15023
| ****
Module 2 State
| ****
Unsigned
Scale 1
| 0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
| 5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
9 = PurgeAir
| ****
RO
| ****
Off
15023
| ****
4 15024
| ****
Module 2 Request
| ****
Unsigned
Scale 1
| 0 = None
1 = Reset Alarms 2 = Drain
| 3 = Reset Counters 4 = Filling
5 = WaterCalib
6 = PurgeAir
| ****
W
| ****
None
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
15024
| ****
4 15025
| ****
Module 2 Alarm
| ****
Unsigned
Scale 1
| 0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = OverHeat
6 = WaterLeak
7 = Service
8 is Reserved
| 9 = BurnerLocked
10 = FanDefect
11= FailedComm
12 = ChimTempHi
13 = RefillTimeout
14 = FanBlocked
15 = SystBlck
16 = TankBlocked
17 = RefillDelay
| ****
RO
| ****
Normal
15025| 4 15026| Water Probe 2 Auto Calib| Unsigned
Scale 1
| 0 = Off| 1 = On| W| On
15026
| ****
4 15027
| ****
Module 2 Water Level Probe Warning
| Unsigned
Scale 1
| 0= Ok
1= Replace
| ****
RO
| ****
Ok
15027
| ****
4 15028
| ****
Water Level 2 Probe Failure
| Unsigned
Scale 1
| 0 = None
1 = Capacitive
| 2 = Resistive
3 = Both
| ****
RO
| ****
None
15028
| ****
4 15029
| ****
Module 2 Water Level Probe Alarm
| Unsigned
Scale 1
| 0 = Ok
1 = Defect
| ****
2 = NoCalib
| ****
RO
| ****
Ok
15029
| ****
4 15030
| ****
Module 3 State
| ****
Unsigned
Scale 1
| 0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
| 5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
9 = PurgeAir
| ****
RO
| ****
Off
15030
| ****
4 15031
| ****
Module 3 Request
| ****
Unsigned
Scale 1
| 0 = None
1 = Reset Alarms 2 = Drain
| 3 = Reset Counters 4 = Filling
5 = WaterCalib
6 = PurgeAir
| ****
W
| ****
None
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
15031
| ****
4 15032
| ****
Module 3 Alarm
| ****
Unsigned
Scale 1
| 0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = OverHeat
6 = WaterLeak
7 = Service
8 is Reserved
| 9 = BurnerLocked
10 = FanDefect
11= FailedComm
12 = ChimTempHi
13 = RefillTimeout
14 = FanBlocked
15 = SystBlck
16 = TankBlocked
17 = RefillDelay
| ****
RO
| ****
Normal
15032| 4 15033| Water Probe 3 Auto Calib| Unsigned
Scale 1
| 0 = Off| 1 = On| W| On
15033
| ****
4 15034
| ****
Module 3 Water Level Probe Warning
| Unsigned
Scale 1
| 0= Ok
1= Replace
| ****
RO
| ****
Ok
15034
| ****
4 15035
| ****
Water Level 3 Probe Failure
| Unsigned
Scale 1
| 0 = None
1 = Capacitive
| 2 = Resistive
3 = Both
| ****
RO
| ****
None
15035
| ****
4 15036
| ****
Module 3 Water Level Probe Alarm
| Unsigned
Scale 1
| 0 = Ok
1 = Defect
| ****
2 = NoCalib
| ****
RO
| ****
Ok
15036
| ****
4 15037
| ****
Module 4 State
| ****
Unsigned
Scale 1
| 0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
| 5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
9 = PurgeAir
| ****
RO
| ****
Off
15037
| ****
4 15038
| ****
Module 4 Request
| ****
Unsigned
Scale 1
| 0 = None
1 = Reset Alarms 2 = Drain
| 3 = Reset Counters 4 = Filling
5 = WaterCalib
6 = PurgeAir
| ****
W
| ****
None
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| ****
Default Value
---|---|---|---|---|---|---
15038
| ****
4 15039
| ****
Module 4 Alarm
| ****
Unsigned
Scale 1
| 0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = OverHeat
6 = WaterLeak
7 = Service
8 is Reserved
| 9 = BurnerLocked
10 = FanDefect
11= FailedComm
12 = ChimTempHi
13 = RefillTimeout
14 = FanBlocked
15 = SystBlck
16 = TankBlocked
17 = RefillDelay
| ****
RO
| ****
Normal
15039| 4 15040| Water Probe 4 Auto Calib| Unsigned
Scale 1
| 0 = Off| 1 = On| W| On
15040
| ****
4 15041
| ****
Module 4 Water Level Probe Warning
| Unsigned
Scale 1
| 0= Ok
1= Replace
| ****
RO
| ****
Ok
15041
| ****
4 15042
| ****
Water Level 4 Probe Failure
| Unsigned
Scale 1
| 0 = None
1 = Capacitive
| 2 = Resistive
3 = Both
| ****
RO
| ****
None
15042
| ****
4 15043
| ****
Module 4 Water Level Probe Alarm
| Unsigned
Scale 1
| 0 = Ok
1 = Defect
| ****
2 = NoCalib
| ****
RO
| ****
Ok
15043| 4 15044| Boiler Fill Mode| Unsigned
Scale 1
| 0 = OneShot| 1 = Pulsed| W| Pulsed
15044
| ****
4 15045
| ****
Boiler Idle Tank Rinse Off
| Unsigned
Scale 1
| ****
0 = Off
| ****
1 = On
| ****
W
| ****
Off
15045
| ****
4 15046
| ****
Boiler Idle Tank Rinse On
| Unsigned
Scale 1
| ****
0 = Off
| ****
1 = On
| ****
W
| ****
Off
15046
| ****
4 15047
| ****
System Mode
| Unsigned
Scale 1
| 0 = Parallel
1 = Sequential
| ****
2 = Hybrid
| ****
W
| ****
Sequential
15047
| ****
415048
| ****
Boiler Startup Tank Rinse
| Unsigned
Scale 1
| ****
0 = Off
| ****
1 = On
| ****
W
| ****
Off
ABOUT COMPANY
- 400 Lebeau blvd, Montreal, Qc, H4N 1R6,
- Canada : www.neptronic.com
- Toll free in North America: 1-800-361-2308
- Tel.: 514-333-1433
- Fax: 514-333-3163
- Customer service fax: 514-333-1091
- Monday to Friday: 8:00am to 5:00pm (Eastern time)
References
- Neptronic | Home - Humidifier Distributor & HVAC Products
- Neptronic | Home - Humidifier Distributor & HVAC Products
Read User Manual Online (PDF format)