VIESSMANN Vitogate 300 Heating Contractor Installation Guide
- June 16, 2024
- VIESSMANN
Table of Contents
Installation and
Service Instructions
for use by heating contractor
Vitogate 300
Communication with heating
systems via BACnet or Modbus
Vitogate 300 Heating Contractor
Certified as a component
part for Viessmann boilers
Product may not be exactly as shown
IMPORTANT
Read and save these instructions for future reference.
Please file in Service Binder
Safety
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
-
Product documentation
Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature, please see section entitled “Important
Regulatory and Safety Requirements”. -
Licensed professional heating contractor
The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor.
Please see section entitled Safety and “Important Regulatory and Installation Requirements”. -
Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins. -
Warranty
Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.
General Information
Important Regulatory and Installation Requirements
Approvals
Viessmann boilers, burners and controls are approved for sale in North America
by CSA International.
Codes
The installation of this unit shall be in accordance with local codes. In the
absence of local codes, use:
- CSA C22.1 Part 1 and/or local codes in Canada
- National Electrical Code ANSI/NFPA 70 in the U.S.
Always use latest editions of codes.
The heating contractor must comply with the Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME CSD-1 where required by the
authority having jurisdiction.
Working on the equipment
The installation, adjustment, service, and maintenance of this product must be
done by a licensed professional heating contractor who is qualified and
experienced in the installation, service, and maintenance of hot water
boilers.
There are no user serviceable parts on the boiler, burner, or control.
Power supply
Install power supply in accordance with the regulations of the authorities
having jurisdiction or, in absence of such requirements, in accordance with
National Codes.
Viessmann recommends the installation of a disconnect switch to the 120V power
supply outside of the boiler room.
Ensure main power supply to equipment, the heating system, and all external
controls have been deactivated.
Close main oil or gas supply valve. Take precautions in both instances to
avoid accidental activation of power during service work.
Please carefully read this manual prior to attempting installation. Any
warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry,
please reference documentation of the respective product.
We offer frequent installation and service seminars to familiarize our
partners with our products. Please inquire.
The completeness and functionality of field supplied electrical controls and
components must be verified by the heating contractor. These include low water
cut-offs, flow switches (if used), staging controls, pumps, motorized valves,
air vents, thermostats, etc.
| WARNING
---|---
Turn off electric power supply before servicing. Contact with live electric
components can cause shock or loss of life.
Installation
About these Installation Instructions
** Take note of all symbols and notations intended to draw attention to
potential hazards or important product information.
WARNING
Warnings draw your attention to the presence of potential hazards or important
product information.
CAUTION
Cautions draw your attention to the presence of potential hazards or important
product information.
IMPORTANT**
Indicates an imminently hazardous situation which, if not avoided, could
result in death, serious injury or substantial product/property damage.
Indicates an imminently hazardous situation which, if not avoided, may result
in minor injury or product / property damage.
Helpful hints for installation, operation or maintenance which pertain to the
product.
This symbol indicates to note additional information
This symbol indicates that other instructions must be referenced.
Preparing for Installation
Intended use
Install and operate Vitogate products as intended in conjunction with the
electronic control units and controllers for the Viessmann heat and power
generators designed for this system, giving due consideration to the
associated installation, service and operating
instructions. In particular, observe the current and voltage specifications
for connections and hook-ups.
Use of the Vitogate products are exclusively for monitoring, operating and
optimizing systems with the user and communication interfaces specified for
this purpose in the relevant printed documentation.
In the case of communication interfaces, ensure on site that the system
requirements specified in the product documentation are met at all times for
every transfer medium employed. Only use the specified components for the
mains power supply (e.g. mains power adaptors).
Product information
The Vitogate 300, type BN/MB gateway is designed to integrate the Vitotronic
control units using the integral LON communication module (accessory*) to
BACnet or Modbus control systems. For supported appliances/ devices and
further information, see www.vitogate.info. The
Vitogate 300, type BN/MB must be integrated into the BACnet or Modbus control
system by an authorized contractor.
- Depending on the relevant control, this may be an additional accessory item.
Functions
The Vitogate 300, type BN/MB enables system users to utilize the following
functions in conjunction with a BACnet or Modbus control system:
- Adjustment of the heating system operating states (standby/heating mode)
- Setting heating system parameters (temperature setpoint)
- Relaying fault and error messages
Legend
A Power supply unit
B Vitogate 300
Vitogate 300, type BN/MB and its power supply unit are suitable for mounting on a DIN rail (TS35 Top Hat Rail 35 mm x 15 mm or 35 mm x 7.5 mm).
Wall Mounting (with enclosure) Legend
A Module enclosure (complete with a Vitogate 300 and power supply unit)
B Enclosure cover
C Wall anchors (field supplied)
D Mounting screws (field supplied)
Power Supply Connections for Wall Mounting (with enclosure)
WARNING
Incorrect core allocation can result in serious injury and damage to the
appliance. Take care not to interchange wires “L” and “N”
Power supply independent of the mains isolator
When the heating system is switched off via the mains isolator, the Vitogate
300 remains on, while the Vitotronic control unit is switched off.
No data is transferred to the BACnet or Modbus control system. Legend
A Vitogate 300
B Power supply 100 to 240V~, 45 to 65 Hz
C Mains isolator
D Power supply unit
E RS 485 connection: Interface for BACnet MS/TP or Modbus RS 485
F 24V power supply connection
The enclosure mounted version comes with a pre-wired power supply unit which includes connection to the Vitogate 300 module and a standard 3 prong AC plug.
CM2 Junction Box DIN Rail Mounting
-
Measure to allow for clearances as shown, than use the DIN rail as a template to mark and centre punch hole locations.
-
Drill two holes Ø3 /16 in. Legend
A Junction box side DIN rail 3 in. (75 mm)
B Power supply unit
C Vitogate 300
D Junction box main DIN rail -
Mount the DIN rail A with the mounting hardware to the inside of the junction box as shown.
-
Mount the Vitogate 300 C to junction box side DIN rail A and mount the power supply unit B to the junction box main DIN rail D.
Power Supply Connections for CM2 Junction Box
-
Connect the 24VDC power supply cable (supplied) to the power supply unit, with the red or brown wire to the +terminal and the black or blue wire to the – terminal as shown.
-
Connect the other end of the 24VDC power supply cable (supplied), into the Vitogate 300, with the red or brown wire to the +24 terminal and the black or blue wire to the GND terminal as shown.
Note: The power supply plug in the Vitogate 300 can be easily removed to aid with wiring connection. -
Make a connection from the power supply unit L and N connections to any vacant L and N connections of the junction box terminals 14 thru 17.
Power supply via the mains isolator
When the heating system is switched off via the mains isolator, the Vitogate
300 and the Vitotronic control unit are also switched off.
No data is transferred to the BACnet or Modbus control system. Legend
A Vitogate 300
B Power supply unit
C RS 485 connection: Interface for BACnet MS/TP or Modbus RS 485
D Junction box main DIN rail
E Junction box side DIN rail
F Junction box
WARNING
Incorrect core allocation can result in serious injury and damage to the
appliance. Take care not to interchange wires “L” and “N”
For more details refer to the Installation and Service Instructions applicable
to the boiler.
Vitogate and Power Supply Mounting Location for CA3/CA3B
- Mount the Vitogate 300 B to junction box main DIN rail C and mount the power supply unit A to the junction box main DIN rail C.
Power Supply Connections for CA3/CA3B Legend
A Vitogate 300
B Power supply unit
C RS 485 connection: Interface for BACnet MS/TP or Modbus RS 485
D Ancillary DIN rail (within Vitotronic 300 GW6C housing)
E External accessories DIN rail
1 Red or brown wire
2 Black or blue wire
3 Black or blue wire
4 Red or brown wire
-
Connect the 24VDC power supply cable (supplied) to the power supply unit, with the red or brown wire to the +terminal and the black or blue wire to the – terminal as shown.
-
Connect the other end of the 24VDC power supply cable (supplied), into the Vitogate 300, with the red or brown wire to the +24 terminal and the black or blue wire to the GND terminal as shown.
Note: The power supply plug in the Vitogate 300 can be easily removed to aid with wiring connection. -
Make a connection from the power supply unit L and N connections to any vacant L and N connections of the junction box terminals 12 thru 14.
Power supply via the mains isolator When the heating system is switched off via the mains isolator, the Vitogate 300 and the Vitotronic control unit are also switched off.
No data is transferred to the BACnet or Modbus control system.
**** WARNING
Incorrect core allocation can result in serious injury and damage to the
appliance. Take care not to interchange wires “L” and “N”
For more details refer to the Installation and Service Instructions applicable
to the boiler.
Connections
Power Supply
WARNING
Incorrectly executed electrical installations can result in injuries from
electrical current and in equipment damage. Direct power supply
Connect the power supply (if required) and implement all grounding measures
(e.g. RCD circuit) in accordance with the following regulations:
- In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction.
- Connection requirements specified by your local power supply utility
- Protect the power cable with max. 12A
IMPORTANT
Protect the Vitogate 300 power cable with the appropriate fuse.
Isolators for non-grounded conductors
- The mains isolator (if installed) must simultaneously isolate all non-grounded conductors from the mains.
- If no mains isolator is installed, all non grounded conductors must be isolated from the mains by the upstream circuit breaker.
WARNING
The absence of component grounding in the system can lead to serious injury
from electrical current if an electrical fault occurs. Connect the appliance
and pipework to the equipotential bonding of the building in question.
WARNING
Incorrect core allocation can result in serious injury and damage to the
appliance. Never interchange cores “L” and “N”.
CAUTION
An incorrect phase sequence can cause damage to the appliance. Check for phase
equality with the power supply connection of the control unit.
Connection Diagram
Legend
LON status Illuminates green
RX Flashes yellow: Device receives data.
TX Flashes yellow: Device sends data.
Power Illuminates green: Power ON, operating voltage ‘live’
Status* Multi color status LED: red, green, orange
A DIP switch:
1 – Bias voltage for RS 485 interface
2 – Bias voltage for RS 485 interface 3-120Ωterminator
B RS 485 connection: Interface for BACnet MS/TP or Modbus RS 485 (this plug in the Vitogate 300 can be easily removed to aid with wiring connection).
C Power supply connection 24VDC
D LAN connection with PC/Laptop or BACnet IP or Modbus TCP/IP
E LON connection, 2 piece RJ 45 sockets, screened
F USB connection for software updates
Illuminates green | Reset is being held down |
---|---|
Flashes green | Standard operation |
Flashes green/red | DHCP server enabled |
Illuminates orange | Indication during re-start |
Flashes orange | Indication following the start phase when there is no gateway |
configuration
Flashes red| Indication in the case of BUS errors in the MS/TP network (e.g.
framing errors)
Illuminates red| Indication prior to a reset while files are being connected.
Making the LON Connection
The Viessmann LON is designed for “Line” BUS topology with a terminal end
resistor at both ends (accessories). Further information can be found in the
“Viessmann LON manual”; see www.viessmann.de/lon.
The transfer distances for LON are subject to the electrical properties of the
respective cable. For this reason, only use the specified cable types. Use
only one cable type
within each LON.
Cable types (on site):
- 2-core cable, CAT5, screened
- JY(St)Y 2 x 2 x 0.8 mm (telephone cable)
Observe the cabling requirements for the operation of the LON interface FTT 10-A (see www.echelon.com).
All Viessmann appliances are connected with RJ45 connectors. The Viessmann LON
always requires cores “1” and “2” plus the screen. The cores are
interchangeable.
The installation is therefore reverse polarity protected.
Note: When connecting devices and routing cables, observe the relevant
safety requirements. Ensure the safe electrical separation of all on-site
components (including PC/laptops).
Connection with LON cable
Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D LON cable, 23 ft. (7 m) long
Connection with LON cable and LON coupling
Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D LON cable, 23 ft. (7 m) long: Max. 3 cables between 2 devices
E LON extension jack
Connection with on-site cable and LON plug Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D RJ45 male plug end
E On-site cable (field supplied)
F Up to 99 participants
Connection with LON cable, on-site cable and LON socket
Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D LON cable, 23 ft. (7 m) long
E On-site cable (field supplied)
F LON sockets
G Up to 99 participants
Commissioning
Integrating the Vitotronic Control Unit into LON
The LON communication module (accessory*) must be installed into the Vitotronic control unit.
- Depending on the relevant control, this may be an additional accessory item.
Note: The data transfer via LON can take several minute
LON system number and participant number
Set LON system number, LON participant number and further functions via code
- Refer to the relevant Vitotronic control unit Service Instructions and the
following table.
Note: In the same LON system, each number an only be allocated once.
Only one Vitotronic control unit per system may be programmed as the fault manager.
Example: Single boiler system with Vitotronic 300, Vitotronic 200-H heating circuit control unit downstream and Vitogate 300, type BN/MB
Participant no. 1
Code “77:1”| Participant no. 10
Code “77:10”| Delivered condition Vitogate 300: Participant no. 97
---|---|---
Control unit is fault manager
Code “79:1”| Control unit is not fault manager.
Code “79:0”| Device is fault manager.
Viessmann system number
Code “98:1”| Viessmann system number
Code “98:1”| —
LON participant fault monitoring
Code “9C:20”| LON participant fault monitoring
Code “9C:20”| —
Updating LON Participant List
Refer to the relevant Vitotronic control unit Installation and Service
Instructions.
Carrying out Participant Check
Refer to the relevant Vitotronic control unit Installation and Service
Instructions.
Devices required for commissioning:
-
PC/laptop with the following equipment:
– Minimum monitor resolution 1024 x 768
– Integral or external Ethernet network module
– PDF Reader -
Supported web browsers:
– MS Internet Explorer V 7 or higher
– Mozilla Firefox V 2 or higher
– Mobile Safari V 3.1 or higher
– Google Chrome V 18.0 or higher -
Twisted pair network cable
Enabling the DHCP server
Dynamic Host Configuration Protocol (DHCP) makes IP addresses available to
clients on request.
If the computer has been set up as DHCP client (standard setting), the DHCP
server of the Vitogate 300 can be used to provide an IP address.
Hold down the reset button on the Vitogate 300 for at least 5 sec, but no
longer than 10 sec.
The DHCP server has been enabled once the LED LON status flashes green/red
alternately.
Note: The DHCP server does not need to be enabled if a manual IP address
is to be used.
Creating an Ethernet network
Connect the computer network module by means of a twisted pair network cable
with the RJ45 connection of the Vitogate 300.
Creating a connection with the Vitogate 300 configuration webserver
An IP address is automatically assigned to the computer if the DHCP server has
been enabled.
If a manual IP address is to be used, make the following settings on the
computer:
- IP address: 169.254.0.2 (or higher)
- Subnet mask: 255.255.0.0
- Standard gateway: Leave blank.
For Vitogate 300 equipped with firmware patch, to access the webserver requires the additional step of pressing and holding the reset button for 2 seconds (location of reset button can be found on page 12). The web server will then remain active for 30 minutes, when the 30 minutes expires access to the webserver will be disabled.
Calling up the Vitogate 300 configuration webserver
Open the Vitogate 300 configuration screens:
Start web browser:
- Enter IP address 169.254.0.1 into the address line.
- User name: vitogate
- Password: viessmann\
You can change the password later.
The gateway default screen is called up.
Note: The configuration screens are described in the integral Vitogate
300 online help.
Parts List
Parts
0001 Replacement module
0002 LON connecting cable, 7m RJ45
0003 Power module, 120-240/24V
0005 Harness, power 24V
0006 Technical Literature Set
Other Parts (not illustrated)
0100 Accessory pack, DIN rail and fasteners 1
0101 Power cable, 120/1/60 2m 2
0103 Installation/Service Instructions
0104 Online Help Guide
0105 Parts List
1 Only for Vitogate 7559705 for Vitocrossal 200.
2 Only for Vitogate 7559706 compact wall-mount unit.
Specifications
Vitogate 300, Type BN/MB
Mains voltage | 12 to 24V AC/DC |
---|---|
Power consumption | Max. 320 mA |
Rated output | Max. 3.85 W |
Frequency range | 47 to 63 Hz |
Permiss. ambient temperature
– During operation 32 to 113°F (0 to 45°C)
– During transport and storage| 32 to 113°F (0 to 45°C)
14 to 149°F (−10 to +65°C)
Permiss. humidity
– During operation 20 to 80%
– During storage and transport| 20 to 80% relative humidity, non-condensing
10 to 85% relative humidity, non-condensing
Dimensions (height x width x depth)| 4 x 2 x 2.75 in. (100 x 48 x 70 mm)
Installation| DIN rail (TS35 Top Hat Rail 35 mm x 15 mm or 35 mm x 7.5 mm)
Power supply unit| STEP-PS 1AC/24DC 0.75/FL.
Power Supply Unit
Rated voltage | 100 to 240V~ |
---|---|
Rated frequency | 45 to 65 Hz |
Output voltage | 24VDC ±1% |
Output current max. | 1.4A |
Permiss. ambient temperature
– Operation > 131°F (> 55°C) line loss
– Storage and transport| -13 to 158°F (–25 to +70°C)
-40 to 185°F (−40 to +85°C)
Max. humidity| 95% relative humidity at 77°F (25°C), non-condensing
Dimensions (height x width x depth)| 6 x 1.4 x 1.7 in. (150 x 36 x 43 mm)
(TS35 Top Hat Rail 35 mm x 15 mm or 35 mm x 7.5 mm)| DIN rail (TS35 Top Hat
Rail 35 mm x 15 mm or 35 mm x 7.5 mm)
Scan for digital copy of this document
http://www.vitoteam.com/docs/?id=5672437&doc=IS&s=VITOGATE300&src=QR
Viessmann Manufacturing Company Inc.
750 McMurray Road
Waterloo, Ontario e N2V 2G5 e Canada
Techinfo Line 1-888-484-8643
1-800-387-7373 © Fax
519-885-0887
www.viessmann.ca
info@viessmann.ca
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island e 02886 « USA
Techinfo Line 1-844-649-5886
1-800-288-0667 © Fax
401-732-0590
www.viessmann-us.com
info@viessmann-us.com
Printed on environmentally friendly
(recycled and recyclable) paper.
Technical information subject to change without notice.
5672 437 – 05