VIESSMANN Vitogate 300 Heating Contractor Installation Guide

June 16, 2024
VIESSMANN

Installation and
Service Instructions
for use by heating contractor
Vitogate 300
Communication with heating
systems via BACnet or Modbus

Vitogate 300 Heating Contractor

VIESSMANN Vitogate 300 Heating Contractor Certified as a component
part for Viessmann boilers

Product may not be exactly as shown
IMPORTANT
Read and save these instructions for future reference.
Please file in Service Binder

Safety

Safety, Installation and Warranty Requirements

Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).

  • Product documentation
    Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
    For a listing of applicable literature, please see section entitled “Important
    Regulatory and Safety Requirements”.

  • Licensed professional heating contractor
    The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor.
    Please see section entitled Safety and “Important Regulatory and Installation Requirements”.

  • Advice to owner
    Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins.

  • Warranty
    Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.

General Information

Important Regulatory and Installation Requirements

Approvals
Viessmann boilers, burners and controls are approved for sale in North America by CSA International.
Codes
The installation of this unit shall be in accordance with local codes. In the absence of local codes, use:

  • CSA C22.1 Part 1 and/or local codes in Canada
  • National Electrical Code ANSI/NFPA 70 in the U.S.

Always use latest editions of codes.
The heating contractor must comply with the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1 where required by the authority having jurisdiction.
Working on the equipment
The installation, adjustment, service, and maintenance of this product must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers.
There are no user serviceable parts on the boiler, burner, or control.
Power supply
Install power supply in accordance with the regulations of the authorities having jurisdiction or, in absence of such requirements, in accordance with National Codes.
Viessmann recommends the installation of a disconnect switch to the 120V power supply outside of the boiler room.
Ensure main power supply to equipment, the heating system, and all external controls have been deactivated.
Close main oil or gas supply valve. Take precautions in both instances to avoid accidental activation of power during service work.

Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.

| WARNING
---|---
Turn off electric power supply before servicing. Contact with live electric components can cause shock or loss of life.

Installation

About these Installation Instructions

** Take note of all symbols and notations intended to draw attention to potential hazards or important product information.
WARNING
Warnings draw your attention to the presence of potential hazards or important product information.
CAUTION
Cautions draw your attention to the presence of potential hazards or important product information.
IMPORTANT**

Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage.
Helpful hints for installation, operation or maintenance which pertain to the product.
This symbol indicates to note additional information
 This symbol indicates that other instructions must be referenced.

Preparing for Installation

Intended use
Install and operate Vitogate products as intended in conjunction with the electronic control units and controllers for the Viessmann heat and power generators designed for this system, giving due consideration to the associated installation, service and operating
instructions. In particular, observe the current and voltage specifications for connections and hook-ups.
Use of the Vitogate products are exclusively for monitoring, operating and optimizing systems with the user and communication interfaces specified for this purpose in the relevant printed documentation.
In the case of communication interfaces, ensure on site that the system requirements specified in the product documentation are met at all times for every transfer medium employed. Only use the specified components for the mains power supply (e.g. mains power adaptors).

Product information
The Vitogate 300, type BN/MB gateway is designed to integrate the Vitotronic control units using the integral LON communication module (accessory*) to BACnet or Modbus control systems. For supported appliances/ devices and further information, see www.vitogate.info. The Vitogate 300, type BN/MB must be integrated into the BACnet or Modbus control system by an authorized contractor.

  • Depending on the relevant control, this may be an additional accessory item.

Functions
The Vitogate 300, type BN/MB enables system users to utilize the following functions in conjunction with a BACnet or Modbus control system:

  • Adjustment of the heating system operating states (standby/heating mode)
  • Setting heating system parameters (temperature setpoint)
  • Relaying fault and error messages

VIESSMANN Vitogate 300 Heating Contractor - mains
powerLegend
A Power supply unit
B Vitogate 300

Vitogate 300, type BN/MB and its power supply unit are suitable for mounting on a DIN rail (TS35 Top Hat Rail 35 mm x 15 mm or 35 mm x 7.5 mm).

Wall Mounting (with enclosure)VIESSMANN Vitogate 300 Heating Contractor -
Wall Mounting Legend
A Module enclosure (complete with a Vitogate 300 and power supply unit)
B Enclosure cover
C Wall anchors (field supplied)
D Mounting screws (field supplied)

Power Supply Connections for Wall Mounting (with enclosure)

WARNING
Incorrect core allocation can result in serious injury and damage to the appliance. Take care not to interchange wires “L” and “N”

Power supply independent of the mains isolator
When the heating system is switched off via the mains isolator, the Vitogate 300 remains on, while the Vitotronic control unit is switched off.
No data is transferred to the BACnet or Modbus control system.VIESSMANN
Vitogate 300 Heating Contractor - Wall Mounting 1 Legend
A Vitogate 300
B Power supply 100 to 240V~, 45 to 65 Hz
C Mains isolator
D Power supply unit
E RS 485 connection: Interface for BACnet MS/TP or Modbus RS 485
F 24V power supply connection

The enclosure mounted version comes with a pre-wired power supply unit which includes connection to the Vitogate 300 module and a standard 3 prong AC plug.

CM2 Junction Box DIN Rail MountingVIESSMANN Vitogate 300 Heating
Contractor - Rail Mounting

  1. Measure to allow for clearances as shown, than use the DIN rail as a template to mark and centre punch hole locations.

  2. Drill two holes Ø3 /16 in.VIESSMANN Vitogate 300 Heating Contractor - Rail Mounting 1 Legend
    A Junction box side DIN rail 3 in. (75 mm)
    B Power supply unit
    C Vitogate 300
    D Junction box main DIN rail

  3. Mount the DIN rail A with the mounting hardware to the inside of the junction box as shown.

  4. Mount the Vitogate 300 C to junction box side DIN rail A and mount the power supply unit B to the junction box main DIN rail D.

Power Supply Connections for CM2 Junction Box

  1. Connect the 24VDC power supply cable (supplied) to the power supply unit, with the red or brown wire to the +terminal and the black or blue wire to the – terminal as shown.

  2. Connect the other end of the 24VDC power supply cable (supplied), into the Vitogate 300, with the red or brown wire to the +24 terminal and the black or blue wire to the GND terminal as shown.
    Note: The power supply plug in the Vitogate 300 can be easily removed to aid with wiring connection.

  3. Make a connection from the power supply unit L and N connections to any vacant L and N connections of the junction box terminals 14 thru 17.

Power supply via the mains isolator
When the heating system is switched off via the mains isolator, the Vitogate 300 and the Vitotronic control unit are also switched off.
No data is transferred to the BACnet or Modbus control system.VIESSMANN
Vitogate 300 Heating Contractor - Rail Mounting 3 Legend
A Vitogate 300
B Power supply unit
C RS 485 connection: Interface for BACnet MS/TP or Modbus RS 485
D Junction box main DIN rail
E Junction box side DIN rail
F Junction box

WARNING
Incorrect core allocation can result in serious injury and damage to the appliance. Take care not to interchange wires “L” and “N”
For more details refer to the Installation and Service Instructions applicable to the boiler.

Vitogate and Power Supply Mounting Location for CA3/CA3BVIESSMANN
Vitogate 300 Heating Contractor - Rail Mounting 4

  1. Mount the Vitogate 300 B to junction box main DIN rail C and mount the power supply unit A to the junction box main DIN rail C.

Power Supply Connections for CA3/CA3BVIESSMANN Vitogate 300 Heating
Contractor - Rail Mounting 5 Legend
A Vitogate 300
B Power supply unit
C RS 485 connection: Interface for BACnet MS/TP or Modbus RS 485
D Ancillary DIN rail (within Vitotronic 300 GW6C housing)
E External accessories DIN rail
1 Red or brown wire
2 Black or blue wire
3 Black or blue wire
4 Red or brown wire

  1. Connect the 24VDC power supply cable (supplied) to the power supply unit, with the red or brown wire to the +terminal and the black or blue wire to the – terminal as shown.

  2. Connect the other end of the 24VDC power supply cable (supplied), into the Vitogate 300, with the red or brown wire to the +24 terminal and the black or blue wire to the GND terminal as shown.
    Note: The power supply plug in the Vitogate 300 can be easily removed to aid with wiring connection.

  3. Make a connection from the power supply unit L and N connections to any vacant L and N connections of the junction box terminals 12 thru 14.
    Power supply via the mains isolator When the heating system is switched off via the mains isolator, the Vitogate 300 and the Vitotronic control unit are also switched off.
    No data is transferred to the BACnet or Modbus control system.

**** WARNING
Incorrect core allocation can result in serious injury and damage to the appliance. Take care not to interchange wires “L” and “N”
For more details refer to the Installation and Service Instructions applicable to the boiler.

Connections

Power Supply
WARNING
Incorrectly executed electrical installations can result in injuries from electrical current and in equipment damage. Direct power supply
Connect the power supply (if required) and implement all grounding measures (e.g. RCD circuit) in accordance with the following regulations:

  • In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction.
  • Connection requirements specified by your local power supply utility
  • Protect the power cable with max. 12A

IMPORTANT
Protect the Vitogate 300 power cable with the appropriate fuse.

Isolators for non-grounded conductors

  • The mains isolator (if installed) must simultaneously isolate all non-grounded conductors from the mains.
  • If no mains isolator is installed, all non grounded conductors must be isolated from the mains by the upstream circuit breaker.

WARNING
The absence of component grounding in the system can lead to serious injury from electrical current if an electrical fault occurs. Connect the appliance and pipework to the equipotential bonding of the building in question.
WARNING
Incorrect core allocation can result in serious injury and damage to the appliance. Never interchange cores “L” and “N”.
CAUTION
An incorrect phase sequence can cause damage to the appliance. Check for phase equality with the power supply connection of the control unit.

Connection DiagramVIESSMANN Vitogate 300 Heating Contractor -
Connection Diagram

Legend

LON status  Illuminates green

RX  Flashes yellow: Device receives data.

TX  Flashes yellow: Device sends data.

Power  Illuminates green: Power ON, operating   voltage ‘live’

Status*  Multi color status LED: red, green, orange

A DIP switch:

 1 – Bias voltage for RS 485 interface

 2 – Bias voltage for RS 485 interface 3-120Ωterminator

B RS 485 connection: Interface for BACnet MS/TP or   Modbus RS 485 (this plug in the Vitogate 300    can be easily removed to aid with wiring connection).

C Power supply connection 24VDC

D LAN connection with PC/Laptop or BACnet IP or  Modbus TCP/IP

E  LON connection, 2 piece RJ 45 sockets, screened

F USB connection for software updates

Illuminates green Reset is being held down
Flashes green Standard operation
Flashes green/red DHCP server enabled
Illuminates orange Indication during re-start
Flashes orange Indication following the start phase when there is no gateway

configuration
Flashes red| Indication in the case of BUS errors in the MS/TP network (e.g. framing errors)
Illuminates red| Indication prior to a reset while files are being connected.

Making the LON Connection

The Viessmann LON is designed for “Line” BUS topology with a terminal end resistor at both ends (accessories). Further information can be found in the “Viessmann LON manual”; see www.viessmann.de/lon.
The transfer distances for LON are subject to the electrical properties of the respective cable. For this reason, only use the specified cable types. Use only one cable type
within each LON.
Cable types (on site):

  • 2-core cable, CAT5, screened
  • JY(St)Y 2 x 2 x 0.8 mm (telephone cable)

Observe the cabling requirements for the operation of the LON interface FTT 10-A (see www.echelon.com).

All Viessmann appliances are connected with RJ45 connectors. The Viessmann LON always requires cores “1” and “2” plus the screen. The cores are interchangeable.
The installation is therefore reverse polarity protected.
Note: When connecting devices and routing cables, observe the relevant safety requirements. Ensure the safe electrical separation of all on-site components (including PC/laptops).

Connection with LON cableVIESSMANN Vitogate 300 Heating Contractor -
Making the LON Connection 1 Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D LON cable, 23 ft. (7 m) long
Connection with LON cable and LON coupling
Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D LON cable, 23 ft. (7 m) long: Max. 3 cables between 2 devices
E LON extension jack
Connection with on-site cable and LON plugVIESSMANN Vitogate 300 Heating
Contractor - Making the LON Connection 2 Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D RJ45 male plug end
E On-site cable (field supplied)
F Up to 99 participants
Connection with LON cable, on-site cable and LON socket
VIESSMANN Vitogate 300 Heating Contractor - Making the LON Connection
3 Legend
A Vitotronic control unit
B Vitogate 300
C Terminal end resistor
D LON cable, 23 ft. (7 m) long
E On-site cable (field supplied)
F LON sockets
G Up to 99 participants

Commissioning

Integrating the Vitotronic Control Unit into LON

The LON communication module (accessory*) must be installed into the Vitotronic control unit.

  • Depending on the relevant control, this may be an additional accessory item.
    Note: The data transfer via LON can take several minute
    LON system number and participant number
    Set LON system number, LON participant number and further functions via code
  1. Refer to the relevant Vitotronic control unit Service Instructions and the following table.
    Note: In the same LON system, each number an only be allocated once.
    Only one Vitotronic control unit per system may be programmed as the fault manager.

Example: Single boiler system with Vitotronic 300, Vitotronic 200-H heating circuit control unit downstream and Vitogate 300, type BN/MBVIESSMANN Vitogate 300 Heating Contractor - Making the LON Connection
4

Participant no. 1
Code “77:1”| Participant no. 10
Code “77:10”| Delivered condition Vitogate 300: Participant no. 97
---|---|---
Control unit is fault manager
Code “79:1”| Control unit is not fault manager.
Code “79:0”| Device is fault manager.
Viessmann system number
Code “98:1”| Viessmann system number
Code “98:1”| —
LON participant fault monitoring
Code “9C:20”| LON participant fault monitoring
Code “9C:20”| —

Updating LON Participant List
Refer to the relevant Vitotronic control unit Installation and Service Instructions.
Carrying out Participant Check
Refer to the relevant Vitotronic control unit Installation and Service Instructions.

Devices required for commissioning:

  • PC/laptop with the following equipment:
    – Minimum monitor resolution 1024 x 768
    – Integral or external Ethernet network module
    – PDF Reader

  • Supported web browsers:
    – MS Internet Explorer V 7 or higher
    – Mozilla Firefox V 2 or higher
    – Mobile Safari V 3.1 or higher
    – Google Chrome V 18.0 or higher

  • Twisted pair network cable

Enabling the DHCP server
Dynamic Host Configuration Protocol (DHCP) makes IP addresses available to clients on request.
If the computer has been set up as DHCP client (standard setting), the DHCP server of the Vitogate 300 can be used to provide an IP address.
Hold down the reset button on the Vitogate 300 for at least 5 sec, but no longer than 10 sec.
The DHCP server has been enabled once the LED LON status flashes green/red alternately.
Note: The DHCP server does not need to be enabled if a manual IP address is to be used.

Creating an Ethernet network
Connect the computer network module by means of a twisted pair network cable with the RJ45 connection of the Vitogate 300.
Creating a connection with the Vitogate 300 configuration webserver
An IP address is automatically assigned to the computer if the DHCP server has been enabled.
If a manual IP address is to be used, make the following settings on the computer:

  • IP address: 169.254.0.2 (or higher)
  • Subnet mask: 255.255.0.0
  • Standard gateway: Leave blank.

For Vitogate 300 equipped with firmware patch, to access the webserver requires the additional step of pressing and holding the reset button for 2 seconds (location of reset button can be found on page 12). The web server will then remain active for 30 minutes, when the 30 minutes expires access to the webserver will be disabled.

Calling up the Vitogate 300 configuration webserver
Open the Vitogate 300 configuration screens:
Start web browser:

  • Enter IP address 169.254.0.1 into the address line.
  • User name: vitogate
  • Password: viessmann\

You can change the password later.
The gateway default screen is called up.
Note: The configuration screens are described in the integral Vitogate 300 online help.

Parts List

Parts
0001 Replacement module
0002 LON connecting cable, 7m RJ45
0003 Power module, 120-240/24V
0005 Harness, power 24V
0006 Technical Literature Set
Other Parts (not illustrated)
0100 Accessory pack, DIN rail and fasteners 1
0101 Power cable, 120/1/60 2m
2
0103 Installation/Service Instructions
0104 Online Help Guide
0105 Parts List
1 Only for Vitogate 7559705 for Vitocrossal 200.
2 Only for Vitogate 7559706 compact wall-mount unit.VIESSMANN Vitogate 300 Heating Contractor - Making the LON Connection 5

Specifications

Vitogate 300, Type BN/MB

Mains voltage 12 to 24V AC/DC
Power consumption Max. 320 mA
Rated output Max. 3.85 W
Frequency range 47 to 63 Hz

Permiss. ambient temperature
– During operation 32 to 113°F (0 to 45°C)
– During transport and storage| 32 to 113°F (0 to 45°C)
14 to 149°F (−10 to +65°C)
Permiss. humidity
– During operation 20 to 80%
– During storage and transport| 20 to 80% relative humidity, non-condensing
10 to 85% relative humidity, non-condensing
Dimensions (height x width x depth)| 4 x 2 x 2.75 in. (100 x 48 x 70 mm)
Installation| DIN rail (TS35 Top Hat Rail 35 mm x 15 mm or 35 mm x 7.5 mm)
Power supply unit| STEP-PS 1AC/24DC 0.75/FL.

Power Supply Unit

Rated voltage 100 to 240V~
Rated frequency 45 to 65 Hz
Output voltage 24VDC ±1%
Output current max. 1.4A

Permiss. ambient temperature
– Operation > 131°F (> 55°C) line loss
– Storage and transport| -13 to 158°F (–25 to +70°C)
-40 to 185°F (−40 to +85°C)
Max. humidity| 95% relative humidity at 77°F (25°C), non-condensing
Dimensions (height x width x depth)| 6 x 1.4 x 1.7 in. (150 x 36 x 43 mm)
 (TS35 Top Hat Rail 35 mm x 15 mm or 35 mm x 7.5 mm)| DIN rail  (TS35 Top Hat Rail 35 mm x 15 mm or 35 mm x 7.5 mm)

VIESSMANN Vitogate 300 Heating Contractor - Making the LON Connection
6Scan for digital copy of this document

http://www.vitoteam.com/docs/?id=5672437&doc=IS&s=VITOGATE300&src=QR

Viessmann Manufacturing Company Inc.
750 McMurray Road
Waterloo, Ontario e N2V 2G5 e Canada
Techinfo Line 1-888-484-8643
1-800-387-7373 © Fax 519-885-0887
www.viessmann.ca
info@viessmann.ca
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island e 02886 « USA
Techinfo Line 1-844-649-5886
1-800-288-0667 © Fax 401-732-0590
www.viessmann-us.com
info@viessmann-us.com
Printed on environmentally friendly
(recycled and recyclable) paper.
Technical information subject to change without notice.
5672 437 – 05