global sources 4T11GB-15PB Series High Performance Frequency Inverter User Manual

June 16, 2024
global sources

series inverter user manual

Product Information

2.1 Model Description

2.3 Description of Nameplate

2.3 Selection Guide

**** Model| Output capacity KVA| Input current A| Output current A| Suitable Motor
---|---|---|---|---
KW| HP
4T11GB/15PB| 17.0| 26.0| 25/32| 11/15| 15/20
4T15GB/18.5PB| 21.0| 35.0| 32/37| 15/18.5| 20/25
4T18.5G/22P| 24.0| 38.5| 37/45| 18.5/22| 25/30
4T22G/30P| 30.0| 46.5| 45/60| 22/30| 30/40
---|---|---|---|---|---
4T30G/37P| 40.0| 62.0| 60/75| 30/37| 40/45
4T37G/45P| 57.0| 76.0| 75/91| 37/45| 50/60
4T45G/55P| 69.0| 92.0| 91/112| 45/55| 60/70
4T55G/75P| 85.0| 113.0| 112/150| 55/75| 70/100
4T75G/93P| 114.0| 157.0| 150/176| 75/93| 100/125
4T93G/110P| 134.0| 180.0| 176/210| 90/110| 125/150
P110G/132P| 160.0| 214.0| 210/253| 110/132| 150/175
4T132G/160P| 192.0| 256.0| 253/304| 132/160| 175/210
4T160G/185P| 231.0| 307.0| 304/340| 160/185| 210/260
4T185G/200P| 242.0| 350.0| 340/377| 185/200| 240/260
4T200G/220P| 250.0| 385.0| 377/426| 200/220| 260/300
4T220G/250P| 280.0| 430.0| 426/465| 220/250| 300/350
4T250G/280P| 355.0| 468.0| 465/520| 250/280| 350/370
4T280G/315P| 396.0| 525.0| 520/585| 280/315| 370/420
4T315G/350P| 445.0| 590.0| 585/650| 315/355| 420/460
4T350G/400P| 500.0| 665.0| 650/725| 355/400| 460/530
4T400G/450P| 565.0| 785.0| 725/800| 400/450| 530/600
4T450G/500P| 630.0| 883.0| 800/860| 450/500| 600/670
4T500G/560P| 750.0| 950.0| 860/950| 500/560| 670/750
4T560G/630P| 840.0| 1000.0| 950/1260| 560/630| 750/840

2.4 Technical Specifications

Items Specification




















****  Basic  functions

| Maximum output frequency| Vector control mode: 0~500Hz V/f control mode: 0~500Hz
Carrier frequency| 0.5~16.0kHz, automatically adjusted according to load characteristics.
Frequency accuracy| Digital setting: 0.01Hz
Analog setting: maximum frequency * 0.025
Control mode| V/f control
Sensorless vector control (SVC) Close-loop vector control (FVC)
Operation command mode| Keypad control Terminal control
Serial communication control (Modbus)
Starting torque| G model: 0.5Hz/150% (SVC); 0Hz/180% (FVC)
P model: 0.5Hz/100%
Speed control precision| ±0.5% (SVC)
±0.02% (FVC)
Torque control precision| ±5% (FVC)
Frequency setting mode| Digital setting, analog setting, pulse frequency setting, serial communication setting, multi- step speed setting & simple PLC, PID setting, etc. These frequency settings can be combined & switched in various modes.
Overload capacity| G model: 150%/60s, 180%/3s. P model: 120%/60s, 150%/3s.
Torque boost| Automatically torque boost; manually torque boost: 0.1%~30.0%
V/f curve| Three types: linear, multiple point and square type (1.2 power, 1. 4 power, 1.6 power, 1.8 power, square)
V/f separate| Two types: completely separate and partially separate.
Acceleration/decele ration mode| Straight line or S curve; four kinds of acceleration/ deceleration time, range: 0.0s~6500.0s
**** DC braking| DC braking frequency: 0.0Hz~maximum frequency, braking time: 0.0s~36.0s braking current: 0.0%~100.0%
Jog operation| Jog operation frequency: 0.0Hz~50.00Hz
Jog acceleration/deceleration time: 0.0s~6500.0s
| Acceleration/decele ration mode| Straight line/S curve; four kinds of acceleration/deceleration time, range: 0.1s~65000s
---|---|---
Braking unit| 0.4~18.5kW: standard build-in.

18.5kW, additional one should be connected if necessary.
Simple PLC & multi-step speed operation| It can realize a maximum of 16 multi- step speeds running via the built-in PLC or control terminals.
**** Built-in PID| Built-in PID control to easily realize the close loop control of the process parameters (such as pressure, temperature, flow, etc.)
Automatic voltage regulation (AVR function)| Keep output voltage constant automatically when input voltage fluctuating
Over-voltage & over-current stall control| Limit current & voltage automatically during the running process, prevent frequent over-current & over-voltage tripping
Fast current limit function| Fast current limit, to make frequency inverter works normally.
Torque limit and control| “Rooter” characteristics, limit the torque automatically and prevent frequent over-current tripping during the running process.
Under FVC control model, it can realize torque control.







Featured functions

| Excellent control performance| Control the synchronous and asynchronous motor based on the high performance current vector control technology.
Keep running while temporary power off| While the temporary power off happens, the feedback energy will keep the load runs normally in a short time.
Virtual IO| 5 groups virtual DIDO can make simple logic control
Timing function| Build-in timing function, the setting time range is 0.0Min~6500.0Min
Multiple motors switching| Two groups of motor parameters, can realize four motors switching control.
Multiple encoders compatible| Optional for differential encoder and open- collector encoder.
  Run| Operation command channel| Keypad control Terminal control
Serial communication control (Modbus)
Frequency setting source| Digital setting, analog current setting, analog voltage setting, high speed pulse frequency setting, serial communication setting, multi-step speed setting & simple PLC, PID setting, etc. These frequency settings can be combined & switched in various modes.
Auxiliary frequency setting source| Realizes auxiliary frequency fine tuning and combining.
| ** Input terminals| Programmable digital inputs : DI1~DI5, DI5 can be set as high speed pulse input terminal (please point out if necessary while placing the order)
Programmable analog inputs : AI1, AI2: AI works with 0~10V signal. AI2 works with both 0~10V & 4~20mA.
Extension capacity:
5 digital input: (DI6~DI10) 1analog input (AI3), works with -10V~10V voltage (customized)
---|---|---
**
Output terminals| Programmable digital outputs :
1 relay output (TA1-TB1-TC1),
1 High speed pulse output (FM), works with 0~1000kHz square wave signal output (please point out if necessary while placing the order).
Programmable analog outputs : AO1, AO2: compile with both 0 ~ 10 V & 4~ 20 mA.
Extension capacity:
2 relay output: (TA2-TB2-TC2 and TA3-TB3-TC3)
Commun  ication| Communication terminals| Standard RS485 communication interface, support MODBUS-RTU communication protocol






Display and Keypad

| LED display| Display frequency setting, output frequency, output voltage, output current, etc. Two lines display
Keypad lock function| Lock the keypad partially or completely, to avoid incorrect operation


Fault protection function

| Comprehensive protections include over-current, over-voltage, under-voltage, overheating, default phase, overload, shortcut, etc., can record the detailed running status during failure & has fault automatic reset function
**** Optional spare parts| Braking sub-units, I/O extension card, Isolation RS485 communication card, differential PG card, UVW differential input PG card, open-collector PG card.







Environ- ment

| **** Installation place| Indoor, without direct sunshine, without dust, corrosive gases, inflammable gases, oil mist, steam, water drop or salinity etc.
Altitude| ≤1000M: output rated power, >1000M: output derated
Ambient temperature| -10℃~40℃ , higher then 40℃, output derated.
Humidity| 90%RH or less (non-condensing)
Vibration| ≤ 5 . 9 m/( s2 )( 0 . 6 g)
Storage temperature| -20℃~60℃

2.5 Product appearance diagram and installation diagram

2.5.2 Product appearance dimensions and installation dimensions list


Model

| Installation dimensions| Appearance dimension| Aperture
---|---|---|---
W1| H 1| W| H| D| Φ
3AC 380V ,50Hz/60Hz
4T11GB/15PB| 130| 287| 170| 300| 183| 6.5
4T15GB/18.5PB
4T18.5GB/22PB| 140| 318| 200| 330| 204| 6.5
4T22GB/30PB
4T30G/37P| 170| 370| 250| 390| 220| 6.5
4T37G/45P
4T45G/55P|
180| 452| 280| 470| 258| 9.0
4T55G/75P
4T75G/90P|
200| 535| 300| 550| 278| 9.0
4T90G/110P
4T110G/132P| 250| 576| 370| 600| 300| 9.0
4T132G/160P|
320| 744| 485| 768| 310| 13.0
4T160G/185P
4T185G/200P
4T200G/220P| ****
220+220| 955| 500| 992| 405| 13.0
4T220G/250P
4T250G/280P
4T280G/315P| ****
246.5+246.5| **** 1065| **** 650| **** 1097| **** 400| **** 13.0
4T315G/350P
4T350G/400P
4T400G/450P| 300+300| 1350| 700| 1384| 440| 16.0
4T450G/500P
4T500G/560P
4T560G/630P

2.6 Optional spare parts
If below spare parts are necessary, please point out while placing the order

Name Model Functions Remark
Build-in braking unit The Model has the mark of “B” 11~22kW build-in
standardly 3 0  ~ 75 KW optional       for build- in
External braking unit BCM series braking unit During fast braking process,
the feedback energy will be consumed by braking resistor.
Dynamic energy feedback unit RGU series energy feedback unit Feedback the
generated energy to grid power during the braking process.
I/O extension card 2 xxx-EXT2 3 digital input terminals will be added
RS-485 communication card xxx-EXT485 ****

Isolated RS-485 communication card

|
Differential encoder PG card| xxx-PG1| Differential encoder PG card, compatible with 5V/12V power supply.|
External connected LED keypad| xxx-EXTJP| External connected LED display and operated keypad, together with the keypad bracket.| RJ45 internet interface
Keypad extension cable| xxx-JPL2| **** Standard 8P8C internet cable| 2 meters in the packing box standardly

2.7 Routine Maintenance of Inverter
2.7.1 Routine Maintenance

The influence of the ambient temperature, humidity, dust and vibration will cause the aging of the devices in the inverter, which may cause potential fault of the inverter or reduce the service life of the inverter.
Therefore, it is necessary to carry out routine and periodical maintenance on the inverter.
Routine inspection Items include:

  1.  Whether there is any abnormal change in the running sound of the motor;
  2. Whether the motor has vibration during the running;
  3. Whether there is any change to the installation environment of the inverter:
  4. Whether the inverter cooling fan works normally;
  5.  Whether the inverter has over temperature.

Routine cleaning:

  1. The inverter should be kept clean all the time.
  2. The dust on the surface of the inverter should be effectively removed, so as to prevent the dust entering the inverter. Especially the metal dust is not allowed.
  3. The oil stain on the inverter cooling fan should be effectively removed.

2.7.2 Periodic Inspection

Please perform periodic inspection on the places where the inspection is a difficult thing.
Periodic inspection Iterns include:

  1. Check and clean the air duct periodically:
  2.  Check if the screws are loose:
  3. Check if the inverter is corroded:
  4.  Check if the wire connector has arc signs;
  5.  Main circuit insulation test.

Remainder: When using the megameter (DC 500V megameter recommended) to measure the insulating resistance, the main circuit should be disconnected with the inverter. Do not use the insulating resistance meter to test the insulation of control circuit. It is not necessary to conduct the high voltage test (which has been completed upon delivery).
2.7.3 Replacement of inverter vulnerable parts
The main vulnerable parts of inverter are capacitors and cooling fans, the working lifetime has strong relationship with the environment conditions and the maintenance status. In normal conditions, the working life time of them as below:

Parts name Working lifetime in normal conditions
Cooling fans 2~3 years
Capacitors 4~5 years

Please calculate working life based on specific usage

  1.  The cooling fan may be damaged due to: bearing wear and blade aging. Judging criteria: Whether there are cracks in the fan blades, etc., whether the sound has abnormal vibration when starting up.
  2. Filter electrolytic capacitor may be damaged causes: Input power quality is bad, ambient temperature is high, the load changes frequently, electrolytes are ageing.
    Judging criteria: Whether there is liquid leakage, whether the safety valve has protruded, the measurement of electrostatic capacitance, and the measurement of insulation resistance

2.7.4 Storage of Inverter
Upon acquiting the inverter, the user should pay attention to the following points regarding the temporary and long-term storage of the inverter

  1. Pack the inverter with original package and place back into the packing box of our company.
  2.  Long-term storage will degrade the electrolytic capacitor. Thus, the product should be powered up once every 2 years, each time lasting at least five hours. The input voltage should be increased slowly to the rated value with the regulator.

2.9 Instructions on Warranty of Inverter
Free warranty only applies to the inverter itself.

  1. Kecen provides 18 months warranty (starting from the date s indicated on the barcode) for the failure or damage under normal use conditions. If the equipment has been used for over 18 months, reasonable repair expenses will be charged

  2.  Reasonable repair expenses will be charged for the following situations within 18 months:
    a) The equipment is damaged because the user fails to comply with the requirements of the user’s manual;
    b) Damage caused by fire, flood and abnormal voltage;

  3.  Damage caused when the inverter is used for abnormal function
    The service expenses will be calculated according to the standard of the manufacturer. If there is any agreement, the agreement should prevail.

Installation and wiring

3.1 Mechanical Installation
3.1.1 Installation environment

  1. Ambient temperature: The ambient temperature exerts great influences on the service life of the inverter and is not allowed to exceed the allowable temperature range (-10°C to 50°C).
  2. The inverter should be mounted on the surface of incombustible articles, with sufficient spaces nearby for heat sinking. The inverter is easy to generate large amount of heat during the operation. The inverter should be mounted vertically on the base with screws
  3. The inverter should be mounted in the place without vibration or with vibration of less than 0.6G, and should be kept away from such equipment as punching machine.
  4. The inverter should be mounted in locations free from direct sunlight, high humidity and condensate
  5. The inverter should be mounted in locations free from corrosive gas, explosive gas or combustible gas
  6. The inverter should be mounted in locations free from oil dirt, dust, and metal powder.

Drive model

| Mounting clearances (mm)
---|---
B| A
≤ 15kW| ≥100| No limitation
18.5~30kW| ≥200| ≥50
≥37kW| ≥300| ≥50

3 .1.2 Heat dissipation should be taken into account during the mechanical installation. Please pay attention the following items:

  1.  Install the inverter vertically so that the heat may be expelled from the top. However, the equipment cannot be installed upside down. f there are multiple inverters, parallel installation is a better choice. In applications where the upper and lower inverters need to be installed, please refer to 3.1.2 “xxx Series
    Inverter Installation Diagram’” and install an insulating spliter.

  2. The mounting space should be as indicated as 3.1.2, 50 s to ensure the heat dissipation space of the inverter. However, the heat dissipation of other devices in the cabinet should also be taken into account

  3. The installation bracket must be flame retardant.

  4.  In the applications where there are metal dusts, it is recommended to mount the radiator outside the cabinet. In this case, the space in the sealed cabinet should be large enough

3.2 Electrical installation
3.2.1 Selection guide of electric parts

Inverter Model| Circuit Breaker (MCCB) (A)| Recommended Contactor A| Recommended Conducting Wire of Main Circuit at Input Side (mm2)| Recommended Conducting Wire of Main Circuit at Output Side (mm2)| Recommended Conducting Wire of Control Circuit (mm2)
---|---|---|---|---|---
4T11GB/15PB| 63| 40| 4.0| 4.0| 1.0
4T15GB/18.5PB| 63| 40| 6.0| 6.0| 1.0
4T18.5GB/22PB| 100| 63| 6| 6.0| 1.5
4T22GB/30PB| 100| 63| 10| 10| 1.5
4T30G/37P| 125| 100| 16| 10| 1.5
4T37G/45P| 160| 100| 16| 16| 1.5
4T45G/55P| 200| 125| 25| 25| 1.5
4T55G/75P| 200| 125| 35| 25| 1.5
---|---|---|---|---|---
4T75G/90P| 250| 160| 50| 35| 1.5
4T90G/110P| 250| 160| 70| 50| 1.5
4T110G/132P| 350| 350| 120| 120| 1.5
4T132G/160P| 400| 400| 150| 150| 1.5
4T160G/185P| 500| 400| 185| 185| 1.5
4T185G/200P| 600| 600| 1502| 1502| 1.5
4T200G/220P| 600| 600| 1502| 1502| 1.5
4T220G/250P| 600| 600| 1502| 1502| 1.5
4T250G/280P| 800| 600| 1852| 1852| 1.5
4T280G/315P| 800| 800| 1852| 1852| 1.5
4T315G/350P| 800| 800| 1503| 1503| 1.5
4T350G/400P| 800| 800| 1504| 1504| 1.5
4T400G/450P| 1000| 1000| 1504| 1504| 1.5
4T450G/500P| 1200| 1200| 1804| 1804| 1.5
4T500G/560P| 1200| 1200| 1804| 1804| 1.5
4T560G/630P| 1200| 1200| 1804| 1804| 1.5

3.2.2 Instructions of peripheral devices

Device Installation place Instructions
**** Circuit breaker **** Input side of inverter Purpose: disconnect power

supply and protect the equipment in case of abnormal overcorrect occurs Type selection: breaking current of circuit breaker is defined to be 1.5~2 times the rated current of the drive Breaking time characteristic of circuit breaker should be selected based on overload protection time characteristic of the drive
Contactor| Between circuit breaker and inverter input side| Switch ON/OFF the inverter, it is prohibited to switch on/off the power supply of inverter frequently (less than two times in one minute).
Input reactor| Input side of inverter| Improve power factor Reduce the impact of imbalanced three-phase input AC power supply on the system Suppress higher harmonics and reduce the conducted and radiated interference to peripheral devices Restrict the impact of impulse current on rectifier bridges
---|---|---
Input EMC filter| Input side of inverter| Reduce conducted interference from power supply to the drive, improve the immunity of the drive from noise Reduce conducted and radiated interference of the drive to peripheral device
DC reactor| 45~110KW standard build-in| Increase the input side power factor, increase the inverter working efficiency and thermal stability. It can eliminate the input higher harmonics, and also reduce the conduction and radiation interference to external devices.
Output reactor| Between the inverter output side and motor (install it close to inverter).| Avoid the motor insulation damage result from harmonic voltage Reduce frequent protection from the drive caused by leakage current In case the cable connecting drive and motor is over 100 meters, output AC reactor recommended

  • Do not install the capacitor or surge suppressor at the output side of the inverter, otherwise it may cause inverter failure or capacitor and surge suppressor damaged
  • The Inverter input / output (main circuit) contains harmonic components, it may interfere with inverter accessories communications equipment. Therefore, please install anti-interference filter to minimize interference.
  • The details of external devices and accessories selection refer to the manual of external devices

3.2.3 Wiring diagram
Main circuit wiring diagram

3.2.4 Description of inverter main circuit terminals.

Terminals Name Description
R, S, T Three phase power supply terminals Terminals for three phase power

supply
P+, P-| DC Bus +, – terminals| External terminals of DC Bus, used to connect braking unit.
P+, PB| Braking resistor terminals| Terminals for connecting braking resistor
U, V, W| Output terminals| Connect to three phase motor
E| Ground connection terminal| Connect to ground

Principle of wiring connection

  1. Terminals R, S, T are input side power supply terminals, no phase sequence requirement

  2. DC bus P+ and P- terminals: Please note that after the power switching off, the DC bus P+ and P- terminals still have residual voltage. It must be confirmed that the voltage s less than 36V, otherwise there is danger of electric shock. When using an exteral brake component above 90KW, be careful that the P+ and P- polarity cannot be reversed, otherwise the inverter may be damaged or even causing fire The wiring length of the brake unit should not exceed 10m. Twisted pair o tight two-wire parallel wiring
    should be used. Do not connect the braking resistor directly to the DC bus, which may cause damage to the inverter or even causing fire.

  3. Braking resistor connection terminals P+, PB:
    Models with a built-in brake unit below 22 kW or models with a built-in brake unit of 30~75kW have these two terminals. The selected braking resistor must follow the recommended value, and the wiring distance should be less than 5m, otherwise it may damage the inverter.

  4. Inverter output terminals U, V, W:
    The capacitor or the surge absorber cannot be connected to the output side of the inverter, otherwise the failures will happen frequency or cause the inverter be damaged. When the motor cable is too long, due to the influence of distributed capacitance, itis easy to generate electrical resonance, which may cause motor insulation damage or generate large leakage current to protect the inverter from overcurrent. When the motor cable length is longer than 100m, an AC output reactor must be installed.

  5.  the grounding terminal
    The terminals must be reliably grounded and the ground wire resistance must be less than 0.10Q Otherwise it may cause the inverter works abnormally or even damage the equipment. Do not share the ground terminal with the power supply neutral N terminal

3 .2.5 Wiring diagram of control circuit

3.2.6 Control terminals and connections

  1. Layout of control terminals

  2. Description of Control Terminals Function
    Type| Terminal
    Symbol| Terminal Name| Function Description
    ---|---|---|---
    Power
    supply| +10V-GND| +10V power
    supply| 1.Provide +10V power supply for external units, and the maximum output current is lOrnA.
    2.It is generally used as the operating power supply for the
    external potentiometer. The potentiometer resistance range is 1k0-5k0 .
    24V-COM| +24V power
    supply| 1.Provide +24V power supply for external units.
    2.It is generally used as the operating power supply for
    digital input/output terminals and the external sensor. The maximum output current is 100mA
    OP| External 24V
    power input
    terminal| 1.Short conned with 24V as default.
    2.When external signal is used to drive DI1 – 015, OP needs to connect to the external power supply and disconnect from the +24V power terminal
    Analog Input| Alt -GND| Analog input
    terminal 1| 1,input voltage range: DC -10V-10V
    2,input resistance: 22ko
    Al2-GND| Analog input
    terminal 2| 1,input range: DC 0V-10V/4-20mA signal changed by J8 jumper on control board.
    2,input resistance: voltage signal is 22ko , current signal is 500o
    Digital
    Input| D11-0P| Digital input 1| 1.Optical coupling isolation, compatible with both PNP and NPN input
    2.Input impedance’ 4k0
    3.Voltage range for level input: 9V-30V
    4.015 terminal can work at both digital input and high speed
    012-OP| Digital input 2
    013-OP| Digital input 3
    014-OP| Digital input 4
    |

DI5-OP

|

Digital input 5

| pulse (maximum input frequency is 100kHz) input. High speed pulse terminal is optional; please point out while placing the order.
---|---|---|---
Digital Output| DO1-CME| open collector output| 1. Compile with both PNP and NPN output;
2. External connection voltage range: 0~24V
3. Output current range: 0~50mA
Note: terminals CME and COM are isolated internally. J10 is used to short connect CME and COM as default ( DO1 is driven by 24V)
If DO1 will be driven by external power supply, the jumper must be removed firstly.

FM-CME

| High speed pulse output| The output type is controlled by parameter P5-00, if set as high speed pulse output, the maximum output frequency is 100kHz. If set as open collector output, it has the same specification as DO1

Analog Output

| AO1~GND| Analog output 1| Output range: DC 0~10V/4~20mA, determined by jumper J5 on the control board.
AO2~GND| Analog output 2| Output range: DC 0~10V/4~20mA, determined by jumper J9 on the control board.
Relay Output 1| TA1-TB1| Normally close output| Driving capacity:

AC 250V/3A, cosØ=0.4 DC 30V/1A

TA1-TC1| Normally open output
Relay Output 2|

TA2-TC2

| Normally close output
RS485| A+| Modbus terminals| Communication interface of Modbus, it is suggested to use twisted-pair cable or shielded cable.
B-
Inter -face| J12| Extension cards interface| Optional cards as, I/O extension card, isolated RS485 communication card etc.
J3| PG card interface| Open-collector PG card, differential PG card etc.
J7| Extension keypad interface| Used to connect extension keypad
3. Principle of wiring connection for control cables
(1) Analog input terminals
•  Don’t put the power cables and control cables in one wire casing, otherwise it will cause interferences
• please use shield cables for control circuit, and it is suggested to use 1mm? shield cables
• Don’t make the analog signal cables’ length longer than 20 meters.

•  Incase if the analog signals are severely interfered, afilter capacitor or a ferrite core is required on the analog signal source side.

  1. Digital input terminals
    Generally, shielded cables are required, and the wiring distance should be as short as possible, not more than 20m. When the active mode is selected, the necessary filtering measures should be taken for the crosstalk of the power supply. Contact control is recommended.

• NPN connection
This is one of the most common wiring methods. If an external power supply is used, the jumper between +24 and OP must be removed, the positive pole of the exteral power supply is connected to the OP terminal, and the negative pole of the external power supply is connected to the CME terminal
Note: Under this type of wiring, the DI digital input terminals of different inverters cannot be used in parallel, otherwise the DI digtal input terminals may be malfunctioned. If the DI digital input terminals are connected in parallel (between different inverters), it needs connect a diode at the DI input terminal (the positive pole of diode connect to digital input terminal side) 1. The diode must meet: IP>10mA, UP<1V, as shown below.
• PNP connection

This type of wiring must remove the short connected sheet between +24V and OP and connect +24V to the common terminal of the external controller. At the same time, OP and COM are connected. If an external power supply is used, the short connected sheet between CME and COM must also be removed. (3) control signal output terminals wiring instructions DO digital output terminals When the digital output terminal needs to drive the relay, an absorbing diode should be installed on both sides of the relay coil. Otherwise, it may cause damage to the DC 24V power supply. The drive capacity is no more than 50mA.
Note: Be sure to properly install the polarity of the absorption diode. As shown below. Otherwise, when the digital output terminal has an output, the DC 24V power supply will be burned out immediately.
Operation and Display

4.1 Keypad Description
With the operation keypad, it can perform such operations on the inverter s function parameter modification, working status monitor and running control (start and stop).

4.1.1 Function keys description

Functional indicator Description
RUN Light-on: inverter is running; Light-off: inverter is stopped.
FWD/REV Light-on: inverter is reverser running.
**TUNE/TC** Light-on: inverter is under torque control mode; Light

flickering slowly: inverter is under auto-tuning; Light flickering quickly: inverter is under fault status.


LOCAL/REMOT

| Light-on: inverter is under terminal control mode;
Light flickering: inverter is under communication control mode; Light-off: inverter is keypad control mode.
---|---
Hz| Unit of frequency
A| Unit of current
V| Unit of voltage
RPM (Hz+V)| Unit of speed
% (A+V)| Percentage


5 bits of LED

| ****

Can display setting frequency, output frequency, various monitoring data and alarm code.

4.1.2 Keypad push-button description

Button Name Function
**PRG** **** Programming key **** Entry and exit of primary menu
**ENT** Confimation key **** Progressively enter menu, and confirm

parameters
| Increment key| Progressively increase of data or function codes
| Decrement key| Progressively decrease of data or function codes
**
SHIFT| ** Shift key| Select the displayed parameters in turn on the stop display interface and running display interface, and select the modification bit of parameters when modifying parameters.
**RUN| ** Running key| Start to run inverter under keyboard control mode
**
STOP/ RESET| ** Stop / Reset| Stop inerter in running status and reset operation in fault alarm status. The reactions are controlled by P7-02.
JOG| Multi-function selection key| The corresponding functions are defined by P7-01.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

global sources User Manuals

Related Manuals