UNITRONICS Vision OPLC PLC Controller User Guide
This guide provides basic information for Unitronics’ controllers V560-T25B.
General Description
V560 OPLCs are programmable logic controllers that comprise a built-in operating panel containing a 5.7” Color Touchscreen. The V560 offers an alpha- numeric keypad with function keys as well as a virtual keyboard. Either may be used when the application requires the operator to enter data.
Communications
- 2 isolated RS232/RS485 ports
- Isolated CANbus port
- The user can order and install an Ethernet port
- Communication Function Blocks include: SMS, GPRS, MODBUS serial/IP Protocol FB enables PLC to communicate with almost any external device, via serial or Ethernet communications
I/O Options
V560 supports digital, high-speed, analog, weight and temperature measurement I/Os via:
- Snap-in I/O Modules Plug into the back of the controller to provide an on-board I/O configuration
- I/O Expansion Modules Local or remote I/Os may be added via expansion port or CANbus.
Installation instructions and other data may be found in the module’s technical specification sheet.
Information Mode
This mode enables you to:
- Calibrate the touchscreen
- View & Edit operand values, COM port settings, RTC and screen contrast/brightness settings
- Stop, initialize, and reset the PLC
To enter Information Mode, press the button, or press the touchscreen and maintain contact for several seconds.
Programming Software, & Utilities
The Unitronics Setup CD contains VisiLogic software and other utilities
- VisiLogic Easily configure hardware and write both HMI and Ladder control applications; the Function Block library simplifies complex tasks such as PID. Write your application, and then download it to the controller via the programming cable included in the kit.
- Utilities These include UniOPC server, Remote Access for remote programming and diagnostics, and DataXport for run-time data logging.
To learn how to use and program the controller, as well as use utilities such as Remote Access, refer to the VisiLogic Help system.
Removable Memory Storage
SD card: store datalogs, Alarms, Trends, Data Tables; export to Excel; backup
Ladder, HMI & OS and use this data to ‘clone’ PLCs.
For more data, refer to the SD topics in the VisiLogic Help system.
Data Tables
Data tables enable you to set recipe parameters and create datalogs.
Additional product documentation is in the Technical Library, located at
www.unitronicsplc.com.
Technical support is available at the site, and from support@unitronics.com.
Standard Kit Contents
- Vision controller
- 3 pin power supply connector
- 5 pin CANbus connector
- CAN bus network termination resistor
- Battery (not installed)
- Mounting brackets (x4)
- Rubber seal
- Extra set of keypad slides
Danger Symbols
When any of the following symbols appear, read the associated information carefully.
Environmental Considerations
Inserting the Battery
In order to preserve data in case of power-off, you must insert the battery.
The battery is supplied taped to the battery cover on the rear of the
controller.
- Remove the battery cover shown on page 4. The polarity (+) is marked on the battery holder and on the battery.
- Insert the battery, ensuring that the polarity symbol on the battery is: – facing up – aligned with the symbol on the holder
- Replace the battery cover.
Mounting
Dimensions
Note that the LCD screen may have a single pixel that is permanently either black or white.
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
Wiring
Wiring Proced
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 2–3.31 mm2).
- Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
- Unscrew the terminal to its widest position before inserting a wire.
- Insert the wire completely into the terminal to ensure a proper connection.
- Tighten enough to keep the wire from pulling free.
Power Supply
The controller requires either an external 12 or 24VDC power supply. Permissible input voltage range: 10.2-28.8VDC, with less than 10% ripple.
Earthing the OPLC
To maximize system performance, avoid electromagnetic interference by:
- Mounting the controller on a metal panel.
- Connect the functional earth terminal of the OPLC, and the common and ground lines of I/Os, directly to the earth ground of your system.
- For ground wiring, use the shortest and thickest possible wire.
Communication Ports
This series comprises a USB port, 2 RS232/RS485 serial ports and a CANbus
port.
▪ Turn off power before making communications connections.
Caution ▪ Always use the appropriate port adapters.
The USB port may be used for programming, OS download, and PC access.
Note that COM port 1 function is suspended when this port is physically
connected to a PC.
The serial ports are type RJ-11 and may be set to either RS232 or RS485 via
DIP switches, in accordance with the table shown below.
Use RS232 to download programs from a PC, and to communicate with serial
devices and applications, such as SCADA.
Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show PLC port signals.
To connect a PC to a port that is set to RS485, remove the RS485 connector,
and connect the PC to the PLC via the programming cable. Note that this is
possible only if flow control signals are not used (which is the standard
case).
*Standard programming cables do not provide connection points for pins 1 and 6.
**When a port is adapted to RS485, Pin 1 (DTR) is used for signal A, and Pin 6
(DSR) signal is used for signal B.
RS232 to RS485: Changing DIP Switch Settings
The ports are set to RS232 by factory default.
To change the settings, first remove the Snap-in I/O Module, if one is
installed, and then set the switches according to the following table.
RS232/RS485: DIP Switch Settings
The settings below are for each COM port.
*Default factory setting
**Causes the unit to function as an end unit in an RS485 network
Removing a Snap -in I/O Module
- Locate the four screws on the sides of the controller, two on either side.
- Press the buttons and hold them down to open the locking mechanism.
- Gently rock the module from side to side, easing the module from the controller.
Re-installing a Snap-in I/O Module
1. Line the circular guidelines on the controller up with the guidelines on
the Snap-in I/O Module as shown below.
2 Apply even pressure on all 4 corners until you hear a distinct ‘click’. The
module is now installed. Check that all sides and corners are correctly
aligned.
CANbus
These controllers comprise a CANbus port. Use this to create a decentralized
control network using one of the following CAN protocols:
- CANopen: 127 controllers or external devices
- CANLayer 2
- Unitronics’ proprietary UniCAN: 60 controllers, (512 data bytes per scan)
The CANbus port is galvanically isolated.
CANbus Wiring
Use twisted-pair cable. DeviceNet® thick shielded twisted pair cable is
recommended.
Network terminators: These are supplied with the controller. Place terminators
at each end of the CANbus network.
Resistance must be set to 1%, 121Ω, 1/4W.
Connect ground signal to the earth at only one point, near the power supply.
The network power supply need not be at the end of the network.
CANbus Connector
Technical Specifications
This guide provides specifications for Unitronics’ controller V560-T25B, which comprises a built-in operating panel containing a 5.7” color touchscreen and an alpha-numeric keypad with function keys. You can find additional documentation on the Unitronics’ Setup CD and in the Technical Library at www.unitronics.com.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided “as is” without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non- infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R”G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
Read More About This Manual & Download PDF:
References
- Home - Unitronics
- Home - Unitronics
- Unitronics- Programmable Logic Controller + Built-in HMI
- Unitronics- Programmable Logic Controller + Built-in HMI
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>